Title: BEE3133 Electrical Power Systems
1BEE3133 Electrical Power Systems
- Chapter 6 System Protection
- Rahmatul Hidayah Salimin
2Introduction
- System Protection the equipment use to detect
and isolate the faulty section from the system
automatically.
3Introduction
- Short circuit occur when equipment insulation
fails due to system overvoltages caused by - Lightning or switching surges
- Flashover line-line (caused by wind)
- Flashover to tree
- Insulation contamination by dirt/salt
- Mechanical failure
- Cable insulation failure
- Natural causes
- Tower/pole or conductor falls
- Objects fall on conductors
4Introduction
- Short circuit currents can be several orders of
magnitude larger than normal operating currents - If it is allowed to persist, may cause
- Damage to the equipment due to heavy currents,
unbalanced current, or low voltage produces by
the short circuit - Fire and explosion effect equipment/people
- Disruption of service in the entire power system
area
5Introduction
- Careful design, operation and maintenance of
system protection can minimize the occurrence of
short circuit but cannot eliminate them.
6Fault Currents and Voltages
7Function of System Protection
- Cause the prompt removal from service of any
elements of power system when it suffers a short
circuit, or when it start to operate in any
abnormal manner that might cause damage or
otherwise interfere with the effective operation
of the rest of the system. - Provide indication of the location and type of
failure so that the data can be used to assist in
expediting repair and analyzing the effectiveness
of fault-prevention and mitigation features.
8Function of System Protection
- Why do we need system protection
- Detect fault
- Isolate faulted component
- Restore faulted component
- Aims
- Continued supply for rest of system
- Protect faulted part from damage
9Types of Protection
- A Fuses
- For LV Systems, Distribution Feeders and
Transformers, VTs, Auxiliary Supplies -
- B - Over current and earth fault
- Widely used in All Power Systems
- Non-Directional
- Directional
-
10Types of Protection
- C - Differential
- For Distribution Feeders, Busbars, Transformers,
Generators etc - High Impedance
- Low Impedance
- Restricted E/F
- Biased
- Pilot Wire
11Types of Protection
- D - Distance
- For Transmission and Sub-transmission Lines and
Distribution Feeders, - Also used as back-up protection for transformers
and generators without signaling with signaling
to provide unit protection e.g. - Time-stepped distance protection
- Phase comparison for transmission lines
- Directional comparison for transmission lines
-
12Types of Protection
- E - Miscellaneous
- Under and over voltage
- Under and over frequency
- A special relay for generators, transformers,
motors etc. - Control relays auto-reclose, tap change control,
etc. - Tripping and auxiliary relays
13Design Criteria/Characteristics
Economy
Simplicity
Speed
Reliability
Sensitivity
Selectivity
14Design Criteria/Characteristics
- Reliability
- Operate dependably and in healthy operating
condition when fault conditions occur, even after
remaining idle for months or years. - Selectivity
- Clearly discriminate between normal and abnormal
system condition to avoid unnecessary, false
trips. - Sensitivity
- Ability to distinguish the fault condition,
although the different between fault and normal
condition is small.
15Design Criteria/Characteristics
- Speed
- Fault at any point in the system must be detected
and isolated rapidly to minimize fault duration
and equipment damage. Any intentional time delays
should be precise. - Economy
- Provide maximum protection at minimum cost
- Simplicity
- Minimize protection equipment and circuitry
16Economic Factor
- Total cost should take account of
- Relays, schemes and associated panels and panel
wiring - Setting studies
- Commissioning
- CTs and VTs
- Maintenance and repairs to relays
- Damage repair if protection fails to operate
- Lost revenue if protection operates unnecessarily
17Economic Factor
- The cost of protection is equivalent to an
insurance policy against damage to plant, and
loss of supply and customer goodwill. - Acceptable cost is based on a balance of
economics and technical factors. Cost of
protection should be balanced against the cost of
potential hazards. - There is an economic limit on what can be spent.
- MINIMUM COST Must ensure that all faulty
equipment is isolated by protection.
18Relationship between reliability of supply, its
value and cost to the consumer
19System Protection Components
- Transducer / Instrument Transformer
- Relay
- Circuit Breaker
20System Protection Components
- Function
- Transducers/Instrument Transformers
- Provide low current and voltage, standardized
levels suitable for the relays operation. - Relays
- Discriminate between normal operating and fault
conditions. - When current exceed a specified value relay will
be operated and cause the trip coil of CB to be
energized/open their contact. - Circuit Breakers
- Open the line
21System Protection Components
22System Protection Components
23System Protection Flow
voltage or current rise from normal condition
voltage/current is reduced to match with relay
rating
activate circuit breaker
circuit isolation
Relay
Transducer
Fault Occur
Circuit Breaker
Fault Clear
24Zones of Protection
- For fault anyway within the zone, the protection
system responsible to isolate everything within
the zone from the rest of the system. - Isolation done by CB
- Must isolate only the faulty equipment or section
25Zones of Protection
- Zones are defined for
- Generators
- Transformers
- Buses
- Transmission and distribution lines
- Motors
26Zones of Protection
27Zones of Protection
- Characteristics
- Zones are overlapped.
- Circuit breakers are located in the overlap
regions. - For a fault anywhere in a zone, all circuit
breakers in that zone open to isolate the fault.
28Overlapped of Protection
- No blind spot
- Neighboring zones are overlapped to avoid the
possibility of unprotected areas - Use overlapping CTs
- Isolation done by CB. Thus, it must be inserted
in each overlap region to identify the boundary
of protective zones.
29Overlapped of Protection
- Overlap accomplish by having 2 sets of instrument
transformers and relays for each CB. - Achieved by the arrangement of CT and CB.
30Primary Back-up Protection
- Primary protection is the protection provided by
each zone to its elements. - However, some component of a zone protection
scheme fail to operate. - Back-up protection is provided which take over
only in the event of primary protection failure.
31Example
- Consider the power system shown below, with the
generating source beyond buses 1, 3 and 4. What
are the zones of protection in which the system
should be divided? Which circuit breakers will
open for faults at P1 and P2?
32Fault at P1 A, B, C Fault at P2 A, B, C,D, E
33Example
- If three circuits breakers are added at the tap
point 2, how would the zones of protection be
modified? Which circuit breakers will operate for
fault at P1 and P2 under these conditions?
34Fault at P1 A, F Fault at P2 C,D,E,G
35Zone Discrimination
- A system as shown with relays and breakers
marked. A single fault has resulted in the
operation of breakers B1, B2, B3 and B4.Identify
the location of the fault - Answer
- Fault in the overlap zone at breaker B2 as shown
36Back-up Protection
- 1.Duplicate Primary
- Provide primary protection when the
primary-relaying equipment is out of service for
maintenance or repair - Disconnect when primary relaying operates
correctly - Operate with sufficient time delay (coordination
time delay) if primary not operate - When short circuit occur, both primary and
back-up start to operate, but if primary is
operate, then the back-up will reset.
37Back-up Protection
- 2.Remote Back-up
- located outside boundary of Zone of Protection
38Example
C, D, E
A, B, F
39Example
C, D, E, F, G, H
A, B, I, J
40Transducers
- Also known as Instrument Transformer
- Use to reduce abnormal current voltage levels
and transmit input signals to the relays of a
protection system. - Why do we need transducer
- The lower level input to the relays ensures that
the physical hardware used to construct the
relays will be small cheap - The personnel who work with the relays will be
working in a safe environment.
41Transducers
- Current and Voltage Transformers
- Correct connection of CTs and VTs to the
protection is important directional, distance,
phase comparison and differential protections. - Earth CT and VT circuits at one point only
42VT and CT Schematic
43Voltage Transformers
- VT is considered to be sufficiently accurate.
- It is generally modeled as an ideal transformer.
- VT secondary connected to voltage-sensing device
with infinite impedance.
44Voltage Transformers
- Types of VTs
- Electromagnetic VT
- Capacitive VT
- Busbar VTs
- Special consideration needed when used for line
protection - LV application(12 kV or lower)
- Industry standard transformer with a primary
winding at a system voltage and secondary winding
at 67 V(line-to-neutral) and 116 V(line-to-line).
45Voltage Transformers
46Voltage Transformers
- Voltage/Potential
- Transformer (VT/PT)
47Voltage Transformers
48Voltage Transformers
49Voltage Transformers
- HV and EHV
- Capacitor-coupled VT (CVT)
- C1 C2 are adjusted, so that a few kVs of
voltage is obtains across C2 - Then, stepped down by T
- VTs must be fused or protected by MCB.
50Voltage Transformers
51Voltage Transformers
- VT ratios
- ratio of the high voltage/secondary voltage
- 11 21 2.51 41
- 51 201 401 601
- 801 1001 2001 3001
- 4001 6001 8001 10001
- 20001 30001 45001
52Current Transformers
- CT is an instrument transformer that is used to
supply a reduced value of current to meters,
protective relays, and other instruments. - The primary winding consist of a single turn
which is the power conductor itself. - CT secondary is connected to a current-sensing
device with zero impedance.
53Current Transformers
- CTs ratio(secondary current rating is 5A)
- 505 1005 1505 2005
- 2505 3005 4005 4505
- 5005 6005 8005 9005
- 10005 12005
- CTs also available with the secondary rating of 1A
54Current Transformers
55Current Transformers
56Reclosers and Fuses
- Automatic reclosers are commonly used for
distribution circuit protection. - Recloser self-controlled device for
automatically interrupting and reclosing an AC
circuit with preset sequence of openings and
reclosures - Have built-in control to clear temporary faults
and restores service with momentary outages. - Disadvantages
- increase hazard when circuit is physically
contacted by people. - Recloser should be locked out during live-line
maintenance.
57Reclosers and Fuses
- An upstream fuse/relay has detected a fault
- Downstream system isolated by fuse or breaker
- Automatic re-closing after delay successful if
fault not permanent
58Relays
- Discriminate between normal operating and fault
conditions. - Type of Relays
- Magnitude Relay
- Directional Relay
- Distance/Ratio Relay
- Differential Relay
- Pilot Relay
59Magnitude Relays
- Also called as Overcurrent Relay
- Response to the magnitude of input quantities ie.
current. - Energize CB trip coil when the fault current
magnitude exceeds a predetermined value or trips
when a current rises above a set point (pick-up
current). - If it is less than the set point value, the relay
remains open, blocking the trip coil. - Time-delay Overcurrent Relay also have the same
operating method but with an intentional
time-delay.
60Directional Relays
- Responds to fault only in one direction, either
to the left or to the right of its location - Operation depends upon the direction (lead or
lag) of the fault current with respect to a
reference voltage. - The directional element of these relays checks
the phase angle between the current and voltage
of one phase, and allows the overcurrent unit to
operate if this phase angle indicates current in
the reverse direction.
61Ratio Relays
- Operate for certain relations between the
magnitudes of voltage, current and the phase
angle between them. - Measures the distance between the relay location
and the point of fault, in term of impedance,
reactance and admittance. - Respond to the ratio of two phasor quantities as
example Voltage and Current (Z V/R) - Also called impedance or distance relay
62Differential Relays
- Respond to the vector difference between two
currents within the zone protection determined by
the location of CTs. - Not suitable for transmission-line protection
because the terminals of a line are separated by
too great a distance to interconnect the CT
secondaries. - For the protection of generators, transformers,
buses, - Most differential-relay applications are of the
current-differential type.
63Differential Relays
Relay
- Fault occur at X
- Suppose that current flows through the primary
circuit either to a load or to a short circuit
located at X. - If the two current transformers have the same
ratio, and are properly connected, their
secondary currents will merely circulate between
the two CTs as shown by the arrows, and no
current will flow through the differential relay.
64Differential Relays
Relay
- A flow on one side only, or even some current
flowing out of one side while a larger current
enters the other side, will cause a differential
current. - In other words, the differential-relay current
will be proportional to the vector difference
between the currents entering and leaving the
protected circuit and, if the differential
current exceeds the relays pickup value, the
relay
65Differential Relays
Relay
- When a short circuit develop anywhere between the
two CTs. - If current flows to the short circuit from both
sides as shown, the sum of the CT secondary
currents will flow through the differential
relay. - It is not necessary that short-circuit current
flow to the fault from both sides to cause
secondary current to flow through the
differential relay.
66Pilot Relays
- The term pilot means that between the ends of
the transmission line there is an interconnecting
channel of some sort over which information can
be conveyed. - Use communicated information from remote sites as
input signals.
67Pilot Relays
- Transmitting fault signals from a remote zone
boundary to relays at the terminals of a long TL - Pilot relaying provides primary protection only
back-up protection must be provided by
supplementary relaying. - Type wire pilot, carrier-current pilot and
microwave pilot.
68Pilot Relays
ZA
ZB
- Station 1 consist of meter for reading voltage,
current and power factor. - Distance relay, tell the different between fault
at A (middle) and B (end) by knowing the
impedance characteristic per unit length of the
line.
69Pilot Relays
- Could not possibly distinguish between fault B
and C because impedance would be so small-
Mistake in tripping CB for fault B or C - Solution- indication from station B, when the
phase angle of the current at S-B(with respect to
current A) is different by approximately 180o
from it value for fault in the line section AB.
70Pilot Relays
2
1
B
C
A
(with respect to current A) is different by
approximately 180o from it value for fault in the
line section
(with respect to current A) is not different in
degree from it value for fault in the line section