Title: Coordinated HVDC Damping Control basedon WAMS
1Coordinated HVDC Damping Control based on WAMS
- Wu Xiao-chen
- China Southern Power Grid Co., Ltd
- Oct., 2008
2Background
2002.4.4
2003.2.23
2003.3.7
2005.5.13
2005.9.1
Osci. Events in CSG
2006.8.29
2008.4.21
2008.8.25
18000MW
8
3
HVAC
HVDC
3Background
GZ
YN
GD
4Rapid development
South China in one of the most booming area in
the world
CSG
5WAMS in CSG
6Challenges and Chances
Challenges to Security of Grid
Chances to new damping tech.
- Oscillatory instability, especially inter-area
oscillation, limits the transfer capability of
CSGs backbone - CSG plants larger than 200 MW (Coal) or 50 MW
(hydro) are all equipped with PSSs - Oscillatory instability problems will be more
severe in next 5 years
- Three HVDC links with total transmission capacity
of 7800 MW in backbone - HVDC modulation can change the dynamic of AC
systems effectively - A large scale WAMS had been established in CSG
CSG launching a project to develop HVDC Damping
Control System based on WAMS (ab. HDCS)
7Process of the Project
6
2008.7
5
2008.4
- Closed-loop testing in the field
4
- Open-Loop trial operation and close-loop test
operation
2007.12
3
- Installation at seven stations
2007.6
2
- Manufacture of central station, control unit
2007.3
1
2006.5
From 2005 to 2008, theory to implementation
- Theoretical study and designing
8Overview of Key technologies
- Tuning of multiple damping controllers
- Countermeasures to time delay
- Adaptive of controller para.
- Interface to HVDC Pole Control
- Selection of input signals
9Basic designing ideas
- There are two dominant oscillation modes in CSG.
One is generators in GZ YN swing against GD
around 0.4 Hz, while the other is generator in GZ
swing against YN around 0.57 Hz - The GGI HVDC, with the rectifier station locating
in the GZ, shows good performance in damping
oscillation mode of YN .vs. GZ. The GGII HVDC,
with the rectifier station near the middle of
intertie of YN GZ, has much more impact on GD
.vs. GZYN mode than GZ .vs. YN mode - GGI damping YN .vs. GZ oscillation GGII
damping GD .vs. GZYN oscillation
10Architecture of HDCS
- CSGs HDCS is a six inputstwo-outputs control
scheme. Inputs are colleted from three 500 kV AC
stations and three 500 kV converter stations.
Two stations are at GZ (AnShun, GaoPo), one near
the GZYN border (XingRen), one is at YN
(LuoPing), and two are at GD (LuoDong, BaoAn).
There inputs are not only for control order
calculation, but for some criteria to start/stop
control actions
11Architecture of HDCS
- Centralized control scheme. The central control
station is located at control center of CSG in
Canton - Control unit placed at the rectifier station of
HVDC systems
12Deal with Time-delay in Wide-Area Control Loops
- Time delay in control loops may deteriorate the
performance of damping controller, even leading
to adverse control actions - During the design and RTDS test of CSGs HDCS, it
is first time observe that high frequency
constant amplitude oscillations can be caused by
a certain value of time delay exist in control
loops - Lead-lag blocks plus band-pass filter are used to
mitigate the effect of time-delay
13Control Blocks and Tuning
- One contribution of our project is to develop a
practical tuning method for MIMO control systems
in bulk power system. With a hybrid stochastic
programming method combined with GA SA, an
optimization-based tuning algorithm is
successfully used in tuning of CSGs HDCS.
14Adaptive Control algorithm base on Online Prony
- An online Prony algorithm was developed in HDCS
to monitor change of oscillation mode in real
time environments - In case of the current oscillation modes bias the
center frequency of filter too much, adaptive
algorithm will adjust parameters of filter and
lead-lag blocks
15Hardware and software
- Central control station has three functional
components control computer, data storage
computer and HMI computer - Control unit connected to Pole Control cubicles
of HVDC through cables has a small text display
status monitor and a sequence of events recorder
16Hardware and software
- The control execution rate at present is 100
control executions per second (10-ms intervals),
which is the same rate as the phasor measurement
packets - All the data are stored and managed in a
real-time database of central control station,
tagged with precise time
17Delay Time in the Control Loop
- The total delay time in control loop of WADC is
around 110 ms. - Delay time for fiber-optic communications is less
than 15 ms - Data processing in central control station around
15 ms, - execution of command from control unit in Pole
Control of HVDC is around 40 ms - 40 ms is contributed by data processing in PMU
18Safe Failure Technology
- PMU will add alarm status word to the data
transmitted to central station in case of
disconnect of CT of GPS failure - Interruption of communication will trig the
central control system to send Control-off
command to control unit which will ramp down the
current modulation command. - The current HVDC active power is also inputted
into central station to evaluate the ability of
HVDC to execute modulation orders
19Interface to HVDC
- The interface receives binary and analog signals
from control units, and interprets them to Pole
Control of HVDC - The interface can block the input from control
unit as soon as external signals are implausible
20Test of HDCS
- Three tests Scheme Checks, Logic Tests and
Remote Modulation Tests - The Scheme Checks is used to verify the physical
connections between components of HDCS. - The Logic Test tests logic inside central control
station, involving control blocks and
block/deblock functions. - The Remote Modulation Test verifies that the
continuous modulation orders from central control
station can be executed by Pole Control of HVDC
exactly. - At the end of tests, the HDCS was operating in
closed-loop manner for three hours to observe its
steady-state performance.
21Trial operation in open-loop mode
- During trial operation, the cable connection
between control units and cubicles of HVDC Pole
Control were disconnected. All functions of WADC
were normally operating except that the command
from HDCS will not be executed by HVDC.
22Two osci. Events during trial operation of HDCS
23Outputs of HDCS in two osci. events
Inputs during 1st event
1V output of control unit corresponding to 200 MW
modulation of HVDC
Inputs during 2nd event
24Torque analysis of HDCSs output
0.01
-0.01
25Closed-loop field testing
- In the early morning of July 20, 2008, CSG
triggered the same kind of large disturbances
twice within one hour. Before the first
disturbance, the connection between HDCS and Pole
Control of HVDC was restored and the control
system can really work. Before the second
disturbance, the control system was shut down.
Power system dynamics during the two events were
recorded and compared - The test results showed that the control system
can increase damping ratio of critical inter-area
oscillation mode by 0.1 (without the control
system damping ratio 9 with the control
system damping ratio 19)
26Output of HDSC during the test
27Comparison of osci. in AC lines
28Prony analysis of the results
29Wavelet transform of the results
Open-loop
Closed-loop
30Conclusions
- Moving from wide-area measurements to wide-area
stability control is a challenge in the new
century. - CSG HDCS exploits advances in digital/optical
communications and computation. - For inter-area oscillation, HDCS improved
observability and controllability compared to
local control - High reliability of HDCS has been proved in
open-loop trial operation - Closed-loop field testing shows that HDCS can
improve the damping of inter-area oscillations in
CSG effectively.
31Thank you for your attention!