Title: BUILDING AUTOMATION
1A PRESENTATION ON
BUILDING AUTOMATION
2BUILDING AUTOMATION
Title
AGENDA
- INTRODUCTION
- NETWORKS
- CONTROLLERS
- AIR HANDLERS
- CENTRE PLANT
- ALARMA SECURITY
- ROOM AUTOMATION
- BUILDING BLOCKS
- CONCLUSION
3WHAT IS BUILDING AUTOMATION??
- Building automation describes the advanced
functionality provided by the control system of a
building. - BAS core are-
- 1) occupancy schedule
- 2)monitors system performance device failures
- 3)provides email and/or text notifications .
- BAS is often referred to as an intelligent
building system or a Smart home.
4BUILDING AUTOMATION ARCHITECTURE
5NETWORKS
- 1) PRIMARY SECONDARY BUS
- Examples--BACnet, optical fiber, ethernet,
ARCNET, RS-232,RS-485 or a wireless network - 2)PROGRAMMABLE LOGIC CONTROLLERS
- ExamplesZigBee
- 3)INPUT/OUTPUT DEVICES USER CONTROLLERS
- Examples--analog or digital humidity and
pressure sensortherlatinum resistance thermometer
6CONTROLLERS
- Programmable Logic Controllers (PLCs)
- PLC's provide the most responsiveness and
processing power - System/Network controllers
- System/Network controllers may be applied to
control one or more mechanical systems such as an
Air Handler Unit (AHU), boiler, chiller, etc. - Terminal Unit controllers.
- Terminal Unit controllers usually are suited for
control of lighting and/or simpler devices such
as a package rooftop unit, heat pump, VAV box.
7BUILDING ELECTRICAL SYSTEM RISER DIAGRAM
8AIR HANDLERS
- Most air handlers mix return and outside air so
less temperature change is needed. - Analog or digital temperature sensors may be
placed in the space or room, the return and
supply air ducts, and sometimes the external air.
- Actuators are placed on the hot and chilled water
valves, the outside air and return air dampers. - The supply fan (and return if applicable) is
started and stopped based on either time of day,
temperatures, building pressures or a
combination.
9AIR HANDLERS ACHITECTURER
10CONSTANT VOLUME AIR-HANDLING UNITS
- The less efficient type of air-handler is a
"constant volume air handling unit," or CAV. - CAVs open and close dampers .
- They heat or cool the spaces by opening or
closing chilled or hot water valves that feed
their internal heat exchangers. - Generally one CAV serves several spaces.
- VARIABLE VOLUME AIR HANDLING UNITS
- A more efficient unit is a "variable air volume
(VAV) air-handling unit," or VAV. - A VAV air handler can change the pressure to the
VAV boxes by changing the speed of a fan or
blower with a variable frequency drive - Each VAV box supply air to a small space, like an
office. Each box has a damper that is opened or
closed based on how much heating or cooling is
required in its space.
11VAV HYBRID SYSTEM
Another variation is a hybrid between VAV and CAV
systems.1) INTERIOR ZONES operate as in a VAV
system.2) OUTER ZONES differ in that the
heating is supplied by a heating fan in a central
location usually with a heating coil fed by the
building boiler.
12CENTRAL PLANT
- A central plant is needed to supply the
air-handling units with water. - chilled water system
- hot water system
- condenser water system
-
13CHILLED WATER SYSTEM
- Chilled water is often used to cool a building's
air and equipment. The chilled water system will
have chiller(s) and pumps
14HOT WATER SYSTEM
- The hot water system supplies heat to the
building's air-handling unit or VAV box heating
coils, along with the domestic hot water heating
coils (Calorifie) The hot water system will have
a boiler(s) and pumps.
15CONDENSER WATER SYSTEM
Cooling tower(s)and pumps are used to supply cool
condenser water to the chillers.
16ALARMS SECURITY
- Many building automation systems have alarm
capabilities. Notification can be through a
computer, pager, cellular phone, or audible
alarm. - Carbon monoxide and carbon dioxide sensors can be
used to alarm if levels are too high. - Refrigerant sensors can be used to indicate a
possible refrigerant leak. - Security systems can be interlocked to a building
automation system. If occupancy sensors are
present, they can also be used as burglar alarms. - Fire and smoke alarm systems can be hard-wired to
override building automation.
17ROOM AUTOMATION
- Room automation is a subset of building
automation ,more systems under centralised
control, though in this case in one room. - Room automation is corporate boardroom,
presentation suites, and lecture halls, where
videoconferencing equipment, video projector,
lighting control systems,public address
18ROOM AUTOMATION ARCHITECTURE
19PROCESSING SYSTEM
- The use of Microprocessors (calculator chips
Mini computers) - Architecture
- --Input, Memory, Output, Micrpchip
- --Address bus, Data bus, control bus
- 8 , 16, 32, 64 bits
- Microprocessors microcontrollers
20ANALOG DIGITAL I/O MODULES
Analog inputs
Control outputs
Display outputs
Digital inputs
Interrupt inputs
Timer / counter inputs
21I/O M O DU L E
- Interrupt input
- Draw attention of real time system towards
abnormal situations - Attends to interrupt and resumes normal work
- Timer / Counter
- Clock input or Gate input to enable/ disable
timer/counters - Output of timer/counter can be used as interrupts
22DISPLAY CONTROL MODULE
- Manual entry sub module
- CRT controller sub module
- LED / LCD control sub module
- Alarm annunciator sub module
- Printer controller sub module
23BLOCK DIAGRAM
24SCADA
- Supervisory Control And Data Acquisition Systems
- Channel scanning
- Conversion into engineering units
- Data processing
25S C A D A ARCHITECTURE
26Title
P L C
27CONCLUSION
- Opportunities arrive daily to intelligently use
building automation as more than just a connector
of brute force comfort generation systems.
- Growing greener application for building
automation, making all large buildings part of
the electrical grid.
28 Thank You For
Your
Time
29Q U E S T
I O N
S??