g - PowerPoint PPT Presentation

1 / 31
About This Presentation
Title:

g

Description:

GE Power Management. Thermal modeling of stator and rotor ... GE Power Management. One of 15 standard overload curves may be programmed based on ... – PowerPoint PPT presentation

Number of Views:145
Avg rating:3.0/5.0
Slides: 32
Provided by: chrisd74
Category:
Tags: ge

less

Transcript and Presenter's Notes

Title: g


1
g
GE Power Management
369 Motor Management Relay
2
g
GE Power Management
369 Motor Management Relay
Offering optimum motor protection in situations
where other relays cannot, the 369 Motor
Management Relay possess the unique feature of
its ability to learn individual motor
parameters, giving it the flexibility to adapt to
each application by learning values of motor
inrush current, negative sequence current K
factor, cool down rates, start thermal capacity
and acceleration time.
3
g
GE Power Management
369 Motor Management Relay
Presentation Overview
  • Applications
  • User Interface
  • Metering and
  • Monitoring
  • Inputs and
  • Outputs
  • Protection and
  • Control
  • Typical Wiring
  • Ordering
  • Communications

4
g
GE Power Management
369 Motor Management Relay
Applications
MAIN
5
g
GE Power Management
369 Motor Management Relay
369 FUNCTIONAL BLOCK DIAGRAM
MAIN
6
g
GE Power Management
369 Motor Management Relay
DEVICE
PROTECTION
Induction Synchronous Motors
  • Large Induction Motors
  • Synchronous Motors

MAIN
7
g
GE Power Management
369 Motor Management Relay
Protection
  • Stator winding
  • overtemperature
  • (R option)
  • Bearing over-temperature
  • (R option)
  • Multiple starts
  • Overloads
  • 15 standard overload
  • curves
  • Phase reversal
  • (M option)
  • User defined overload
  • FlexCurveTM
  • Ground fault
  • Locked rotor
  • Undercurrent
  • Rapid trip/mechanical jam
  • Unbalance/single phasing
  • Variable lock out time
  • Learns individual
  • motor parameters
  • Short circuit
  • Backspin Detection
  • (B option)

MAIN
8
g
GE Power Management
369 Motor Management Relay
Motor Protection
  • Thermal modeling of stator and rotor
  • RTD (resistance temperature unit) and negative
    sequence feedback (R option)
  • Overload protection (15 standard curves plus
    custom FlexCurve)
  • Adapts for hot or cold starts
  • Power factor with time delays (M option)
  • Backspin detection for protection of downhole
    pumps

MAIN
9
g
GE Power Management
369 Motor Management Relay
Start and Running
  • Motor is protected under both Acceleration and
    Running
  • conditions

The 369 can trigger an alarm or trip the motor
based on
  • normal acceleration time
  • number of starts per hour
  • multiple starts
  • time between starts
  • motor overload conditions

MAIN
10
g
GE Power Management
369 Motor Management Relay
Overload
  • One of 15 standard overload curves may be
    programmed based on
  • motor manufacturers locked rotor time
    capability.
  • Alternately the user may program in a custom
    curve using the built-in
  • FlexCurve function.

View 15 Standard Overload Curves
MAIN
11
g
GE Power Management
369 Motor Management Relay
15 Standard Overload Curves
  • The motors service factor value is
  • entered as the overload pickup level

12
g
GE Power Management
369 Motor Management Relay
FlexCurve
When a FlexCurve is programmed, the 369 develops
a smooth custom overload curve within a selected
range.
FlexCurve can be used to protect motors which
have different rotor and stator damage, allowing
total motor design capacity with complete
protection.
13
g
GE Power Management
369 Motor Management Relay
Thermal Modeling
The Thermal Model within the 369 has the ability
to compute the motor I2t value based on actual
motor load current.
  • thermal model calculates value in terms of
    thermal capacity used
  • RTDs (resistance temperature units) measuring
    stator temperature
  • act as a thermal capacity check to confirm
    value calculated by
  • thermal model. RTDs may be used for monitoring
    stator, bearing,
  • ambient, or other temperature monitoring.
  • thermal capacity used is then updated to reflect
    the higher of the
  • two values

MAIN
14
g
GE Power Management
369 Motor Management Relay
Motor Match
MotorMatch modifies the initially entered relay
parameters to match actual measured motor
characteristics. The key elements include
  • accumulated I2t in the memory
  • RTD input to the memory
  • learned cooldown time from run to stop
  • learned cooldown time from run-
  • overload to run-normal
  • learned acceleration time
  • learned negative sequence contribution (K-factor)

MAIN
15
g
GE Power Management
369 Motor Management Relay
RTD Hot Motor Compensation
When hot motor compensation is enabled (R option)
  • RTD feedback from actual stator temperature
  • checks the thermal capacity model
  • User has the capability to match the motor
  • thermal characteristics with a dual slope RTD
  • bias curve
  • The two part curve allows for easy fitting of
    hot
  • and cold motor damage curves to the RTD
  • bias feature

MAIN
16
g
GE Power Management
369 Motor Management Relay
User Interfaces
  • PC Software for setting, monitoring
  • Flash Memory for Future Upgrades or
  • industry modifications
  • 40 character alpha-numeric backlit LCD display
  • Five Target LED indicators
  • 3 RS485 com port (ModBus RTU)
  • Front Panel RS232 port
  • Optional Fiber Optic Port
  • Optional Profibus Port

MAIN
17
g
GE Power Management
369 Motor Management Relay
Control
  • Full remote local control
  • Power factor control
  • Current and Voltage Sensing
  • Two speed motor
  • Testing Switch
  • Emergency Restart

MAIN
18
g
GE Power Management
369 Motor Management Relay
Monitoring
  • Event Recorder (Last 40 Events)
  • Trace Memory (16 Cycle Waveform Capture)
  • Complete Self Checking

MAIN
19
g
GE Power Management
369 Motor Management Relay
Metering
  • Individual Voltages Currents
  • Real, Reactive Apparent Power Demand
  • Real Reactive Power Costs Usage
  • Running Maximum Demand Levels
  • Power Factor
  • Temperatures
  • Backspin Frequency and Predication Time

MAIN
20
g
GE Power Management
369 Motor Management Relay
MAIN
21
g
GE Power Management
369 Motor Management Relay
MAIN
22
g
GE Power Management
369 Motor Management Relay
Communications
  • Modbus protocol (Modicon, Bailey, Siemens,
    Allen Bradley, GE Fanuc, Square D, Honeywell,
    Foxboro, Intellution FIX/DMACS, Wonderware In
    Touch, etc. )
  • Windows based
  • Access all
  • Actual Values
  • Setpoints
  • Status
  • Event records
  • Graphical trending
  • Setpoint programming
  • Setpoint files
  • Download update
  • firmware to Flash
  • memory
  • Oscillography

MAIN
23
g
GE Power Management
369 Motor Management Relay
Metering
Actual Values
  • average and individual phase currents
  • RTD temperatures (hottest, individual, maximum)
    (R option)
  • unbalance ratio
  • ground leakage current
  • thermal capacity remaining / estimated time to
    trip
  • at present overload level
  • motor load as a percent of full load
  • phase to phase or phase to neutral voltage
    voltage
  • (meter option)
  • W, var, Mwhr, PF, Hz (M option)

MAIN
24
g
GE Power Management
369 Motor Management Relay
Monitoring
Prior Alarms
  • immediate overload/stall warning
  • ground fault
  • mechanical jam
  • unbalance
  • undercurrent
  • RTD overtemperature, broken RTD sensor,
  • low temperature RTD (R option)
  • self-test-service
  • under/overvoltage (M option)
  • low power factor (M option)

MAIN
25
g
GE Power Management
369 Motor Management Relay
Monitoring
Fault Diagnosis
  • 369 displays the cause of the trip and
  • will show the remaining lock-out time if
    applicable
  • cause of the last trip and pre-trip values can
    be
  • recalled for rapid fault diagnosis.

MAIN
26
g
GE Power Management
369 Motor Management Relay
Monitoring
Statistical Data (StatTracTM)
  • StatTracTM provides statistical data of motor
    use for
  • operations monitoring, maintenance, and fault
    diagnosis.
  • Using the Keypad, the user can display
  • running hours and number of starts since last
    commissioning
  • number of all trips
  • number of specific types of trips
  • total Watt-hours (M option)

MAIN
27
g
GE Power Management
369 Motor Management Relay
Inputs
  • General Switch and Digital Counters
  • Any of the Switch inputs can be configured as a
    General or Digital Counter
  • Speed Switch Input
  • enables the user to use an external speed device
  • Differential Relay Input
  • provided terminals to accept contact closure
    from an external
  • differential relay
  • all protective functions grouped through one
    main relay
  • Spare Input
  • spare input terminals configurable to represent
    either a standard contact input
  • (ie-pressure switch), or a specific contact
    input (circuit breaker/contactor status)
  • 52a or 52b contact from a circuit breaker
    positive identification of the position of
  • the breaker(open or closed)

MAIN
28
g
GE Power Management
369 Motor Management Relay
Outputs
  • 4 Output Relay Contacts
  • Trip Relay as main latched output relay
  • Alarm output relay (latched or unlatched)
  • Auxiliary 1 output relay (latched or unlatched)
  • Auxiliary 2 output relay
  • 4 Fully Programmable Analog Outputs (M option)
  • Used to indicate one of motor thermal capacity
    used,
  • motor current, hottest stator RTD, bearing RTD,
    CT
  • secondary current, or other various parameters

MAIN
29
369 TYPICAL WIRING
MAIN
30
g
GE Power Management
369 Motor Management Relay
Ordering
369





369 Basic Unit HI
50-300 VDC / 40-265 VAC control
power LO 20-60 VDC
/ 20-48 VAC control power R
Optional 12 RTD inputs
(built-in) 0 No optional
RTD inputs M
Optional metering package B
Optional backspin detection (incl. metering
0 No optional metering or
backspin detection F Optional Fiber
Optic Port 0 No Optional Fiber Optic
Port P Optional Profibus
protocol interface 0 No
optional Profibus protocol interface
MAIN
31
g
GE Power Management
Contact Information
369 Motor Management Relay
Write a Comment
User Comments (0)
About PowerShow.com