Title: EUGENE SILBERSTEIN
113 SEER BEYOND...
-
- EUGENE SILBERSTEIN
- Suffolk County Community
College -
- JOHN
TOMCZYK - Ferris
State University - HVAC EXCELLENCE INSTRUCTOR CONFERENCE
- Imperial Palace, Las Vegas, Nevada
- MARCH 16-19, 2008
2EER vs SEER
3EER
-
- Measure of system cooling efficiency with a
constant outdoor temp. (Usually 95F) - Ratio of the average rate of space cooling to
the average rate of electrical energy consumed - Expressed in Btuh/Watt
- Commonly used when referring to window a/c units
and heat pumps, as well as water - source and geothermal heat pumps
4SEER
- How efficiently a residential central cooling
system operates over an entire cooling season - The total heat removed from the conditioned space
during the entire cooling season, expressed in
btus, divided by the total electrical energy
consumed in watt-hours - Expressed in Btu/Watt-hour
- 13 SEER requirement as of January 23, 2006
5SEER EXAMPLE
- 24,000 btu/hr air conditioning system
- Energy cost 0.20/kWh
- 10 SEER system
- Solution
- 24,000 btu/hr 10 btu/watt-hour 2,400 W
- 2,400 Watts 2.4kW
- 2.4 kW x 0.20 48 per hour
6SEER EXAMPLE
- 24,000 btu/hr air conditioning system
- Energy cost 0.20/kWh
- 13 SEER system
- Solution
- 24,000 btu/hr 13 btu/watt-hour 1,846.2 W
- 1,846.2 Watts 1.846 kW
- 1.846 kW x 0.20 36.5 per hour
7THE SAVINGS
- Cost per hour (10 SEER system) 48/hour
- Cost per hour (13 SEER system) 36.5/hour
- Cost savings per hour
- (48/hour - 36.5/hour) 48/hour 11.5/hour
- 11.5/hour 115 over the cooling season
813 SEER REQUIREMENTS
- Apply to residential equipment in the 1.5 to 5
ton range (Split/Packaged A/C Heat Pump
systems) - Do not apply to
- Commercial Equipment
- Space Constrained Units
- Water Source
9THE GREAT DEBATE
- How accurate are SEER ratings?
- Are all systems tested the same?
- How do the tests mimic actual system operation?
- When were the original SEER tests implemented?
- Are the SEER tests performed in third party
testing facilities? - Will a customers system actually deliver the
advertised SEER?
10SEER FACTORS
- Length of refrigerant lines
- Refrigerant charge
- Duct system
- Ambient conditions
- Constant evaporator airflow? Nope!
- Seasonal weather data
- Poor dehumidification? No problem!
11Where will a system operate with the highest
efficiency?
- Binghamton, New York
- Yuma, Arizona
- Crescent City, California
82F 109F 65F
12Standard Rating Conditions
13SEER FORMULA
EERC
1
EERD
1 0.5
EERB
QD
1
QC ?
14SEER COMPONENTS
- QD Total cooling over one complete compressor
on and off cycle, (Btus) - QC Total steady-state cooling capacity from
Test C, (Btuh) - ? Time duration for one complete compressor
on and off cycle, (hours) - CLF Cooling Load Factor
- CLF (QD QC ?)
15SEER FORMULA
EERC
1
EERD
1 0.5
EERB
1
CLF
16SEER COMPONENTS
- EERD EER from test D
- EERC EER from test C
- CD Degredation Coefficient
- CD 1 ( EERC / EERD ) / 1 CLF
17SEER FORMULA
1 0.5 (CD)
EERB
The part-load performance factor PLF (at 0.5
cooling load) is identified as
1 0.5 (CD)
So
18SEER FORMULA
SEER PLF (0.5)
EERB
19SEER, EER and COP
- SEER, EER and COP are all inter-related
- SEER can be estimated using the pressure-enthalpy
chart, by first calculating the COP of the system - COP is equal to the systems net refrigeration
effect divided by the heat of compression of the
system - Lets take a look
20SYSTEM COP
40
112 130
21SYSTEM COP
- NRE 72 btu/lb
- HOC 18 btu/lb
- COP NRE HOC
- COP 72 btu/lb 18 btu/lb
- COP 4
- Notice that the COP is UNITLESS
22EER and SEER
- From our example, COP 4
- EER COP x 3.413 13.65 btuh/watt
- Parameters of SEER can be estimated to be between
1.1 EER and 1.3 EER - Low end ? 1.1 x 13.65 15
- High end ? 1.3 x 13.65 17.7
- For our example, the SEER rating can be between
15 and 17.7 btu/watt-hour
2313 SEER TransitionImpact on Consumer Demand
- Distribution/Dealers
- Shipping/Logistics
- Warehouse/Storage/Handling
- Cost/price
- Refrigerant Charge
- Coil Matching
- Consumer Comfort
- Training/New Technology
- Obsolescence
13 SEER
40 Size Increase
10 SEER
- Manufacturers
- Cost/Price
- Investment
- Engineering Resources
- Mfg. Equipment Lead Time
- Training/New Technology
- Obsolescence
- Shipping/Logistics
- Warehouse/Storage/Handling
24RELATIVE SIZE COMPARISON
25Consumer Benefits of 13 SEER Systems
- Improved comfort
- Variable Speed Blowers
- Modulating Compressors
- Improved Reliability
- Internal diagnostics
- Communications
- Noise Levels
- Reduced Bower Noise
- Reduced Compressor Noise
2613 SEER Summary
- Consumers Were Originally Unaware Of Change
- Significant Increase In Costs
- Repair Vs. Replace
- Payback Period
- Significant Increase In Size
- Logistics/Handling/Warehouse Space
- New Skills/Added Training Required
- Follow Manufacturers Recommendations
- Deliver 13 SEER
- Maintain Reliability
27NEW COIL TECHNOLOGY
28MICROCHANNELTechnology
29(No Transcript)
30MICROCHANNEL TECHNOLOGY
- Meeting Efficiency Standards
- Size / Weight Reduction Goals
- Corrosion Resistance Enhancement
-
31Lessons Learned
-
- Standard in the Automotive Industry
- HVAC Industry Concerns Identified
- - Aluminum to Copper Transition
- - Corrosion Capabilities
- - Dust Clogging
- - Field Repair
- - Cleaning
- Economics Needed to be Addressed
32PARALLEL FLOW (PF) HISTORY
- Introduced to Automotive market in 1986
- Addressed the market requirement to reduce size
(front end design) and weight (fuel efficiency)
of heat exchanger - Industry change to R-134a required a more
effective heat exchanger - Automotive volumes drove manufacturing
processes (high tooling dollars per model) - Modine developed PF (Parallel Flow)
technology in 1980s - Standard in Automotive Truck markets today
33Product Advantages Easily Formed
Folded V
Bent
Increased Design Flexibility
34Product AdvantagesIncreased Heat Exchanger
Effectiveness
EER
TONS
LATENT HEAT TRANSFER
35Product AdvantagesReduced Heat Exchanger Size
and Weight
Cost
Fan
Shipping Cost
System Cost Savings
36Product AdvantagesReduced Heat Exchanger Size
and Weight
Fan Noise
Customer Product Advantage
Improved System Performance
37R-410A Drop-In Performance Comparison
- RTPF Coil
- louvered fin, 24 fpi
- rifled 3/8 tube
- Face Area 73 x 30
- 30 tubes high
- 1 row deep (0.728)
- PF Coil
- louvered fin, 23 fpi
- microchannel tube
- Face Area 70 x 29
- 74 tubes high
- 1 row deep, 3-pass
- fin height 0.312
38- TXVs
- Thermostatic Expansion Valves
39Purpose of A TXV
- The TXV has a one- line job description
- TO MAINTAIN CONSTANT EVAPORATOR SUPERHEAT!
- The TXV Does Not
- Control Air Temperature
- Maintain Head Pressure
- Maintain System Capacity
- Maintain Constant Suction Pressure
- Control or Maintain Humidity
- Clean the House and Cook Dinner
40Increased TXV Usage On Residential HVAC Equipment
- Many Manufacturers Using TXVs to Meet 13 SEER
Requirements - Constant Superheat Throughout Operating Range
- Less Cycling Losses Improved Cd
- Estimated SEER increase 0.5 SEER points
- Most Cost Effective SEER Improvement Technology
- Significant Increase in TXV Demand
- Manufacturing increases
- Increased Interest and Need For More Training On
TXV Operation and Troubleshooting
41TXV OPERATING PRESSURES
- Bulb Pressure Opening pressure
- Spring Pressure Closing pressure
- Evaporator Pressure
- Closing pressure
- Can come from the inlet or the outlet of the
evaporator - Bulb Press Spring Press Evaporator Press
- Valve seeks to be in equilibrium
42Force Balance Diagram
P1
BULB
F
EVAPORATOR
For Valve To Be In Balance
SPRING
43Superheat Is A Temperature Difference... Not Just
A Temperature
10F Superheat
10F Superheat
Both Evaporators are operating with the same
superheat
44Superheat Measurement
45Low Superheat
Latent Heat Transfer
Last Point of Liquid Refrigerant
Sensible Heat Transfer
46Low Superheat can cause Crankcase Foaming from
Flooding
47 VAPOR
LIQUID
48High Superheat
Last Point of Liquid Refrigerant
Inefficient
49The Best Time To Take A Superheat Reading
- Steady State Condition
- Prior to Unit Cycling off on Temperature or
Pressure - Prior to a Scheduled Defrost
50Normal Superheat Settings For Thermo Expansion
Valves
- High Temp 10 to 12 F (gt30F Evap. )
- Med. Temp 5 to10 F (0 to 30F Evap.)
- Low Temp 2 to 5 F ( Below 0F Evap.)
Follow System Manufacturers Recommended Superheat
51INTERNAL BLEED VALVE
- A bleed port is an internal passage directly
between the inlet and outlet of the TXV - Provides for System Equalization During the off
Cycle for Low Starting Torque Compressors
52(No Transcript)
53(No Transcript)
54TXV with Internal Check
Check Ball
Eliminates The Need For A Separately Installed
Check Valve For Reverse Cycle Operation
55INTERNALLY VS EXTERNALLY EQUALIZED TXVs
56INTERNALLY EQUALIZED TXV
- Gets its evaporator pressure from the inlet of
the evaporator coil - Valve has an inlet port and an outlet port
- Used on evaporators that have a small pressure
drop between the coils inlet and outlet
57EXTERNALLY EQUALIZED TXV
- Gets its evaporator pressure from the outlet of
the evaporator coil - Has three ports
- Inlet port
- Outlet port
- Equalizer line port
- Used on evaporators that have large pressure
drops between the inlet and outlet of the coil - Has nothing to do with equalizing pressures
58Internally/ExternallyEqualized TXVs
External Equalizer
59If we use an internally equalized TXV with a
spring pressure of 15.5 psig...
55 psig 30ºF
62.5 psig 36ºF
Bulb Pressure 84 psig (68.5 psig 15.5 psig)
Evaporator Outlet Temperature 50ºF
Evaporator Superheat 50ºF - 26ºF 24ºF
R-22
60If we use an externally equalized TXV with a
spring pressure of 15.5 psig...
55 psig 30ºF
62.5 psig 36ºF
Bulb Pressure 65.5 psig (50 psig 15.5 psig)
Evaporator Outlet Temperature 38ºF
Evaporator Superheat 38ºF - 26ºF 12ºF
R-22
61Probably the three most commonly asked questions
regarding internally and externally equalized
TXVs
62If a system is equipped with an externally
equalized TXV, can you replace the valve with an
internally equalized valve?
63If a system is equipped with an internally
equalized TXV, can you replace the valve with an
externally equalized valve?
64If a system is equipped with an internally
equalized TXV, can you replace the valve with an
externally equalized valve if I simply put a cap
on the external equalizer port?
65TXV
EXTERNAL EQUALIZER CONNECTION
66Internal Or Externally Equalized TXV?
Externally Equalizer is Required When
Pressure Drop in The Evaporator Exceeds -
3 PSIG - Air Conditioning - 2 PSIG -
Commercial - 1 PSIG - Low Temperature
67Expansion Valve Selection
- Refrigeration Type
- Evaporator Temperature
- Evaporator Capacity
- Condensing Temperature/Pressure
- Liquid Temperature
- Distributor Type (if used)
Note The valve is sized to the evaporator and
not the compressor.
68SCROLL COMPRESSORS
69SCROLLS
70(No Transcript)
71(No Transcript)
72CONTINUOUS SMOOTH COMPRESSION WITH LESS MOVING
PARTS.
73LIQUID TOLERANT
74Next Generation Copeland Scroll
Improved Temperature Protection
- New Design Benefits
- 2-6 Efficiency
- Enhanced Reliability
- 2-4 dBA Quieter
Pressure Protection
New Quiet Shutdown Solution
Optimized Scroll/Seal For Higher Efficiency
Larger Shaft Bearing System For Enhanced
Reliability
Common Shell/Tubing Configuration
High Efficiency Motor
KFZblc/2006/Hardi 5.06.ppt 4/26/2006 74
75Copeland Scroll UltraTechProduct Design
Modulation Ring/Bypass Seals
Solenoid Return Spring
Solenoid Actuator Coil
76Copeland Scroll UltraTechContractor Field Test
Results
Reduces Humidity 8 While Improving Humidity
Control 50
77Copeland Scroll UltraTech Featuring Two-Stage
Capacity
- Superior Efficiency (16 SEER)
- Better Comfort
- (67 Part Load Capacity)
- Quieter Operation
- (Sound And Vibration)
- Simpler Design
- Inherent Scroll Design
- No shutdown to change capacity
- Less Applied Components
- Proven Copeland Scroll Reliability
78Comfort Alert Diagnostics
- Technology Using Scroll as a Sensor
- Significant Customer Need For 13 SEER
Differentiation - Lower No Defect Found Field
Failure Rates - High Contractor Interest
79COMFORT ALERT DIAGNOSTIC MODULE
- Installed in the outdoor unit
- Diagnoses a variety of system problems
- Compressor acts as a sensor monitoring and
analyzing system performance data - Relays the information
- Quickens and Improves diagnostic accuracy
- Guides service technicians to the root of the
problem quickly.
80Future Capability to Send Signal to Thermostat
and Download Fault History to PC/Palm Device
Green POWER LED
Pass Through Ports Spade Connectors Detect
Tstat Demand and Pilot Voltage
Yellow ALERT LED Red TRIP LED
Diagnostics Key
81System And Electrical Alert Codes
- Long Run Time (Code 1)
- System Pressure Trip (Code 2)
- Short Cycling (Code 3)
- Locked Rotor (Code 4)
- Open Circuit (Code 5)
- Open Start Circuit (Code 6)
- Open Run Circuit (Code 7)
- Welded Contactor (Code 8)
- Low Voltage (Code 9)
82Comfort Alert Fault Codes And Causes
83Resetting Alert Codes
- Automatic Reset
- Code 1 - 30 Alert Free On And Off Cycles
- Code 2 ? 4 - 4 Alert Free On And Off Cycles
- Codes 5 ? 8 - Occur And Reset Immediately
- Code 9 - Resets When Voltage Rises Above 19VAC
- Manual Reset
- All Alert Codes Can Be Reset By Cycling 24VAC
Power
84ROLLING PISTON AND SLIDE VANE
85ROLLING PISTON ROTARY COMPRESSOR
86(No Transcript)
87SLIDING VANE ROTARY COMPRESSOR
88REFRIGERANT CHARGING
- Proper refrigerant charge helps ensure system
efficiency - Systems can cool a space with an undercharge or
an overcharge - Use superheat method for cap tube or fixed bore
metering devices - Use subcooling method for TXV systems
89ECM MOTORS
90A/C SYSTEM EFFICIENCY WITH ECM MOTORS
- With low system load, compressor speed can be
reduced - The indoor and outdoor fan speeds must be reduced
in proportion to the load on them - By reducing the indoor fan speed, the humidity in
the conditioned space can be controlled because
suction pressure is maintained. - By reducing the condenser fan speed, the head
pressure will be maintained.
91ECM MOTORS
- Ultra-high efficiency, programmable, brushless,
DC motors. - They operate with high voltage, single-phase
inputs. - They have a permanent magnet rotor.
- Have a built-in AC to DC inverter to produce the
DC that actually operates the motor.
92ECM MOTORS
- Single-phase alternating current is supplied
- AC power is converted to DC
- The DC power is then passed through a transistor
bank - An artificial three-phase power source is
generated to power the motor
93(No Transcript)
94(No Transcript)
95Q1 Q2
Q3
Q4 Q5
Q6
960 30 60 90 120 150 180
210 240 270 300 330 360
Q1
Q2
Q3
Q4
Q5
Q6
970 30 60 90 120 150 180
210 240 270 300 330 360
Q1/Q4
Q2/Q5
Q2/Q5
Q3/Q6
Q3/Q6
98ECM MOTORS
- More efficient than PSC motors
- Have a wider temperature operating range
- Have a Soft Starting Feature for lower inrush
current - Start at a low RPM and gradually ramp up to
design speed - Reduced amperage spikes
- Soft Starting places less stress on the motor,
fan, and other mechanical parts - Preset for a specific CFM requirement.
99ECM MOTORS
- DC motors have a rotating magnetic field in the
stator to create a rotating force in the
permanent magnet armature. - The speed of the magnetic field is controlled by
an electronic motor controller. - Electronic motor controllers can provide constant
CFM, constant RPM, or variable CFM.
100ECM VARIABLE SPEED MOTOR ADVANTAGES
- Power savings
- Load reduction based on demand
- Soft starting (No LRA)
- Better space temperature and humidity control
- Solid state motor starters (Controllers)
- Load and capacity matching
- Run at part load for future expansion
101ECM MOTORS
- Can be a constant airflow (CFM) motor by
regulating torque and speed over a wide range of
static pressures - Provides variable speed motors for gas furnaces,
A/C systems, heat pumps, commercial
refrigeration, and oil burner systems. Are also
used on compressor motors - ECM consists of a motor section and a control
section. Each can be replaced separately. - ECM motors use permanently lubricated ball
bearings
102ECMs CONSTANT CFM QUALITIES WITH STATIC
PRESSURE CHANGES
103CONSTANT AIR FLOW (CFM)
- Compensates for poor duct design
- Compensates for inadequate duct volume
- Compensates for abnormally high static pressure
- - Use of flex duct
- - Loaded air filter
- - Zone changes
- - Obstructed supply register
104ECM VARIABLE SPEED MOTOR ADVANTAGES
- Power savings
- Load reduction based on demand
- Soft starting (No LRA)
- Better space temperature and humidity control
- Solid state motor starters (Controllers)
- Load and capacity matching
- Run at part load for future expansion
105INFORMATION SOURCES
- WWW.EMERSONCLIMATECONTRACTOR.COM
- WWW.EMERSONCLIMATE.COM
- WWW.ARI.ORG/STANDARD/210-240-2006.HTM
- WWW.COPELAND-SCROLL.COM
- WWW.APPLIANCEDESIGN.COM (April, 2006)
- WWW.MODINE.COM
106finis
JOHN TOMCZYK tomczykj_at_tucker-usa.com
EUGENE SILBERSTEIN silbere_at_sunysuffolk.edu (631)
851-6897
107Comfort AlertProduct Overview
- Nearly 40 Of Compressor Warranty Returns
Classified As No Defect Found - Field Technicians Are Not Accurately
Troubleshooting System Problems - Comfort Alert Key Benefits
- Improves Service Technician Diagnostic Accuracy
And Speed Of Service - Delivers Homeowner Peace Of Mind And Improved
Reliability - Helps Differentiate Mainline Vs. Entry Equipment
- Comfort Alert Product Description
- Diagnostics For Systems With Copeland Scroll
Compressors - Detects System And Electrical Problem Conditions
Using Scroll Compressors As Sensor (No Added
Sensors Needed) - Compatible With A/C, Heat Pump And UltraTech
Modulated Systems - Can Communicate Check System To Thermostat
108Comfort AlertDiagnostic Alert Codes
109Comfort Alert Wiring Schematic
- Provides 4 Inputs To Diagnose Faults (Run
Circuit, Start Circuit, Common Circuit,
Thermostat Demand Y) - Algorithms Determine The Patterns And Timing Of
Symptoms To Diagnose Faults
110Copeland Scroll Motor Protector Is The Key
- Protector Is Embedded In Motor Windings
- Located In Hot Spot Of Motor
- Reacts To A Temperature Set Point
- High Current Results In High Temperature
- Lack Of Cooling Results In High Temperature
- Protectors are sized Specifically For Each
Motor-Compressor Combination
111Sensing Motor Protector Trips
- Comfort Alert Detects A Motor Trip When
- Thermostat Demand Y Is On
- No Current Is Measured To Compressor
- Interpretation Compressor Isnt Running When
System Wants It To Run - Root Causes
- Motor Protector Open
- Power Disconnected (Fuse, Switch, Etc.)
- Comfort Alert Not Wired Properly
- Pattern Of Trips Leads To Alert Codes
112Sensing Long Run Time (Code 1)
- Comfort Alert Detects A Code 1 When
- Thermostat Demand Y Is On And Current Is
Detected 18 Hours Continuously - No Protector Trips Are Detected For Code 1
- Interpretation Compressor Cannot Meet Cooling
Demand Evaporator Iced Up - Root Causes
- Low Refrigerant Charge
- Evaporator Blower Failure
- Liquid Line Restriction
- Thermostat Set Extremely Low
113Sensing System Pressure Trip (Code 2)
- Comfort Alert Detects A Code 2 When
- Four Consecutive Protector Trips Occur
- The Average Run Until Trip Time Is Between 1
Minute And 15 Minutes - Interpretation High Pressure Condition Causes
Compressor To Run Briefly Before Tripping - Root Causes
- Blocked Condenser Coils
- Condenser Fan Not Running
- If LPCO In System, Low Pressure Condition
114Sensing Short Cycling (Code 3)
- Comfort Alert Detects A Code 3 When
- A Pattern Of Short Cycles Emerges
- The Run Time For The Past 4 Runs Is Less Than 3
Minutes Each - No Protector Trips Are Detected For Code 3
- Interpretation Compressor Is Running Only Short
Periods Of Time - Root Causes
- Safety Cutout Switch Interrupting Y
- Faulty Thermostat
- Intermittent Contactor
- If HPCO In System, High Pressure Condition
115Comfort Alert Memory
- Comfort Alert Displays Last Alarm At Each Power
Up - Displays Code If Alarm Occurred During Last Power
Cycle - Display Lasts For One Minute
- Alarm History Is Kept In Memory
- Seven Day History Of Alarms
- Overall Count Of Alarms Since Factory Testing
116 SUPERHEAT
- ANY SENSIBLE HEAT GAINED AFTER THE 100 SATURATED
VAPOR POINT IN THE EVAPORATOR. - THE 100 SATURATED VAPOR POINTS TEMPERATURE WILL
BE AT THE EVAPORATORS TEMPERATURE WHICH
CORRESPONDING TO THE EVAPORATING PRESSURE.
117R-22
118SUBCOOLING
- ANY SENSIBLE HEAT LOST AFTER THE 100 SATURATED
LIQUID POINT IN THE CONDENSER. - THE 100 SATURATED LIQUID POINTS TEMPERATURE IN
THE CONDENSER WILL BE AT THE CONDENSING
TEMPERATURE WHICH CORRESPONDS TO THE CONDENSING
PRESSURE.
119R-410A SUBCOOLING METHOD CHARGING PROCEDURE
120(No Transcript)
121Electronically Commutated Motors (ECM)