Title: MSA GasGard XL Controller
1MSA GasGard XL Controller
2GasGard XL Controller
Multi-channel, wall-mounted economical controller
for all of your gas monitoring needs. A
practical partner for hazardous gas monitoring.
3GasGard XL Controller
- Features and Benefits
- Expandable up to 8 channels
- 4-20mA input
- Ultima X Transmitters
- Flamegard Flame Detector
- SafEye Xenon 800 Gas Detection System
- Fully configurable by laptop via USB or RS-485
Modbus connection - Event log upload by USB or RS-485
- Ethernet w/Modbus TCP/IP for SCADA visualization
interface - Multi-language display (13)
4GasGard XL Controller
- Features and Benefits
- Large graphic display
- LEDs for each channel
- Common relay board
- Pre-formed cable entries
- Easy maintenance
- Hot-swap channel boards
- Robust ABS housing flame retardant V0 rating
- Temperature rating -10oC to 50oC
5GasGard XL Controller
- Standard configuration
- 100 W (24VDC) power supply
- 5 common relays
- 2 alarms levels
- 5A _at_ 250 VAC, 24VDC, SPDT
- 2 horns
- 5A _at_ 250 VAC, 24VDC, SPDT
- Failure
- 8A _at_ 250 VAC, 24VDC, DPDT
- Internal buzzer 85 dB
- Main board includes space for 4 channel cards
6GasGard XL Controller
- Options
- 2 additional relays per channel
- Configurable by zone, group, voting
- Back-up battery 2.2Ah
- Sensor extension board (for channels 5-8)
7GasGard XL Controller
Sensor extension board (optional)
Channel cards
Battery backup (optional)
100 W power supply
Additional relay board
Main board
Common relays
Wiring for channel cards
USB RS485 connections
8GasGard XL Controller Display
Time
Date
Flame symbol
STEL TWA alarms
Alarm 1
Actual values
Sensor fault
Alarm 2
Battery (not included)
Bold indicates active channel
Events archive
9GasGard XL Controller Display
Description
Gas
Channel
mA, active card
Fault condition
Alarm 1, 15 ppm, increasing
STEL and TWA set points
Alarm 2, 25 ppm, increasing, latching
10GasGard XL Controller Display
Horn relay 1
Relay Status Normally de-energized
Channel cards
Voting, 4 out of 5 conditions
Horn to activate on condition
Alarm type
11GasGard XL Configuration Software
Must check box, save and download settings to
activate battery back-up
Date Format
Save
12GasGard XL Configuration Software
Select channels to configure
Channel details screen
Input customized info
Configure alarm details
13GasGard XL Configuration Software
Upload/ download to Gasgard XL
Relay outputs screen
A1 A2 cannot be modified
Check relay boards if included
Horns and additional relays can be configured
14GasGard XL Controller
- Approvals
- cCSAus
- Fire, Shock Safety
- CSA 22.2 No. 61010-1 for Canada
- UL 61010-1 for USA
- Performance
- CSA 22.2 No.152 for Canada
- ISA 12.13 for USA
- ATEX
- SIL 2
- IP56/NEMA 4X