Title: FIXED INSTALLATIONS
1FIXED INSTALLATIONS
COMPETENCE STATEMENT 373
2AIM To enable the individual to use a rising main
for firefighting
OBJECTIVES 1) Recognize a dry riser
inlet 2) Recognize a dry/wet riser
outlet 3) State the building heights for dry/wet
risers 4) List the actions to be taken to check a
dry riser system 5) Deploy a firefighting jet
from a riser 6) Describe the system to drain a
dry riser 7) Describe typical locations of
dry/wet riser outlets
3TYPES OF BUILDINGS WITH RISERS
- 1) High rise - Dwelling Offices Factories
- 2) Multi - storey car parks
- 3) Shopping centres
Air valve
Dry rising main
Inlet
Drain valve
4DRY RISER INLET
- 1) Usually housed in a wired glassfronted
box At ground level Near front
entrance External wall - 2) Identified by the words DRY RISERpainted in
red on the glass - 3) Normally two fire service inlets inside the box
5DRY/WET RISER OUTLET
- 1) A valve with a wheel type handle and a female
instantaneous coupling - 2) Direction for opening is shown on the wheel
itself or on a plate between the wheel and the
locking nut - 3) Usually locked closed with a wire and lead
seal or a leather strap to prevent unauthorised
use
6LOCATION OF RISER OUTLET
- 1) a) Firefighting staircase lobby
- b) Enclosed staircase
- 2) On every floor or every alternate floor
- 3) May be in a marked glazed cupboard
7ADVANTAGES OF RISING MAINS
- 1) Hose quickly got to work
- 2) Greater capacity
- 3) Less risk of water damage
- 4) Adjacent buildings are covered
8CHECKING DRY RISER SYSTEM
- 1) Ensure all landing valves are closed prior to
charging - 2) Drain after use
- 3) Ensure all landing valves are closed before
leaving - 4) Report any defects to a responsible person
9DEPLOYING A FIREFIGHTING JET FROM A RISER
- 1) Two lengths of 45mm hose and a branch will
have been supplied to the floor below the fire - 2) Taking hose through fire doors from stairwell
to corridor where fire is may allow products of
combustion to affect bridgehead - 3) It may be possible to use Fixed Installation
hosereels - 4) Commence salvage operations on the floor below
the fire as soon as possible
10DRAINING A DRY RISER
- 1) Drain hose out of a window and disconnect
- 2) Close landing valves
- 3) Open drain cock at riser inlet
- 4) If auto air valve is not fitted open top
landing valve - 5) If top landing valve was opened close it
11QUESTIONS
- 1) State the building heights for both dry and
wet risers - Buildings greater than 18m Dry Riser.
- Buildings greater than 60m Wet Riser.
- 2) Where would the dry riser inlet usually be
found? - At ground level.
- Near front entrance.
- External wall.
- 3) What is the purpose of the air valve in a dry
rising system? - Vents air out of system when charging and lets
air into system when draining.
12QUESTIONS contd
- 4) List four advantages of using rising mains
- Hose quickly got to work.
- Greater capacity.
- Less risk of water damage.
- Adjacent buildings are covered.
- 5) List the precautions taken when checking dry
risers - Ensure all landing valves are closed prior to
charging. - Drain after use.
- Ensure all landing valves are closed before
leaving. - Report any defects to a responsible person.
13QUESTIONS contd
- 6) Where are riser outlets normally found?
- Firefighting staircase lobby.
- Enclosed staircase.
- On every floor or every alternate floor.
- May be in a marked glazed cupboard.
- 7) Name three types of building where risers are
normally installed - High rise- Dwellings
- Offices
- Factories
- Multi-storey car parks
- Shopping Centres
14QUESTIONS contd
- 8) What device is fitted to landing valves to
protect fire brigade hose and on what type of
riser would it be found? - Pressure regulators on Wet Risers.
- 9) What are the three sources of water for a wet
riser? - 1) Water Main, 2) Gravity Tanks, 3) Booster
pumps supplied from storage tanks. - 10) What is the procedure for draining a dry
riser? - a) Drain hose out of a window and disconnect.
- b) Close landing valves.
- c) Open drain cock at riser inlet.
- d) If auto air valve is not fitted open top
landing valve. - e) If top landing valve was opened close it.