1
Power Supply Regulation
  • WBS 1.1.3 Power Supply System
  • Level 3 Manager
  • Nancy Grossman
  • FNAL
  • June 28, 2001

2
Overview of Regulation Needs
  • 7 Magnet Strings with regulation requirements
    ranging from 55 ppm to 400 ppm.
  • 55 ppm means /- 55 ppm relative to the flattop
    operating current (RMS).
  • V105 string requirement is 60 ppm, close to the
    tightest requirement.
  • Discussion will center around simulations of the
    V105 string.
  • 3 sources of current variation for magnet
    strings
  • 720 Hz power supply voltage ripple being applied
    to the magnets.
  • Line voltage changes.
  • Load changes.
  • Simulations of a particular power supply (or
    series of power supplies) can be used to see the
    effects of these changes on the resulting flattop
    current.

3
720 Hz Ripple Effect
  • 720 Hz line ripple effect on the PS currents is
    shown in the table below.
  • Not acceptable
  • Need filters for each string
  • Refurbish existing filters
  • Have costed 3, have claimed 7 for NuMI.
  • Estimated cost to remove, refurbish and install
    10k/string (extra 40K)

4
Line Voltage and Load Changes
  • Simulations were run for the NuMI V105 string,
    assuming a constant reference voltage.
  • 5 change in line voltage was easily
    corrected for at the level of 25 ppm
  • with standard voltage regulation. (most
    variation one would expect)
  • 5 load change (resistance) gave a 240 ppm
    current variation.
  • Corresponds to about a 100 C change in the copper
    in the magnet or the LCW changing 150C
  • Other magnet strings would have similar results
    most likely.
  • Not acceptable.
  • Need additional regulation.
  • HOLEC transductor (5K/string)
  • Special FNAL regulation electronics (5K/string)
  • Both are designed and installed in the Main
    Injector
  • This combination of electronics would give
    another factor of 2 120 ppm

5
Line Voltage and Load Changes
  • Three strings are still above the required
    specifications.
  • So now what?

6
Additional Factor of 2 - 4
  • Bandwidth
  • Each string will be tuned for maximum bandwidth.
  • 20 Hz is assumed in the previous calculations.
  • 40 Hz is frequently achieved (but not
    guaranteed).
  • Gives a factor of 2 in current stability.
  • Auto-tune
  • Load changes are typically slow changes and thus
    Auto-tune can correct for these.
  • One could then argue why do you need the extra
    power supply regulation too?
  • Auto-tune does not always work.
  • Needs beam and working beam position monitors to
    work.
  • Assumes next beam pulse like the previous one.
  • Experience at FNAL where significant beam control
    is needed says do both.
  • Since the power supply regulation is also driven
    some by groundwater concerns, we want something
    that is always working.

7
Other Primary Beam Power Supplies
  • Quadropole power supplies (20 KW PEIs)
  • Standard regulation is at /- 0.05 of the
    maximum current (100 or 200 amps)
  • Corresponds to up to /-0.44 variation in
    operating current.
  • Believed to be sufficient.
  • Main Injector Trim Magnet power supplies
  • Standard regulation is at /- 0.1 of the maximum
    current (15 amps)
  • Believed to be sufficient.

8
Summary
  • NuMI power supply regulation levels will be
    achieved by
  • Filters on all 7 strings.
  • HOLEC and FNAL Electronics on all 7 strings.
  • Auto-tune.
  • Tuning for maximum bandwidth.
  • Cost increase to NuMI
  • 40k for 4 additional filters (refurbished)
  • 70k for 7 sets of HOLEC/regulation electronics
    (one for each string)
  • Other slightly less expensive (and perhaps more
    effective) options may be designed by Fermilab
    before NuMI runs, in which case we would
    certainly use them.
  • Studies in the Main Injector P1 line will also
    help us to better define the level of regulation
    one obtains with a HOLEC transductor and special
    regulation electronics.