Title: Energy Control Through Building Automation
1Energy Control Through Building Automation
- Building Automation Control Seminar
- CANDO EnergySmart Schools
- January 24, 2006
2Energy Control Through Building Automation
- Why Control Energy Consumption?
- How Can Building Automation Help?
- What Are Typical Solutions?
- Which Are Possibilities (Using Building
Automation)? - Conclusion
3Why Control Energy Consumption?
- Saving Energy is
- Earth Friendly reduces pollution
conserves resources
4How Can Building Automation Help?
- Use Automation Trend Data and Reports to
- Monitor Operating Conditions
- Monitor Equipment Schedules
- Monitor Energy Consumption
- Which Will
- Assist in Troubleshooting
- Assist in Maintenance schedules
- Assist in Minimizing Energy Consumption
5What Are Typical Solutions?
- Common Energy Savings Measures (Determined by
Building Automation Systems) - Start/Stop Optimization (Night set back or
shutdown) - Resets (Water Temperature, Air Temperature, Air
pressure) - Demand Control Ventilation (CO2 monitoring)
- Variable Frequency Drives (VFDs on pumps or fans)
- Economizers (outside air damper position)
- Peak Demand Limiting
6Which Are Possibilities (Using Building
Automation)?
- Determining Feasibility of Three Common Measures
Using BAS Data. - Variable Frequency Drive Fan
- Hot Water Reset
- Economizer
7Variable Frequency Drive - fan
- Advantages
- Identifying Requirements
- Savings
- Implementation Follow-up
8VFD fan Advantages
- Reduced Maintenance Costs
- Increased Occupant Comfort
- Reduced Noise
- Reduced Energy Consumption
- A Variable Air Volume system using a standard
constant volume fan uses mechanisms such as
discharge dampers, inlet vanes, and variable
pitch blades to restrict the air wasting
energy. - When a fan can only operate either on at full
load, or completely off, the electric energy used
to run the fan is often wasted.
9VFD fan Identifying Requirements
- Not to be used in Critical Environments
- Not to be used with Constant Speed Exhaust Hoods
- Works for VAV Application with currently
modulating Damper, Vane, or Blade - Works for systems that are not currently VAV, but
have varying air needs.
10VFD fan Savings
11VFD fan Savings
- Example results vary greatly but
- Using the following general parameters
- 10 HP, 10,000 CFM Supply Fan
- 1.00/therm, 0.04/kWh, 12/kW demand
- 24 hour operation
- Estimated typical annual savings
- 4,500
12VFD fan Implementation Follow-up
- After installing the VFD on the system, there
are often still opportunities to save energy by
monitoring trends and data on the automation
system. - Trends can show areas needing improvement and
tuning, or even equipment problems. - Continuous Monitoring Continuous Savings
13Hot Water Reset
- Advantages
- Identifying Requirements
- Savings
- Implementation Follow-up
14Hot Water Reset Advantages
- Reduced Maintenance Costs
- Increased Occupant Comfort
- Reduced Energy Consumption
- Water temperature required to heat a building
varies based on - Outdoor air temperature
- Amount of sun or wind
- Occupant needs
- Many times, heating water temperatures are
maintained at a constant temperature, relying on
valves and thermostats to modulate according to
load changes and wasting energy.
15Hot Water Reset Identifying Requirements
- Useful in buildings with large variance in loads
throughout the year - Greatly reduces heat losses through large boilers
and long lengths of pipes
16Hot Water Reset Savings(by delta temperature)
17Hot Water Reset Savings
- Example results vary greatly but
- Using the following general parameters
- 5 MBH Boiler
- 1.00/therm
- 24 hour operation
- Estimated typical annual savings
- 3,500
18Hot Water Reset - Implementation Follow-up
- Even after installing a reset control strategy
on a hot water system, there are often still
opportunities to save energy by monitoring trends
and data on the automation system. - Trends can help determine where tighter
adjustments can be made to further savings. - Continuous Monitoring Continuous Savings
19Economizer
- Advantages
- Identifying Requirements
- Savings
- Implementation Follow-up
20Economizer Advantages
- Increased Occupant Comfort
- Reduced Energy Consumption
- Facilities without economizers must use
mechanical heating and cooling to keep the supply
temperature near its set point. However, with an
economizer, the system can utilize the free
heating or cooling from the outside air.
21Economizer Identifying Requirements
- All building types can benefit
- Locations in high humidity climates will require
increased dehumidification
22Economizer Savings
23Economizer Savings
- Example results vary greatly but
- Using the following general parameters
- 30,000 CFM Air Handling Unit
- 0.04/kWH
- 24 hour operation
- Estimated typical annual savings
- 1,000
24Economizer - Implementation Follow-up
- Even after installing an economizer on an air
handling unit, there are often still
opportunities to save energy by monitoring trends
and data on the automation system. - Trends can help determine where tighter
adjustments can be made to further savings. - Continuous Monitoring Continuous Savings
25Conclusion
- Building Automation can help users monitor and
manage energy consumption. - There are many ways to use an automation system
to find energy savings projects. - By collecting, storing, and analyzing trend data,
techniques and strategies can be developed to
reduce energy consumption and save money. - Monitor and Measure to Minimize Waste
26Siemens Building TechnologiesEnergy
Environmental Solutions Helping your
building work for you