Title: CO2based Demand Controlled Ventilation DCV
1CO2-based Demand Controlled Ventilation (DCV)
04/05/2006 Ryan R. Hoger Commercial Controls
Mgr. Temperature Equipment Corp.
ryan.hoger_at_tecmungo.com
2Benjamin Franklin on Ventilation (c. 1794)
- I considered fresh air an enemy,
- and closed with extreme care
- every crevice in the rooms I inhabited
Experience has convinced me of my error. I now
look upon fresh air as a friend. I even sleep
with an open window
I am persuaded that no common air from without is
so unwholesome as the air within a closed room
that has been often breathed and not changed.
3Comfort Is More Than Just The Right Temperature
Ventilation Control
- Comfort
- Temperature Ventilation
4How is ventilation provided in buildings today?
Ventilation Control
The same way it was in 1930. With Fixed
Ventilation!
5Fixed Ventilation
Building codes require ventilation rates based on
cfm/person (typically 20 cfm/person)
Max Occupancy 25 people 500cfm
Actual Occupancy 5 people 500cfm
Actual Occupancy 1 person 500cfm
Inefficient!
6Ventilation Control
Fixed Ventilation In a Multi-Zone VAV Building
Total cfm Max occupants X 20 cfm
There Is No Control!
7Temperature Control InA Multi-Zone VAV Building
- Measure In Each Zone
- Control Based On Actual Load
What if we did the same thing with ventilation?
8Great Idea!
Delivers The RIGHT Amount of Fresh Air, To The
RIGHT Place, At The RIGHT Time
But How Does It Work?
9Controlling Ventilation
There is a clearly defined relationship between
indoor CO2 levels ventilation rates
established by Indoor CO2 levels are a
measure of ventilation rates (cfm/person) CO2
levels are not a measure of overall IAQ.
CO2 is the control parameter for ventilation!
10CO2 Basics
- CO2 is NOT a contaminant, it is a colorless,
odorless gas found naturally in the atmosphere - Outdoor levels are fairly constant at 400 /- 25
ppm - Typical indoor levels 400 to 2,500 ppm
- Not harmful unless concentrations reach 30,000
ppm - Carbon Monoxide (CO) and Carbon Dioxide are NOT
the Same
11CO2 Basics
People exhale CO2 at concentrations of 4 (40,000
ppm) Normal room concentrations are in the range
of 400 - 1200 ppm As a gas, CO2 diffuses and
equalizes rapidly throughout a room (like
humidity)
12CO2 and Ventilation Rates
- CO2 production by people is very predictable
based on activity level - Doubling the people in a room will double CO2
production
13CO2 and Ventilation Rates
CO2 levels will build until an equilibrium level
is reached with outside air entering the space
5 cfm/person
10 cfm/person
15 cfm/person
20 cfm/person
30 cfm/person
14CO2 and Ventilation Rates
Two Sources of CO2 in Buildings are People or
Exhaled CO2 and Outdoor Air Indoor CO2 Levels
Mix of Exhaled CO2 with Outdoor Air Same as
mixing a cup of extremely strong coffee
(breathing) with a bucket of weak coffee (Outdoor
Air) The resulting concentration (Indoor CO2
Level) can be calculated
15CO2 and Ventilation Rates
Vo N/(Cs - Co) Office Space Met Level of 1.2
0.30 L/min (0.0107ft3/min) Outside CO2
concentration is 400 ppm or 0.04 Inside CO2
concentration is 1100 ppm or 0.11 Vo (0.0107
ft3/min)/(0.0011-0.0004) or 15 cfm Cs
Co N/Vo Cs 0.0004 (0.0107 ft3/min/15
ft3/min) 0.0011 or 1100 PPM
Vo Outdoor air flow rate Ve breathing rate N
CO2 generation rate per person Ce CO2
concentration in exhaled breath Cs CO2
concentration in the space Co Co2 concentration
in outdoor space
Source ASHRAE 62-1989 Appendix D
16CO2 and Ventilation Rates
Also can be expressed as... Rp 8,400 X m
CR - COA Where Rp The rate of outdoor air
per person (cfm/person) m The metabolic rate (1
met 58.2 W/m2). The default metabolic rate is
1.2 mets. COA The outdoor air CO2 concentration
(ppm). The default outdoor air CO2 concentration
is 400 ppm. CR The room CO2 concentration (ppm)
measured by
17CO2 and Ventilation Rates
Example 1 Person in an Office
Outdoor Air OA Ventilation Rate 20
cfm/person OA CO2 ppm 400 ppm CO2 Production
by People CO2 Production 0.0106
cfm/person Concentration 1,000,000 ppm
18CO2 and Ventilation Rates
Example
Outdoor Air (20 ft3/min/person _at_ 400 ppm)
What is the CO2 level for one person in the room?
People
People CO2 (0.0106 ft3/min/person _at_ 1,000,000 ppm)
Outdoor Air
19CO2 and Ventilation Rates
What happens with 2 people in the room?
20CO2 and Ventilation Rates
What happens with 100 people in the room?
21CO2 and Ventilation Rates
What is the Control Point for a 15 cfm/person
ventilation rate?
Outdoor Air (15 ft3/min/person _at_ 400 ppm)
People CO2 (0.0106 ft3/min/person _at_ 1,000,000 ppm)
Value Given in ASHRAE 62-1989
22CO2 Equilibrium Levels
CO2 Levels Will Build And Level Off At The Point
Were CO2 Produced By People Is In Equilibrium
With Outside Air Ventilated Into The Space
23Ventilation Control
Actual Occupancy 25 people 500cfm
Actual Occupancy 5 people 100cfm
Actual Occupancy 1 person 20cfm
Ventilation based on actual occupancy!
24With Zone Ventilation Control in a VAV Building
Zone Ventilation Control
Healthy Efficient!
Healthy Efficient!
25Zone Ventilation Control
OK! But How Do We Do It?
26Zone Ventilation Control
Zone level DDC VAV and VVT control systems that
automatically give you the ventilation you need
only when you really need it.
27Zone Ventilation Control
28Numerous Studies Confirm that Correct Ventilation
Zone Ventilation Control
- Increases Productivity
- Improves Occupant/Customer Satisfaction
- Helps Prevent Sick Building Syndrome Health
Affects
DOE/Lawrence Berkeley Labs Indoor Environment In
Schools Pupils Health Performance In Regard To
CO2 Concentrations A significant correlation was
found between decreased performance and high CO2
levels (lower ventilation rates).
29Numerous Studies Confirm that Correct Ventilation
Zone Ventilation Control
- Increases Productivity
- Improves Occupant/Customer Satisfaction
- Helps Prevent Sick Building Syndrome Health
Affects
Air Quality and Ventilation ranked very high
(2 of 25) on the list of tenant retention
issues in a recent survey conducted by Real
Estate Information Systems.
30Numerous Studies Confirm that Correct Ventilation
Zone Ventilation Control
- Increases Productivity
- Improves Occupant/Customer Satisfaction
- Helps Prevent Sick Building Syndrome Health
Affects
Economic Considerations of Air Quality and
Ventilation in Offices (US EPA) Improvements in
the indoor air environment substantially increase
employee morale and productivity.
31Numerous Studies Confirm that Correct Ventilation
Zone Ventilation Control
- Increases Productivity
- Improves Occupant/Customer Satisfaction
- Helps Prevent Sick Building Syndrome Health
Affects
DOE/Lawrence Berkeley Labs Evaluation of Sick
Leave Statistics vs. Ventilation Rates (3720
employees / 40 buildings) Optimal ventilation
reduces sick time costs. For
every 1 spent on ventilation cost, 2 are
saved in sick time.
32Ventilation Control
Benefits of Ventilation Control
ASHRAE Standard 62
Using CO2-based ventilation control ensures
compliance to codes and standards
33ASHRAE Interpretation IC 62-1999-33
Ventilation Control
- It is consistent with the Ventilation Rate
Procedure that demand control be permitted for
use to reduce the total outdoor air supply during
periods of less occupancy
34Commentary To The International Mechanical Code
(IMC)Section 403.3.1
Ventilation Control
- The intent of this section is to allow the rate
of ventilation to modulate in proportion to the
number of occupants. This can result in
significant energy savings. Current technology
can permit the design of ventilation systems that
are capable of detecting the occupant load of the
space and automatically adjusting the ventilation
rate accordingly. - For example, carbon dioxide (CO2) detectors can
be used to sense the level of CO2 concentrations
which are indicative of the number of occupants.
People emit predictable quantities of CO2 for any
given activity, and this knowledge can be used to
estimate the occupant load in a space.
35Chicago Ventilation Code
18-28-403.1.2 Demand ventilation. The amount of
outside air delivered by a mechanical supply
system may be reduced during operation below the
quantities listed in able 18-28-403.3 if the
system is capable of measuring and maintaining
CO2 levels in occupied spaces no greater than
1000 ppm. The system capacity shall be greater
than or equal to the ordinance requirements.
36A Better Operating Building
Zone Ventilation Control
- Ventilate to Actual vs. Assumed Occupancy
- Eliminate Wasteful Over-Ventilation
- Very Attractive ROI/Lower Operating Costs
37DCV Savings
This chart compares ventilation usage throughout
a typical day using purple to represent demand
controlled and green to represent constant.
The difference between the two equates to
significant savings.
38DCV Savings
Average Occupancy Schedule (For Occupied Days)
Relative To Design Occupancy
0 4 8 12 16 20 24
Average occupancy pattern by building type
39Research Findings Demand Control Ventilation
Energy required, DCV control applied
Energy wasted - no DCV
HUGE Savings
40Examples of Potential Energy Savings and ROI
41Zone Ventilation Control Examples
42Red Wing School District, MN
Zone Ventilation Control
- Driver
- Comfort/Productivity
- Need For Quick Response To Complaints
- Results
- Problem areas identified and corrected quickly
- (over and under ventilation).
- Teacher concerns resolved quickly.
43LaSalle Plaza, MN
Zone Ventilation Control
- Driver
- Energy Savings
- Tenant Comfort/Satisfaction
- Results
- Significant reduction in heating and cooling
costs (200k 1st year) - 3 month ROI
44Purdue University, IN
Zone Ventilation Control
- Drivers
- Energy Savings
- Productivity/Learning
- Low Maintenance Solution
- Results
- The installation provided a 1 to 2 year payback
- (Luci Keazer, Controls Engineer)
45Harley Davidson, WI
Zone Ventilation Control
- Drivers
- Productivity
- Comfort
- Total Quality Environment
- Results
- An Important part of Harleys Quality Program for
a comfortable and productive work environment. -
46Application Stepsfor CO2 Ventilation Control
47Step 1 Determine if CO2 Control is Appropriate
- Factors that may affect the application of CO2
control are - Building pressurization
- Ventilation requirements other than ASHRAE 62 or
the IMC - Special requirements for control of hazardous
materials
48Step 1 Determine if CO2 Control is Appropriate
49Step 2 Determine the Design Ventilation
Requirement
- Ventilation required when the building is fully
occupied - Ventilation rate used for sizing the HVAC
equipment - Outdoor air requirement/damper setting when DCV
is not used, previously known as minimum
ventilation
Design Ventilation
50Step 2 Determine the Design Ventilation
Requirement
- For Constant Volume Systems
- Same as current method
- Multiply the per person ventilation rate
(required by codes) by the number of design
occupants - For example if an office space is designed for
100 people - Design Ventilation 20 cfm/person 100 people
- 2,000 cfm
51Step 2 Determine the Design Ventilation
Requirement
- For Multiple Zone VAV Systems
- When using CO2 Control, the Multiple Space or
Critical Space equation is NOT required. - CO2 control ensures the correct ventilation to
each zone - Calculate design ventilation the same as a
constant volume system
52Step 3 Calculate the Base Ventilation Rate
- Base ventilation establishes the lowest outdoor
air rate during times when the building is
sparsely occupied - Must be adequate to
- Balance supply, exhaust, and building
pressurization requirements - Dilute any non-occupant related contaminants
Design Ventilation
Base Ventilation
53Step 3 Calculate the Base Ventilation Rate
- Typical base ventilation is between 20 - 30 of
design - Retail and new buildings may want to use 40 of
design due to higher concentrations of
non-occupant related contaminants
Design Ventilation
Base Ventilation
54Step 3 Calculate the Base Ventilation Rate
- For VAV Systems
- To ensure the base ventilation rate is delivered
at light loads - Set all zone dampers to their base ventilation
rate - Ensure the unit is maintaining the design static
pressure - Set the outside air damper to bring in the
buildings base ventilation
55Step 4 Choose the Control Strategy
Determine the CO2 Control Point
- CO2 Control Point Depends on
- Outdoor CO2 Level (typically 400 ppm)
- Required cfm/person ventilation rate
- If OA CO2 is 400 ppm
- 20 cfm/person 930 ppm CO2
- 15 cfm/person 1,100 ppm CO2
- 10 cfm/person 1,450 ppm CO2
56Step 4 Choose the Control Strategy
- Set Point (Relay) Control
- Simplest control strategy (two position damper)
- When the CO2 level reaches the Control Point,
outside air delivery Increases from the base to
the design level - When the CO2 level drops 200 ppm below the
Control Point, outside air drops back to the base
level - Use in high occupant density applications that
reach peak levels quickly (i.e. classrooms) - Use only where one air handler serves a single
zone.
Design Ventilation
Base Ventilation
57Step 4 Choose the Control Strategy
- Proportional Control
- Dampers open as the CO2 level rises
- Set minimum damper position to 20-30 of design,
start modulation at 100 ppm over outside levels
(500 ppm). When CO2 level reaches the control
point, the outdoor air system brings in design
ventilation levels - Responds quicker to small changes in occupancy or
CO2
58Step 4 Choose the Control Strategy
- Proportional-Integral Control
- Ventilation system responds to both the CO2
level and rate of change - Best performance from both a comfort and total
energy savings perspective - Works well in all applications
CO2 Control Point
Increased CO2 Levels
59Step 5 Locating CO2 Sensors
- Use duct sensors only when one HVAC unit serves
one occupancy zone - Locating Wall-Mounted Sensors
- Similar to Tstat
- Centrally located in the space
- Away from doors and windows
- Avoid putting next to where people congregate
(water coolers) - 4 feet and higher on the wall
- A wall-mounted CO2 sensor can cover up to 5,000
ft2 of open space - For VAV systems, locate at least one CO2 sensor
in each occupancy zone
60Step 5 Locating CO2 Sensors
61ApplyingCO2 Ventilation Control
62Applying CO2 Sensors
- Most economizer controls accept a CO2 (or IAQ)
input - Most HVAC manufacturers have incorporated CO2
ventilation control into their rooftops - Most building management systems also can utilize
CO2 control
63OEM Rooftop Equipment
- Many factory mounted rooftop controllers/
economizers can accept a CO2 sensor input
directly. - In many cases the logic to modulate the dampers
(including economizer overrides) is built
in.consult manufacturers literature for
details. - If not present, an economizer or motorized damper
is required.
641916 Engineers Handbook
Is Using CO2 to Measure Ventilation a New Idea?
CO2 tests should be used for checking the
renewal of air and its distribution within the
room. the CO2 should NOT exceed 8 or 10
parts in 10,000
65DCV Timeline
VAV
CO2
2004 ASHRAE Standard 62 update adds DCV to body
of standard
2000 Intro of low cost temp/CO2 sensor enabling
affordable zone level DCV
1916 Mechanical Engineers Handbook Explains
relationship between CO2 and ventilation
1929 NY Building code details CO2 levels shall
not be greater than one part in one thousand
1973 Energy crunch introduce VAV system for
commercial buildings
- 1989
- ASHRAE Standard 62-89 increases
- ventilation rates, foundation for DCV and 1000
PPM rate
1997 Interpretation IC-62-1989-27 clarifies use
of CO2 as a method of controlling ventilation
based on occupancy
1999 ASHRAE 62-99 eliminates 1000 PPM CO2
threshold in/outside differential introduced
66Why Now?
- Digital Control Systems
- Integration of ventilation control
- Increased Ventilation Rates (ASHRAE/IMC)
- Increasing Energy Costs
- Decreasing Sensor Costs (First Life Cycle)
Increased Sensor Reliability
67Sensor Cost
- Control system integration
- Sensor technology and integration (CO2
Temp) - Volume increases
1500
Installed Cost Per Point
500
1992
1997
2003
68Sensor Reliability
- 15 Year design life
- Non-interactive, selective to CO2 only
- Stable - lifetime calibration
69Sensor Technology
Cost Effective Zone Level CO2 Temp Sensor
70Sensor Technology
IR Detector
IR Source
- Target gas absorbs radiation at signature
wavelength - Filter isolates wavelength that reaches detector
- More gas in chamber leads to lower signal to
detector
0 ppm CO2
Wavelength Filter
IR Detector
IR Source
1000 ppm CO2
Wavelength Filter
IR Detector
IR Source
2000 PPM CO2
Wavelength Filter
71Sensor Technology
Long life expectance (15 years) Lifetime
calibration guarantee Selective - no interference
with other gases Stable - does not require
calibration
72Self Calibration of a CO2 Detector
- Automatic Baseline Calibration (ABC Logic)
- Self calibrating algorithm
- Considers lowest CO2 level every 24 hrs
- Looks at long term changes in baseline
- Applies a correction factor for calibration
73Self Calibration of a CO2 Detector
74Sensor Reliability
Self Calibration Over 14 Days
75Long Term Sensor Stability
76Infrared Absorption Of Gases
77Infrared Design
- Current Design Product Of Over 10 years/50,000
units of Experience - Infrared source emits energy through the patented
waveguide - Optical filter eliminates all but CO2 target
wavelength - Detector measures amount of infrared energy and
sends the signal to - the microprocessor
- More CO2 in the chamber means less infrared
energy reaches the detector
78Wall-Mount Ventostat 8001 8002
- Single Channel Sensor w/ and w/o Display
- Utilizes ABC Logic - Requires No Calibration
791508 Aspiration Box
- Compatible with 8000 9000 Series Sensor
Platforms
80Duct-Mount Ventostat 8007 8008
- Pitot Sampling Measurement Incorporated into the
8000 Sensor Platform - Lower-Cost Alternative to Aspiration Box
- Allows Mounting of Sensor Remote from Duct
81Wall-Mount CO2/Temp Airestat 5010 5011
- Designed Specifically for VAV Applications
- Utilizes ABC LogicTM - Needs No Calibration
- Utilizes 10K Thermistor
- Optional Slide Pot Adjustment
82Zone Ventilation Control
Whats new in ASHRAE 62-2004
83Zone Ventilation Control
Whats new in ASHRAE 62-2004 As stated in
forward of 2004 standard
- IAQ procedure has been restated to include
mandatory and enforceable language - Appendix G has been added as a guideline for
application and enforcement of the standard - Requirements have been added to ensure air
systems are capable of delivering outdoor air to
occupied spaces - Air cleaning requirements have been added when
OA is unacceptable
84Zone Ventilation Control
- Ventilation Rate procedure introduces the
concept of the Breathing Zone, changes
calculations for zone and system ventilation
rates to include area and people related
components, changes the multiple space equation
to include components for space air distribution
and system efficiency - All tables for ventilation rates are specified
for non-smoking areas - Air type and quality classification standards
have been added
Whats new in ASHRAE 62-2004 As stated in
forward of 2004 standard
85Zone Ventilation Control
Whats new in ASHRAE 62-2004
- CO2 based Demand Controlled Ventilation is now
specifically stated in the body of the
standard - Section 6.2.7 of the Ventilation Rate Procedure
- Dynamic Reset. The system may be designed to
- reset the design outdoor air intake flow (Vot)
and/or space or - zone airflow as operating conditions change.
These conditions - include but are not limited to
- 1. Variations in occupancy or ventilation airflow
in one or - more individual zones for which ventilation
airflow requirements will - be reset.
- Note Examples of measures for estimating such
variations include - occupancy scheduled by time-of-day, a direct
count of occupants, - or an estimate of occupancy or ventilation rate
per person - using occupancy sensors such as those based on
- indoor CO2 concentrations.
-
86Zone Ventilation Control
Whats new in ASHRAE 62-2004
- Calculations for Ventilation Requirements in the
Breathing Zone now provide for - Population density based upon Table 6-1 or the
expected population - Space ventilation requirements are added to
people related ventilation requirements based
upon values in Table 6-1 - Short term conditions (starting and stopping of
mechanical equipment, highly variable
occupancy, intermittent OA intake) are
accounted for in equations 6-9a and 6-9b
This can reduce the design ventilation
requirements
87Zone Ventilation Control
Whats new in ASHRAE 62-2004
- Concerns over new standard
- 15 and 20 CFM per person in the previous
standard was easily understood and implemented.
Some say the new standard is more difficult to
enforce. - With the 2001 standard, code officials could
calculate ventilation requirements for zones
without the use of spreadsheets and engineering
tools - It took years for most municipalities to adopt
the current standards. How quickly will they
adopt the 2004 standard? - In many cases, the 2004 Standard design
ventilation rates are lower than 15 and 20 CFM
per person, which can be seen as decreasing the
standard of care in building design - How is a CO2 setpoint derived for a Dynamic
Reset control strategy?
88Zone Ventilation Control
Use DCV CO2 Setpoint Calculator
89Zone Ventilation Control
CO2 Setpoint Calculator determines optimum CO2
setpoint for all populations
Fixed Ventilation
DCV
90Zone Ventilation Control
- Ventilate to Actual vs. Assumed Occupancy
- Eliminate Wasteful Over-Ventilation
- Insure Adequate Ventilation
- Very Attractive ROI/Lower Operating Costs
91Benjamin Franklin on Ventilation (c. 1794)
- Who says history does not repeat itself?
- Like Ben, we have learned the error of our ways
(closing with extreme care every crack and
crevice). - IAQ and Sick Building Syndrome have "persuaded"
us on the "Virtues of Ventilation - "Zone Ventilation Control" an old idea whos
time has come!
92CO2-based Demand Controlled Ventilation (DCV)
Thank you! Ryan R. Hoger Commercial Controls
Mgr. Temperature Equipment Corp. 708.418.7901
ryan.hoger_at_tecmungo.com