Aircraft Cargo - PowerPoint PPT Presentation

About This Presentation
Title:

Aircraft Cargo

Description:

... fire signatures that could be used to discriminate between actual fires and ... Not all fires transition through a small smoldering state. ... – PowerPoint PPT presentation

Number of Views:200
Avg rating:3.0/5.0
Slides: 53
Provided by: daveb3
Category:
Tags: aircraft | cargo | fire

less

Transcript and Presenter's Notes

Title: Aircraft Cargo


1
International Aircraft Systems Fire Protection
Working Group Atlantic City, NJ October 30-31,
2002
Aircraft Cargo Compartment Fire Detection
David Blake FAA Technical Center Atlantic City
Airport, NJ. 08405 Phone 609-485-4525 email
dave.blake_at_faa.gov
2
Cargo Compartment Fire Detection Project
Objective
  • - Standardize the fire(s) that should be detected
    (smoke, gas, heat output)
  • - Provide guidelines for the certification of
    newer technology detectors (multi sensor or other
    nuisance alarm rejection techniques) to reduce
    the false alarm rate (1001)

3
  • Federal Aviation Regulation
  • Part 25.858 Cargo Compartment Fire Detection
    Systems.
  • If certification with cargo compartment fire
    detection provisions is requested, the following
    must be met for each cargo compartment with those
    provisions
  • The detection system must provide a visual
    indication to the flight crew within one minute
    after the start of a fire.
  • The system must be capable of detecting a fire at
    a temperature significantly below that at which
    the structural integrity of the airplane is
    substantially decreased.
  • There must be means to allow the crew to check in
    flight, the functioning of each fire detector
    circuit.
  • The effectiveness of the detection system must be
    shown for all approved operating configurations
    and conditions.

4
FAA Technical Standard Order (TSO) C1c
7/10/87 Cargo Compartment Fire Detection
Instruments References a Society of Automotive
Engineers (SAE), Aerospace Standard AS 8036 Type
I Carbon Monoxide, Alarm level 200 /- 50
ppm. Type II Photoelectric, Alarm level 60-96
light transmission/foot. Type III Visual, Alarm
level 70 /- 10 light transmission/foot. Type
IV. Ionization, Alarm level 60-96 light
transmission/foot.
5
FAA Advisory Circular 25-9A Smoke Detection,
Penetration, and Evacuation Tests and Related
Flight Manual Emergency Procedures. Section
10.a.(2) A smoldering fire producing a small
amount of smoke in conjunction with the
applicable detection time has been selected as a
fire or failure condition that could be detected
early enough to ensure that the fire and smoke
procedures would be effective. Subjective
judgment, considering the failure , size of
compartment, materials contained in the
compartment, and the containment methods and
procedures, is needed to asses the significance
of a small amount of smoke.
6
Target Smoke Level for Certification with
Existing Regulations
7
False Alarm Issue
Source FAA Service Difficulty Reports, FAA
Accident/Incident database, NTSB reports.
8
(No Transcript)
9
(No Transcript)
10
The NTSB has issued numerous safety
recommendations to the FAA based on a study
conducted on aircraft emergency evacuations. One
of the recommendations (A-00-91) is as
follows Document the extent of false
indications for cargo smoke detectors on all
airplanes and improve the reliability of the
detectors. The FAA Administrator responded to
the above recommendation in a letter dated
11/8/00. An excerpt from this letter is the
FAA is sponsoring a program to produce a standard
means of testing detectors to demonstrate
compliance with regulatory response requirements
and to develop reliable aircraft smoke and fire
detection systems that reduce the cargo
compartment false alarm rate. The WJHTC tests
will quantify typical gaseous compounds and
particulate resulting from cargo fires that can
be detected. These data can then be used to
standardize the procedures used to certify
multiple sensor cargo fire detection systems. The
FAA has been working with the WJHTC to ensure
that the information obtained from the testing
will lead to the development of appropriate
guidance and certification criteria.
11
Starting point was the same quantity of smoke
previously used in certification tests in small,
narrow body cargo compartments.
707 Forward Compartment. 910 cubic feet
Rosco 1600. 10.5 ml/min.
12
  • Fire Source Criteria
  • Good repeatability.
  • Immediate plume of smoke and gases.
  • Ability to generate all the products of
    combustion from actual luggage fires.
  • Ability to run the fire source in a cone
    calorimeter hood to accurately measure the heat
    release rate, mass loss rate and generation rate
    of the products of combustion.
  • Ability to remotely activate the fire source in
    an unoccupied compartment.

13
Nylon Polyethylene Polyurethane Polystyrene PVC PB
T
Standardized Fire Source
14
Smoldering Fire (Pyrolysis)
Spark Igniters, 2 ml heptane
Flaming Fire
15
SMOLDERING RESIN BLOCK FLAMING RESIN BLOCK ROSCO
SMOKE GENERATOR
16
707 Cargo Compartment
Ceiling Smoke Meters
Resin Block/Rosco Location
17
Smoke generated for 60 seconds. Smoke source
stopped and a mixing fan was turned on for 4
additional minutes. The purpose of the mixing fan
was to allow the measurement of the total
quantity of smoke produced by eliminating
buoyancy effects.
18
(No Transcript)
19
Smoldering Resin Alarm Times (Seconds) Detector
A 69 Detector B 66 Detector C 33 Detector D
36 Detector E 30 Detector F 36
Resin Block
20
Resin Block
Smoldering Resin Alarm Times (Seconds) Detector
A 101 Detector B 69 Detector C 64 Detector D
85 Detector E No alarm Detector F 119
21
Flaming Resin Alarm Times (Seconds) Detector A
56 Detector B 150 Detector C 39 Detector D
45 Detector E 32 Detector F 36
Resin Block
22
Resin Block
Flaming Resin Alarm Times (Seconds) Detector A
70 Detector B 61 Detector C 52 Detector D
65 Detector E 81 Detector F 100
23
Cone Calorimeter with FTIR gas analysis
24
Cone calorimeter/FTIR
25
Cone calorimeter/FTIR
26
Cone calorimeter/FTIR
27
Cone calorimeter/FTIR
28
Cone calorimeter/FTIR
29
Cone calorimeter/FTIR
30
(No Transcript)
31
(No Transcript)
32
(No Transcript)
33
(No Transcript)
34
(No Transcript)
35
Smoldering fire source produces similar light
obscuration values as previously used smoke
sources for certification tests. It does not
produce any other measurable fire signatures that
could be used to discriminate between actual
fires and nuisance alarm sources.
36
Volume 3500 cubic feet. Ventilation 850 CFM
DC-10 Below Floor Cargo Compartment
37
Detector Alarm Time A
140 B 112 C
No Detection D No
Detection Alarm time is the average of 2 tests.
Compartment volume 3500 cubic
feet Ventilation850 CFM
Flaming Resin
Resin Block
38
Detector Alarm Time A
107 B 056 C
No Detection D No
Detection Alarm time is the average of 2 tests.
Compartment volume 3500 cubic
feet Ventilation850 CFM
Flaming Resin
Resin Block
39
Flaming Resin Block
40
(No Transcript)
41
Signatures of Various Fire Sources in 707 Lower
Cargo Compartment.
42
(No Transcript)
43
(No Transcript)
44
(No Transcript)
45
(No Transcript)
46
(No Transcript)
47
(No Transcript)
48
AC 25-9A specifies a smoldering fire producing a
small amount of smoke as the fire that should be
detected within one minute. The origin of that
statement was the desire to detect a fire before
it could grow to a size that was uncontrollable.
Not all fires transition through a small
smoldering state. Ignition of flammable fluids
goes directly into a flaming fire mode and may
produce little smoke initially. This type of fire
is more threatening to an airplane and would not
be detected quickly with detectors that only
respond to particulates.
49
Cargo Liner Burnthrough Test Requirement. Minimum
Flame Temperature 1600 F. Minimum Heat Flux
7.5 BTU/ft2-sec. Test Duration 5
minutes Approximate Heat Release Rate 50
KW Flaming Resin Heat Release Rate 1 KW
50
Halon Replacement Minimum Performance
Standards 2 X 2 Pan Fire with 0.5 gallons Jet
A Must be Extinguished/Suppressed within 30
Seconds. Approximate Heat Release Rate 200
KW Flaming Resin Heat Release Rate 1 KW
51
  • Project Status
  • Flaming resin meets criteria for repeatability,
    generation of other fire signatures, remote
    activation and immediate plume.
  • Smoldering resin does not meet all criteria. True
    smoldering sources exist but also do not meet all
    criteria.
  • Flaming resin produces appropriate smoke and
    gases to be detected within one minute in small
    narrow body below floor compartments.
  • Flaming resin does not produce sufficient smoke
    and gases to be detected within one minute in
    large ventilated compartments.

52
  • Recommended Direction
  • Use the flaming resin block as the standard fire
    for detection.
  • Develop simulants for the smoke, heat and gases
    produced by the flaming resin block.
  • Scale appropriate detection time limits based on
    cargo compartment volume and ventilation rates.
Write a Comment
User Comments (0)
About PowerShow.com