Schedule - PowerPoint PPT Presentation

1 / 50
About This Presentation
Title:

Schedule

Description:

What will happen if electrical appliances are not earthed? Can earthing help? ... Volt drop pre unit value in from of mv/A/m are shown on IEE tables of Appendix 4. ... – PowerPoint PPT presentation

Number of Views:416
Avg rating:3.0/5.0
Slides: 51
Provided by: Aqu55
Category:

less

Transcript and Presenter's Notes

Title: Schedule


1
Schedule
2
Introduction
Load Estimation
Terminology
Basic Equipment
Codes and Standards
Power Distribution Final Circuit
Standby Generator and Power Supplies
Protection Cable Wiring
Earthing
Design of Electricity Distribution
3
Earthing and Design of Electricity Distribution
  • Date 20 November 2008
  • Ir. KF Cheung

4
Earthed Equipotential Bonding and Automatic
Disconnection - 1
  • A) Principle
  • To bond all the exposed and extraneous conductive
    parts to earth in order to create a zone at
    earthed potential so that the potential
    difference (touch voltage) between those parts
    are minimized in the event of an earth fault
    inside the zone (touch voltage would be reduced
    by bonding), and then to cut the supply within
    the maximum safe time duration.

5
(No Transcript)
6
What will happen if electrical appliances are not
earthed?
7
Can earthing help?
8
What will happen if extraneous conductive parts
are not bonded?
9
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • A protection device shall disconnect the supply
    during an earth fault so as not to cause danger.
  • Maximum disconnection times are shown as follows

10
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • Maximum value of earth loop impedance achieving
    the above disconnection time for various
    protective devices are shown in Table 41B1, Table
    41B2 and Table 41D of IEE Regulations (for 240V).
    The values shall be multiplied by 0.916 (220V/
    240V) for nominal supply voltage of 220V.

11
Earthed Equipotential Bonding and Automatic
Disconnection
12
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • The breaking capacity of the protective device
    shall be capable to withstand the prospective
    earth fault current.
  • Local supplementary bonding shall be required
    where the disconnection time cannot be achieved

13
Earthed Equipotential Bonding and Automatic
Disconnection
  • B) Disconnection of Supply under Earth Fault
  • The principle is to limit the resistance of the
    protective conductor so that the voltage
    appearing on exposed conductor parts under fault
    conditions is limited to 50 volts or if the
    voltage is a higher value the circuit would
    disconnect faster.
  • For ring circuits the impedance of the protective
    conductor is calculated between its two ends
    before final connection is made and shall not
    exceed four times the value given in table 41C.

14
Earthed Equipotential Bonding and Automatic
Disconnectio
15
Earthed Equipotential Bonding and Automatic
Disconnection
C) Determination of Disconnection Time 1) Maximum
values of earth loop impedance for various
overcurrent protective devices are shown in table
41B1, Table 41B2 Table 41D 2) Actual earth loop
impedance can be calculated as follows Zs Ze
Z1 Z2 Ze Earth loop impedance at the
source Z1 Impedance of phase conductor Z2
Impedance of circuit protective conductor (cpc)
16
Earthed Equipotential Bonding and Automatic
Disconnection
  • C) Determination of Disconnection Time
  • 3) Compare the actual Zs with the tabulated
    Zs(max)
  • The actual Zs value measured from the
    installation should be smaller than the Zs(max)
    value from IEE Tables in order to achieve safe
    disconnection time. Attention is drawn on that
    the Zs (max) form IEE Tables shall be converted
    to nominal supply voltage system in Hong Kong
    before comparison.
  • Zs (max 220) Zs (max 240) in IEE Tables X
    220/240

17
Earthed Equipotential Bonding and Automatic
Disconnection
C) Determination of Disconnection Time 4) The
earth fault current can be calculated using the
following formula If Uo /Zs Uo Phase to
earth voltage If earth fault current 5) By
putting the calculated fault current against the
characteristic curves of the protective device
given in IEE, the actual disconnection time can
be found.
18
Example
  • A 220V circuit is protected by a 30A Type 2 MCB,
    the cable used is 2.5/1.5 twin with cpc PVC
    copper conductor, if the circuit length is 15m
    and Ze up to the MCB board is 0.5O, what is the
    actual disconnection time?
  • From table 17, R1R2 /m 19.51mO x 1.38
  • 0.269
    O/m

19
Time (s)
Current (A)
20
(No Transcript)
21
(No Transcript)
22
A) Cable Selection
  • Factors to be considered in sizing of cable
    conductors
  • Conductor material
  • Insulating material
  • Method of installation
  • Installed environment
  • Ambient temperature
  • Thermal insulating enclosure
  • Adjacent cables
  • Type of protective device
  • Voltage drop
  • Minimum cross-sectional area

23
Comparison between Copper Conductor and Aluminum
Conductor
  • A) Copper Conductor
  • High degree of electrical conductivity
  • Tough, slow to tarnish
  • Can be jointed without any special provision to
    prevent electrolytic action
  • B) Aluminum Conductor
  • Lower price light in weight
  • Pliable, it can be used in solid-core cables
  • Excellent resistance to corrosion

24
Insulating Materials
25
Bends of Non-flexible Cable
  • The minimum internal radius bend in cables for
    fixing wiring are shown in the following table

26
Correction Factor for Conductors
  • Factors which affect the ability of a cable to
    lose heat are
  • Grouping (Cg or C1)
  • Ambient temperature (Ca or C2)
  • Thermal insulation (Ci or C3)
  • Semi-enclosed fuse to BS 3036 (0.725 or C4)
  • Type of installation (Table 4A)

27
Correction Factor for Conductors
  • A) Grouping factor (Cg) - 1
  • IEE Table 4B1 gives correction factors to be
    applied to te tabulated current-carrying
    capacities where cables or circuits are grouped.
  • Where the horizontal clearance s between adjacent
    cables exceed two cable diameter (2D2), no
    correction factor need be applied.

28
Correction Factor for Conductors
  • A) Grouping factor (Cg) - 2
  • If a cable is expected to carry not more than 30
    of its grouped rating, it may be ignored from the
    rest of the group.

29
Correction Factor for Conductors
  • B) Correction Factor for Ambient Temperature (Ca)
  • Correction factor for ambient temperature is
    shown in IEE Table 4C1. Where for semi-enclosed
    fuses are being used, see IEE Table 4C2.
  • It In / Ca
  • Typical data are shown in the following table for
    quick reference.

30
Correction Factor for Conductors
  • C) Correction Factor for thermal Insulation (Ci)
  • The value of current-carrying-capacity for
    various sizes of conductors shown in Tables of
    Appendix 4 have been taken into account of cables
    installed in a thermally insulated wall or
    ceiling where one side of the cable is in contact
    with a thermally conductive surface.
  • Where the cable is totally enclosed in thermal
    insulation, Ci0.5 shall be used in absence of
    more precise information.
  • It In / Ci
  • Ci shall only be applied to the open and clipped
    direct column of respective IEE Tables.

31
Correction Factor for Conductors
  • D) factor for Semi-enlosed fuse to BS3036 (C4)
  • When semi-enclosed fuse is used for protecting
    the conductor, a derating factor of 0.726 shall
    be applied.

32
Correction Factor for Conductors
  • E) General Formula for Correction Factors Applied
    to Cable Sizing
  • It In / Cg x Ca x Ci x C4

33
Example
34
Example
  • Protective device BS 3036 fuses
  • Ambient temperature 30oC
  • Cable use PVC twin with cpc cable
  • Cabling conditions at
  • 1) Bunched and clipped direct
  • 2) Passed through totally enclosed thermal
    insulation area
  • 3) One side in contact with thermally insulated
    ceiling
  • 4) Passed through a boiler house where ambient
    temperature of 45oC
  • 5) Clipped direct
  • Ignore voltage drop
  • Select the appropriate size of cables?

35
Voltage Drop
  • The overall voltage drop shall not exceed the
    value appropriate to the safe functioning of the
    equipment in normal service.
  • The voltage drop in any circuit from the origin
    of installation to the current-using equipment
    should not exceed 4 of the nominal voltage.
  • Volt drop pre unit value in from of mv/A/m are
    shown on IEE tables of Appendix 4. The values are
    based on the circuit conductor working at the
    maximum permitted operating temperature and at
    unity power factor.

36
Voltage Drop
37
Voltage Drop
38
Voltage Drop
39
Voltage Drop
  • Voltage drop (V.D.) can be calculated as follows
  • V.D. design current (Ib) x circuit length (L)
    x volt drop per unit (mv/A/m)

40
Example
  • A PVC/SWA/PVC armoured cable is to be installed
    from an HRC 100A fuse in a distribution board to
    a 3-phase 380V motor, along with 5 other cables
    fixed to a perforated metal cable tray where the
    cable sheaths will be touching, if the cable
    length is 125 meters and the power factor of the
    load is 0.89, what size of cable would be
    required to satisfy voltage drop if the ambient
    temperature is 30oC and the voltage drop in the 3
    phase feeder cable up to the distribution board
    is 3.7V and the total voltage drop allowed is 4?

41
  • Cg 0.74 (from the Table)
  • It 100/0.74 135.14A

    From the Table
  • Iz 163 A (for 50mm2 cable)
  • V.D. allowances for the circuit
  • (380V x 4) 3.7V 11.5V
  • From the Table, z 0.81 mV/A/m
    Actual
    V.D. circuit 125m x 100A x 0.81 x 10-3
  • 10.125V
  • V.D. from Table for 50mm2 r 0.8, x 0.14
    Consider the power
    factor
  • cos Power factor is 0.89
  • sin power factor is 0.46
  • V.D. ((0.89 x 0.8 0.14 x 0.46) x 125m x 100A)
    / 1000
  • 9.705V lt 11.5V

42
Sizing Circuit Protective Conductors
  • If the conductor 35mm2 Zs Ze R1 R2
  • gt35mm2 Zs Ze
    Z1 Z2
  • Use the formula S v(I2t) / K
  • Value of K from IEE Tables 54B to 54F
  • If Uo / Zs
  • Value of t from IEE Fig. 1 to 8 of Appendix 3
  • Use Table 54G to size the minimum size of
    protective conductors.

43
Thermal Constraint
  • To protect conductor insulation against thermal
    damage during short circuit conditions.
  • I2 t K2 S2
  • t K2 S2/ I2
  • t duration in second
  • S cross-sectional area in mm2
  • I effective short-circuit current in A
  • K 115 for copper conductor insulated with PVC

44
Thermal Constraint
  • Procedure
  • To check the prospective short-circuit current at
    the farthest point of the circuit from the point
    where the device is installed
  • To check the operation time of the device
    according to the short-circuit current from the
    time/ current characteristic of the device
  • To check the adiabatic line of the conductor by
    superimposing onto the characteristics of
    protective devices.

45
Cable Selection Procedure
  • Select wiring system to be installed and type of
    cable
  • Calculate the equipment current demand using
    Table 4A
  • Calculate the circuit design current (Ib) and
    using diversity allowance.
  • Determine the overcueent protective device (In)
    type rating
  • Check Ib In
  • Determine correction factors for installation
  • Grouping (Cg)
  • Ambient temperature (Ca)
  • Thermal insulation (Ci)
  • Semi-enclosed fuse (C4)

46
Cable Selection Procedure
  • Calculate the tabulated current carrying capacity
    of conductor
  • It (min) In x (1/ Cg) x (1/ Ca) x (1/ Ci) x
    (1/ C4)
  • Select cable size from Appendix 4
  • Check Ib In Iz
  • Calculate volt drop at the farthest point of
    circuit

47
Cable Selection Procedure
  • Does it offer shock protection in accordance with
    table 41B1, 41B2 41D for Zs (max)?
  • Check Zs Zs (max) from the tables
  • If No
  • Re-select device or re-select phase conductor
    size
  • Re-select cpc size
  • Use alternative method as stated in Reg.
    413-02-12
  • Checked by calculation
  • Obtain Ze form supply authority
  • Calculate R1 R2 using Table 17A B
  • Determine actual Zs Ze (R1 R2)

48
Cable Selection Procedure
  • Does the type and size of cpc offer protection?
  • Check S v(I2t) / K
  • If No re-select type and/ or size of cpc
  • Check the adiabatic line of conductor against the
    characteristic of overcurrent protective device.

49
Q A
50
The End
Write a Comment
User Comments (0)
About PowerShow.com