VdS Schadenverhütung GmbHJörg Wilms-Vahrenhorst
INSPECTION OF SPRINKLER SYSTEMS AFTER 12,5 / 25
YEARS OF OPERATION
www.vds.de
2
(No Transcript)
3
(No Transcript)
4
(No Transcript)
5
(No Transcript)
6
Inspection procedure
  • Guidelines for design and installation of
    sprinkler systems
  • CEA 4001/ VdS CEA 4001, Cl. 18
  • EN 12845, Annex K (informative)
  • Leaflet Maintenance of operational readiness
    VdS 2091

7
Inspection procedure
  • Inspection
  • sprinklers and pipework, random test
  • the expert is responsible
  • Inspection time
  • dry pipe systems after 12,5 years of operation
  • wet pipe systems after 25 years of operation

8
Sprinkler inspection
9
Sprinkler inspection
10
Sprinkler inspection Laboratory VdS
Schadenverhütung
11
Statistics Sprinkler inspection
  • Wet pipe systems
  • positive (68)
  • negative (32)
  • Dry pipe systems
  • positive (67)
  • negative (33)

12
(No Transcript)
13
(No Transcript)
14
inspection of the pipework
15
Check of pipework Laboratory and Inspection
Services
16
Inspection of pipework Laboratory and Inspection
Services
17
Classification of damage
18
Statistics of inspection of pipework
Class 1
Class 2
Class 3
wet pipe systems
dry pipe systems/12,5
19
Faults
Dry pipe systems 1. Corrosion products / deposits
in the main pipes 2. Deposits in the branch pipes
Wet pipe systems 1. Corrosion products / deposits
in the main pipes
  • Sprinkler test
  • K-factor reduction
  • Lodgement / destruction of the spray pattern
  • No release at 1 bar

20
Result / Summary
  • The inspection of old sprinkler systems is
    important in order to find out whether corrosion
    products and deposits which cannot be seen in
    periodical inspections influence the efficiency
    of the sprinkler system.
  • Are the sprinkler characteristics (temperature,
    K-Faktor) conform to the requirements .
  • It is very risky for the experts to issue a
    report about the reliability and efficiency, if
    this special inspection has not been carried out.
  • From inspecting old sprinkler systems the experts
    gather important knowledge for the installation
    of new systems and for updating the relevant
    guidelines.