Title: Small Office Savings Analysis
1Small Office Savings Analysis
2Summary
- Tested a dozen measures
- Tested sensitivities to climate, building size,
HVAC system type, baseline assumptions - Findings
- HVAC system type baseline conditions impact
savings estimates - Climate building size not big factors
- Package savings show modest range due to
compensating effects of package
3Electric Site Savings All Measures
4Electric Savings by MeasureMean of all System
Types
5Mean Gas Savings by MeasureMean of all System
Types
6Interactive Electric Savings from LPDBy System
Type for Boise Seattle
7Interactive Electric Savings from HVAC Equip.By
Location System Type
8Windows Savings are Sensitive to the following
- Baseline assumptions for U SHGC
- Measure U value SHGC interact
- System Type
- Window area, window / wall ratio
- Climate
- Other measures in package
9Window Baseline Assumptions
10Interactive Elec. Savings from WindowsBaseline
to U40/SHCG40 By System Location
11Interactive Elec. Savings from WindowsBaseline
to U35/SHCG30 By System Location
Window U35/SHGC30
12Interactive Elec. Savings from WindowsCompare
U35/SHCG30 to U40/SHGC40
35/30
35/30
35/30
13Interactive Gas Savings from WindowsCompare
U35/SHCG30 to U40/SHGC40
35/30
35/30
35/30
14Cooling Ventilation Savings from Windows in
Gas-Heated
35/30
35/30
35/30
15Electric Savings from Economizer Commissioning
16Measure Cost Estimates
17Measure Cost per Unit
- Windows 3.67 / sf glass, 30 window wall
ratio - LPD 37 / fixture, for 300 fixtures
- Lighting Controls 312 / sensor, for 50 open
office - CEE Tier 2 155 / ton small, 120/ton large
- Fan Power 50 / ton
- Economizer Cx 250/unit 10 units for small,
500 large - Cool Cap Redux -1000/ton (this is a cost
reduction) - Wall Insulation 3.85 / sf floor
- Roof Insulation .64 / sf floor
18Measure TRC Cost-Effectiveness Seattle
19Measure TRC Cost-Effectiveness Boise
20Package TRC Cost-Effectiveness
21Electric Bus Bar Savings All Measures
22Weighted Savings B/C
- TRC B/C Ratio 1.2
- Savings 2.0 kWh/sf site and 2.1 kWh/sf at bus
bar - Weighting Factors
- Commercial Valuation from FW Dodge
- HVAC System type heat fuel for lt 100ksf from
CBSA NEEA - Code jurisdiction for window baseline savings
23The End