Title: BALLOREX


1
BALLOREX
Dynamic balancing valves DN 15 - 32
  • APPLICATIONS
  • Central heating and district heating
  • systems
  • - BALLOREX is used in the installation.
  • Air conditioning
  • - BALLOREX on cooling and heating pipes.

LCJ May 2001
2
BALLOREX
Dynamic balancing valves DN 15 - 32
  • BALLOREX QP M
  • QP for flow and pressure
  • - Setting of max. Flow
  • - Balancing the differential pressure
  • - Range from 10 40 kPa
  • M for measuring
  • - Shut off of the risers
  • - Flow measuring
  • - Draining / filling
  • - Temperature measuring
  • - Connection of capillary

LCJ May 2001
3
BALLOREX
Dynamic balancing valves DN 15 - 32
  • FUNCTION
  • Flow and differential pressure control
  • - Flow is set by the means of the baffle ring
  • - Max. differential pressure i set by the
    means of
  • an allen key
  • Differential pressure control
  • - Measured through the callibary
  • - Minimising the differental pressure across
    the
  • heating system or unit
  • Locking nut
  • - Secures the setting
  • Shut off handle
  • - Quater turn shut off of the risers

Locking nut
Flow regulation
Differential pressure
Shut off handle
Capillary
LCJ May 2001
4
BALLOREX
Dynamic balancing valves DN 15 - 32
4
3
  • BALLOREX QP
  • Scale for setting of differential pressure
  • Protection cap
  • Handle for setting of max. flow
  • Lock nut for fixing the setting
  • Baffle for flow control
  • Connection for capillary from the return
  • Membrane

5
6
7
1
2
LCJ May 2001
5
BALLOREX
Dynamic balancing valves DN 15 - 32
  • BALLOREX QP M
  • For two-pipe system
  • QP always installed in the flow
  • QP always connected to BALLOREX M by
  • the means of the capillary
  • When using BALLOREX Flowmeter, 5 x DN
  • straight pipe is required to BALLOREX M
  • Max. working pressure 10 bar
  • Max. differential pressure 2 bar
  • Max. water temperature 120 C0

LCJ May 2001
6
BALLOREX
Dynamic balancing valves DN 15 - 32
Example Required pressure drop 20 kPa and
Qmax 0,14 l/s From the intersection
between the wanted differential pressure and max.
Water flow the graph is follewed to the right for
reading of spindle position. The spindle is
adjusted in position 4
Setting of differential pressure

?Pa
LCJ May 2001
7
BALLOREX
Dynamic balancing valves DN 15 - 32
Example Spindel for setting of ?Pa is adjusted
to position 4 Required Qmax 0,14 l/s From the
intersection between the wanted differential
pressure and max. Water flow the graph is
follewed to the right for reading of baffle
position Setting III at ?Pb
Flow control
?Pa
?Pb
LCJ May 2001
8
BALLOREX
Dynamic balancing valves DN 15 - 32
Heating system with BALLOREX
LCJ May 2001
9
BALLOREX
Dynamic balancing valves DN 15 - 32
  • BALLOREX Q
  • Controls the water flow between
  • individual risers
  • For use in one-pipe heating systems
  • Can be mounted in the flow or in the
  • return
  • Secures correct distribution of water flow

LCJ May 2001
10
BALLOREX
Dynamic balancing valves DN 15 - 32
  • FUNCTION
  • Flow control
  • - Flow is set by the means of the baffle ring
  • Controls the differential pressure across the
  • Valve
  • - Differential pressure is set by the means of
    an
  • Allen key

Flow regulation
Locking nut
Differential pressure
LCJ May 2001
11
BALLOREX
Dynamic balancing valves DN 15 - 32
Example Required Qmsx 0,125 l/s The spring
for the differential pressure (scale value) must
be set lowest possible e.g. position 2 (reduces
the pressure drop over the valve) At the
intersection between the graph position 2 and the
wanted water flow, the graph is followed to
reading of baffle position III
Flow control
LCJ May 2001
12
BALLOREX
Dynamic balancing valves DN 15 - 32
  • BENEFITS
  • Regardsless of pressure changes in the
  • system
  • (Keeps the set flow)
  • Range 10-40 kPa
  • Both for one and two-pipe heating systems
  • Both flow and differential pressure control
  • Measuring during setting
  • BALLOREX Q can be installed both in the
  • flow and the return line

LCJ May 2001