Title: SYMMETRICAL COMPONENETS OF POWER SYSTEM
1 SYMMETRICAL COMPONENETS OF POWER SYSTEM
- BY TANDIN JAMTSHO
- MScE STUDENT
- STUDENT 3226091
2OUTLINE OF THE PRESENTATION
- INTRODUCTION
- NEED FOR THE SYMMETRICAL COMPONENET METHOD
- TECHINQUES USED TO ANALYSIS SYMMETRICAL
- SYMMETRICAL METHODS USED TO STUDY POWER SYSTEM
FAULTS - CONCLUSION
- REFERENCES
3INTRODUCTION
- The normal operating conditions of an electric
power system are occasionally disrupted because
of faults. - Analysis of power systems usually implies the
computation of network voltages and currents
under a given set of conditions. - Under many circumstances we tend to ignore the
unbalanced operation in the system and unbalanced
operation is always present. -
4An organization of power system analysis problem
5Effects of faults on power system
- Flow of excessive current
- Abnormal voltages
- Voltage elevation of system neutral
- Induce over voltages on neighbouring equipments .
- Hazards to human, equipment and animals.
6Need for fault analysis
- Design of protection system requires the
knowledge of fault current. - The information obtained from the fault studies
are used - to select the sizes of circuit breaker,
- fuse and characteristic,
- setting of relay.
7Normal types of fault are
- Fault due to lightning
- Tree limbs falling on the line
- Wind damage
- Insulation deterioration
- Vandalism
8Types of fault
- Symmetrical fault
- Usually three phase to ground fault
- Unsymmetrical fault
- The fault is unbalanced in nature
9Sources of Asymmetrical fault are (Reference2)
10Sources of Asymmetrical fault are (cont.)
- One phase open circuit
- Unbalanced in load mainly the arc loads
11Sources of Asymmetrical fault are (cont.)
12Sources of Asymmetrical fault are (cont.)
13Need for the symmetrical component analysis
- Negative sequence relay in generator has helped
in protecting the generator from over heating in
the event of unbalanced loads. - The positive sequence segregating network is
used to supply the sensing voltage to generator
voltage regulators - Certain connections of CT and PT develop zero
sequence components that are used in protective
ground relaying scheme.
14Method of adopted for symmetrical component
analysis (cont)
- Mathematically
- Va Va1 Va2 Va3---------- Van
- Vb Vb1 Vb2 Vb3---------- Vbn
-
- Vn Vn1 Vn2 Vn3---------- Vnn
- Where
- Va, Vb. Vn are unbalanced set of phosors
- Va1, Vb1 Vn1 first set of n balanced phasors
with an angle 2pi/n - between components a,b,..n
15Method of adopted for symmetrical component
analysis (cont)
- Mathematically
- Va2, Vb2 Vn2 second set of n balanced phasors
with an angle 4pi/n between components a,
b,..n - .
- Va(n-1), Vb(n-1) Vn(n-1)are (n-1)th set of n
balanced phasors with an angle 2pi(n-1)/n between
components a, b,..n
16Phasor a or a-operator
- The phasor notation of a-operator
17Phasor a or a-operator
18Phasor a or a-operator
19Equation in matrix form
20Symmetrical components for three Phase system
- The n-phase system presented above is of academic
interest only and only the practical three phase
system will be emphasised. - Power is generated, transmitted and consumed
mostly in three phase only. -
21Symmetrical components for three Phase system
(cont)
- The phasor representation of three phase system
(source reference2) -
22Symmetrical components for three Phase system
(cont)
- The positive sequence set consisting of three
components of equal magnitude, displaced by 120
240o respectively and having the phase sequence
of abca. - The negative sequence set consisting of three
components of equal magnitude displaced by 240
120o respectively, having phase sequence of acba. - The zero sequence set of the component of which
being equal both in magnitude and and phase. -
-
23Symmetrical components for three Phase system
(cont)
- Relations of voltage components in matrix form
-
24Symmetrical components of generator
25Symmetrical components of generator
26Symmetrical components of transformer (zero)
27Fault analysis using symmetrical components
- The most common type of fault is the single line
to ground fault -
28Fault analysis using symmetrical components
(cont)
- The sequence component connection for the single
line to ground fault -
29Fault analysis using symmetrical components
(cont)
- The sequence component connection for the single
line to ground fault - The sequence components are connected in series.
- The three currents in the case of SLG fault are
equal. -
30Fault analysis using symmetrical components
(cont)
31Fault analysis using symmetrical components
(cont)
- LL fault
- There is no zero sequence component due to
absence of ground return path. - The positive and negative sequence components are
connected in parallel.
32Fault analysis using symmetrical components
(cont)
33Fault analysis using symmetrical components
(cont)
- LLG fault
- For the zero sequence component it requires to
add an external impedance of Zf3Zg - The networks are connected in parallel.
34Software available for carrying fault analysis
- The most commonly used soft ware are
- MATLAB
- EDSA
- ETAP
- CYME
35Conclusion
- Power system analysis using symmetrical component
is very helpful in improving the reliability of
the power system. - The principle adopted for the analysis of
unbalanced fault system is symmetrical component
method. - By knowing the principle, the results obtained
from the computer can be analysed.
36References
- 1. Paul M. Anderson, Analysis of Faulted Power
Systems. - 2. W.D. Stevenson, Elements of Power System
Analysis. - 3. A.P.S Meliopoulos, Power System Grounding and
Transients. - 4. Olle. I. Elgerd, Electric Energy Systems
Theory. - 5. IEEE Transactions