Title: AFFF FIREFIGHTING SYSTEMS
1AFFF FIREFIGHTING SYSTEMS
2AFFF SYSTEMS
3AFFF FACTS
- CLEAR TO SLIGHTLY AMBER APPEARANCE
- INDEFINITE SHELF LIFE
- STORE AT TEMPERATURES gt320F (if AFFF freezes, it
may be used after thawing) - 94 WATER / 6 FOAM MIX
4AFFF FACTS
- MIXES WITH WATER TO FORM AN AQUEOUS FILM WHICH
EXCLUDES OXYGEN FROM THE SURFACE OF THE FUEL - COOLS DUE TO WATER CONTENT
- EXCELLENT PENETRATING CHARACTERISTICS / SUPERIOR
TO WATER ON CLASS A FIRES
5AFFF FACTS
- GENERAL PRECAUTIONS
- AFFF IS EXTREMELY CORROSIVE
- ENSURE SYSTEM IS PROPERLY ALIGNED FOLLOWING EACH
USE - AVOID INADVERTENT CONTACT WITH ELECTRICAL
EQUIPMENT - WHEN SYSTEM MAINTENANCE IS BEING PERFORMED ENSURE
YOU ARE KEPT ABREAST OF FIRE FIGHTING CAPABILITY
6AFFF FACTS
- GENERAL PRECAUTIONS
- SOME FORMATION/COLLECTION OF H2S MAY OCCUR IN
PIPING/AREAS WHERE AFFF STANDS STAGNANT FOR A
PERIOD OF TIME, PARTICULARLY IN THE BALANCED
PROPORTIONING SYSTEM
7AFFF SYSTEM COMMON ITEMS
- OVERBOARD DISCHARGE REQUIREMENTS
- lt3 NM FROM LAND - NO OVERBOARD DISCHARGE
- 3 - 12 NM FROM LAND - DISCHARGE PERMITTED IF
SHIP SPEED IS 10 KTS OR HIGHER - gt12 NM FROM LAND - DISCHARGE AS REQUIRED
8AFFF SYSTEM COMMON ITEMS
- DC DECK RE-ENTRY HOSE REELS
- 125 NON COLLAPSIBLE RUBBER HOSE WITH 11/2 INCH
95 GPM VARI NOZZLE (100 ON MHC) - HOSE REEL CUTOUT VALVE NORMALLY CLOSED
9AFFF SYSTEM COMMON ITEMS
- ENGINEERING SPACE HOSE REELS
- 50 NON COLLAPSIBLE RUBBER HOSE WITH 11/2 INCH 95
GPM VARI NOZZLE - HOSE REEL CUTOUT VALVE LOCKED OPEN.
10AFFF SYSTEM COMMON ITEMS
- ENGINEERING SPACE HOSE REELS
- 27 LB PORTABLE PKP CYLINDER LOCATED NEAR EACH
AFFF HOSE REEL
11AFFF SYSTEM COMMON ITEMS
- SERVICE VALVE TEST CASTING
- ALLOWS FOR TESTING OF BILGE SPRINKLING SYSTEM
WITHOUT SPRINKLING THE BILGES - AFFF CONCENTRATE TANKS
- MANUFACTURED FROM 9010 CUNI OR STAINLESS
- VENT/VACUUM BREAKER .05PSIG/.05Hg
12BILGE SPRINKLING SERVICE VALVE
TEST FITTING
INLET
INLET
SERVICE VALVE TEST CAST FITTING
CHAIN
TEST CONNECTION
CAP
13AFFF SYSTEM COMMON ITEMS
- PLANNED MAINTENANCE
- DAILY INSPECTION OF VALVE ALIGNMENT AND FLUID
LEVELS - MONTHLY PUMP MAINTENANCE CHECKS
- SEMI ANNUAL CHECK FOR SEAWATER CONTAMINATION
14AFFF SYSTEM COMMON ITEMS
- PLANNED MAINTENANCE
- SEMI ANNUAL SYSTEM OPERATION CHECK FROM ALL
REMOTE LOCATIONS - ANNUAL FOAM ANALYSIS
- NUMEROUS SITUATIONAL REQUIREMENTS
15FIXED EDUCTOR SYSTEM
- HIGH POINTS
- FOUND ON MHC / MCM
- MCM
- FORWARD TANK CAPACITY 50 GL
- AFT TANK CAPACITY 200 GL
- MHC
- TANK CAPACITIES 75 GL FWD / AFT
16FIXED EDUCTOR SYSTEM
- TANKS ARE REFILLED VIA GRAVITY FROM STORAGE TANK
LOCATED NEAR STACKS - PMS CHECK FOR AFFF CONCENTRATE SEAWATER
CONTAMINATION IS DONE QUARTERLY - OVERHEAD SPRINKLERS INSTALLED IN MHC CLASS SHIPS
17BPPS AFFF System
18AFFF FILL CONN
LOW FLOW RATE DEMAND (WEAPON, ELEVATORS, PUMP
ROOMS)
POWERTROL W/ TEST CASTING
OPTIONAL AFFF FILL CONN
HIGH FLOW RATE DEMAND (HANGAR SPRINKLER SYSTEM)
TO HOSE STATION OUTLETS
VENT
MANUALLY OPERATED BUTTERFLY VALVE
AFFF CONCENTRATE STORAGE TANK
BUTTERFLY VALVE
2 SPEED INJECTION SYSTEM
RECIRC CUTOUT
POWERCHECK
SUCTION LINE
DRAIN
CUTOUT
SEAWATER HUDRAULIC CONTROL LINES
SOPV
AFFF CONCENTRATE TWO SPEED AFFF PUMP
SEAWATER HYDRAULIC CONTROL LINE
SOPV
CONCENTRATE PRESSURE GAGE
SOPV
SOPV
HYCHECK
FIREMAIN
STRAINER BLOWDOWN
192 SPEED INJECTION SYSTEM
- HIGH POINTS
- PUMPS RATED AT 27/65 GPM _at_175 PSI
- 27 GPM - LOW FLOW RATE DEMAND USER (HOSE LINE,
ELEVATOR SRINKLER, etc) - 65 GPM - HIGH FLOW RATE DEMAND USER (HANGAR
SPRINKLER, etc) - POSITIVE DISPLACEMENT ROTARY VANE TYPE PUMP
- MOTOR CONTROLLER POWERED FROM ABT
- START LOCAL/ REMOTE. MUST BE STOPPED LOCALLY
20Single Speed Injection AFFF System
MAIN DECK
600 GALLON AFFF CONCENTRATE TANK
21DECK EDGE NOZZLES
FLUSH DECK NOZZLES
PRESSURE SWITCHES
POWERTROL TYPE VALVE
FIREMAIN
03 DECK
SOPV
CHECK VALVE
SINGLE SPEED AFFF SYSTEM
MAIN DECK
TO TRANSFER SYSTEM
ALTITUDE GAGE
VENT
PUMP DISCHARGE GAGE
600 GALLON AFFF TANK
AFFF PUMP
2ND DECK
HYDRAULIC CHECK VALVE
22SINGLE SPEED AFFF SYSTEM
- HIGH POINTS
- SERVICES HANGAR AND FLIGHT DECK AREAS, PUMP ROOMS
- FLUSH DECK NOZZLES
- DECK EDGE NOZZLES
- ELECTRIC PUSHBUTTON AT EACH HOSE OUTLET
23HIGH CAPACITY AFFF SYSTEM
- HIGH POINTS
- TYPES INSTALLED IN NAVY SHIPS
- BALANCED PRESSURE PROPORTIONER
- ELECTRIC 2 SPEED AFFF PUMP SYSTEM
- HIGH CAPACITY SINGLE SPEED PUMP
24SUMMARY
- FOAM GENERATING SYSTEMS
- 2 SPEED INJECTION SYSTEM
- HIGH CAPACITY SYSTEMS
25REVIEW QUESTION
- WHAT RULES APPLY WITH RESPECT TO THE DISCHARGE OF
AFFF INTO THE SEA WHEN - INPORT / 3NM FROM LAND?
- PROHIBITED
- 3 -12 NM FROM LAND?
- IF SHIP SPEED IS gt 10 KTS
- gt12 NM FROM LAND?
- DISCHARGE AT WILL
26REVIEW QUESTION
- DESCRIBE THE ACTIVATION SEQUENCE IN A 2 SPEED
INJECTION SYSTEM WHEN THE LOW FLOW RATE DEMAND
CIRCUIT IS ENERGIZED. - THE MASTER SOPV IS ENERGIZED, STARTING THE AFFF
CONCENTRATE PUMP ON SLOW AND OPENING THE HYCHECK
AND POWERCHECK VALVES AS WELL AS ENERGIZING THE
SOPV FOR THE LOW FLOW RATE GROUP (MINUS HOSE
REELS)
27REVIEW QUESTION
- WHAT ARE SOME OF THE DIFFERENT TYPES OF HIGH
CAPACITY AFFF STATIONS? - BALANCED PRESSURE PROPORTIONER
- 2 SPEED INJECTION SYSTEM
- SINGLE SPEED INJECTION SYSTEM
28INSTALLED FIREFIGHTING SYSTEMS