Air System Balancing - PowerPoint PPT Presentation

1 / 27
About This Presentation
Title:

Air System Balancing

Description:

AABC Associated Air Balance Council requires TAB contractors to be ... Check blower motor amperage and voltage. 4/18/2006. 10. TAB. Pre-balance Checks. Fans ... – PowerPoint PPT presentation

Number of Views:856
Avg rating:3.0/5.0
Slides: 28
Provided by: SinclairC4
Category:

less

Transcript and Presenter's Notes

Title: Air System Balancing


1
Air System Balancing
  • MET 150

2
What is TAB?
  • Testing to document existing conditions
  • Adjusting to match contract requirements
  • Balancing to provide acceptable space conditions
    in accordance with the system design requirements

3
Who Does It?
  • Certified Balancing Technician
  • AABC Associated Air Balance Council requires
    TAB contractors to be independent cannot be a
    contractor who also performs installation work,
    on this job or any other.
  • NEBB National Environmental Balancing Bureau
    installing contractors who have personnel trained
    to perform test and balance functions
  • TABB Testing, Adjusting and Balancing Bureau, a
    subsidiary of the National Energy Management
    Institute provides training and certification
    to contractors and independent test and balance
    companies

4
Qualifications
  • Vary by certifying organization but, in general
  • Training in proper methods of measurement, use of
    testing equipment, and system balance procedures
  • Lead engineer or technician qualified to evaluate
    test data, determine necessary system adjustments

5
Preliminary Work
  • Equipment data
  • Fan curves for all fans
  • Performance data for all installed equipment
    take special notice of equipment changes from
    original specifications
  • Motor nameplate data, motor starters, overload
    protection and drive information

6
Preliminary Work
  • Equipment data
  • Air distribution devices effective areas,
    pressure drops, required pressure behind
  • Temperature control diagrams
  • Manufacturers catalogs for equipment
  • OM instructions for all equipment

7
Schematic Layout
  • Indicate dampers, regulating devices, terminal
    units, outlets and inlets
  • Sizes and CFMs for main ducts, outlets and
    inlets, and fresh air and return air quantities
  • Convert cfm to fpm (velocities easier to work
    with)

8
Prepare Schematics
9
Pre-balance Checks
  • Fans
  • Bearings lubricated
  • Fan wheels clear of housing, correct rotation
  • Foreign objects removed
  • Motors fastened securely, drives aligned, drive
    set screws and keyways tight
  • Belt tensions correct, belt guards in place
  • Check motor and fan rotation
  • Check blower motor amperage and voltage

10
Pre-balance Checks
  • Fans
  • Vibration isolators or bases have correct springs
    in correct location, springs not collapsed
  • Equipment leveled
  • NO CLOSED OR UNCONNECTED DAMPERS ANYWHERE IN
    SYSTEM
  • Filters properly installed (either temporary for
    TAB work or permanent)

11
Pre-balance Checks
  • Other equipment
  • Check coils for proper installation, insure coils
    are clean and free of obstructions
  • Check and set all automatic control dampers as
    required
  • Confirm that crankcase heaters on refrigeration
    systems have been operating for at least 24 hours

12
Pre-balance Checks
  • Duct System
  • Intake, return and exhaust dampers in proper
    position and operable
  • All system volume dampers, fire dampers and smoke
    dampers installed and fully open
  • Air terminals and terminal units installed,
    terminal dampers fully open

13
Pre-balance Checks
  • Duct System
  • Confirm openings in walls and plenums for proper
    air passage
  • Inspect duct system for proper construction,
    including turning vanes installed where indicated
    and joints sealed as specified
  • Confirm required architectural features
    (ceilings, doors, etc.) in place as required

14
General Balancing Procedure
  • Check airflow for all fans should be within /-
    10 before starting system balance.
  • If too low, investigate system to determine there
    are no blockages, excessive system effects, etc.
  • If too high, reduce airflow to specifications /-
    10.

15
General Balancing Procedure
  • Main supply ducts
  • Adjust volume dampers serving each branch to the
    approximate airflow required (note that changing
    one will change another may have to adjust
    multiple times)
  • Once mains and branches balanced, proceed to air
    terminals and balance each successively may
    have to repeat multiple times

16
Terminal Balancing
  • Check farthest outlet of each branch.
  • If below design fpm, leave damper fully open and
    go on to next outlet upstream.
  • If outlet velocity at farthest device above
    design specifications, throttle down and proceed
    to next outlet upstream.
  • Proceed upstream until all outlets have been
    adjusted.

17
Terminal Balancing
  • Repeat procedure three times through system until
    all outlets are close to required fpm.
  • If terminal dampers are generating noise,
    readjust branch air volume and recheck outlets.
    Adjust as required. May need to go through
    entire system again.

18
General Balancing Procedure
  • Exhaust and return systems
  • Adjust return and exhaust fan volumes within /-
    10 of specifications
  • Adjust each main and branch as before
  • Adjust terminal devices
  • Verify overall system balance

19
Mixed Air Section
  • Check all dampers for free travel
  • Set outside air damper for minimum outside air
    verify with airflows or by temperature
  • MB IB FA (OB-IB)
  • MB MA drybulb
  • IB indoor drybulb
  • OB outdoor drybulb
  • FA fresh air

Outside Air
Mixed Air
M
Exhaust Air
20
Mixed Air Section
  • If economizer used, check outside air/return air
    for 25, 50, 75 and 100 outside air will need
    to work with temperature control contractor to
    perform these checks
  • Check for leakage when OA dampers are 100 closed
    (such as for morning warm-up of off-hours
    operation)

21
Coil Section
  • Verify control valve operation over entire range
    of travel
  • Check heating coil performance using energy
    balance equations
  • Check cooling coil performance using
    psychrometric equations

H E A T
C O O L
Supply Air
22
Heating Coil Performance
  • Air side Q 1.08 x CFM x Dtair
  • Water side Q 500 x GPM x Dtwater
  • Example 30 gpm of 200oF water circulates through
    a coil, heating 4000 CFM from 50oF to 120oF.
    What is the leaving water temperature?
  • 1.08 x CFM x Dtair 500 x GPM x Dtwater
  • 1.08(4000)(70oF) 500(30) Dtwater
  • Dtwater 20.2oF twater 200 20.2
    179.8oF

H E A T
Supply Air
23
Cooling Coil Performance
  • Air side Q 4.5 x CFM x Dhair
  • Water side Q 500 x GPM x Dtwater
  • Example 30 gpm of 40oF water circulates through
    a coil, cooling 4000 CFM from 85oF/40 to
    55o/90. What is the leaving water temperature?
  • 4.5 x CFM x Dhair 500 x GPM x Dtwater
  • 4.5(4000)(31.8-22.2) 500(30) Dtwater
  • Dtwater 11.5oF twater 40 11.5
    51.5oF

C O O L
Supply Air
24
Cooling Coil Performance
25
Coil Performance
  • What if performance doesnt match?
  • One of the parameters is not as expected
  • Usually, you can easily measure everything but
    the gpm, so calculate the gpm being delivered and
    compare to that specified to verify performance

26
Humidifier
  • Verify equipment operates upon a call for
    humidification
  • Check air off humidifier for desired
    temperature/humidity condition
  • Check humidifier performance using psychrometric
    equations

Supply Air
Steam Grid or Pan-type
27
Smoke Dampers
  • Verify that damper is properly connected
  • Check damper operation on signal that smoke is
    present
  • Fire inspector may want to see damper operate in
    presence of real smoke

M
Write a Comment
User Comments (0)
About PowerShow.com