Title: Via Christi Regional Medical Center Wichita, KS
1Via Christi Regional Medical CenterWichita, KS
Electricity Reduction
- Lindy Pope
- September 14, 2007
2Presentation Overview
- Via Christi Overview
- Energy Consumption Audit
- Light Audit
- Delamping and Timers
- New Lamp Purchases
- Occupancy Sensors
- Dimming Controls
- Air Audit
- Employee Awareness
- Energy Star Products
- Monitor Power Management
- Energy Awareness Program
- Total Savings
- Questions
3Via Christi Overview
Via Christi Regional Medical Center is a
non-profit Catholic health organization based in
Wichita, Kansas.
I worked at their St. Francis campus. St.
Francis is a 1,450,000 square feet Level-1 Trauma
Center.
4 Energy Consumption Audit
12 months of energy data was collected for St.
Francis, St. Joseph, Our Lady of Lourdes, Good
Shepherd, and 30 other locations owned by Via
Christi. The 4 main buildings were placed into
Energy Stars Portfolio Manager to get a
benchmark reading.
5 Energy Consumption Audit
- St. Francis meters were broken down into the
location they served, what events happen in those
locations, and per square foot. - All this information was collected to allow the
hospital to focus their energy conservation on
the locations where they use the most energy. - An example of the final spreadsheet can be seen
below. -
6Light Audit
- Overall higher lighting levels than needed.
- Recommendations
- ¼ Delamping- 25 locations
- In locations that are over lit constantly
and/or low traffic hallways - Turn off certain lights during the day- 21
locations - Achieve through timers or connecting the
lighting to a Building Automation System - 21 timers are needed a purchase price of 630
- Benefits
- 5,793.27 and 125,068 kWh savings in electricity
per year - Removal of 336 lamps
7New Lamp Purchases
- A list of the current lamp purchases for St.
Francis and St. Joseph was reviewed to determine
if there are better options. - 11 lamp types were identified that should be
changed. - The new lamps reduce electricity, lamp disposal,
mercury, and/or maintenance costs - T-8 38,350 to 45,950 T- 8s in the 4 main
buildings -
- Savings
- 81,920 to 97,302 in electricity per year
- 1,638,387 to 1,946,005 kWh per year
- 69,030 to 82,710 mg of mercury
-
8Occupancy Sensors
- Location Average Savings Amount Annual Savings
(per room) - Private Offices 35 600 7.59 - 12.56
- Classrooms 40 35 18.40 - 49.06
- Conference Rooms 47 62 10.29 -
20.58 - Restrooms 54 121 35.50 - 59.13
- Storage Areas 60 264 7.88 - 15.77
- Lounge/Kitchen 35 90 13.80 - 27.60
- Waiting Room 30 50 26.28 - 52.56
- Exam Room 50 121 6.57 - 13.14
- Total Savings
- 15,497 to 28,591 in electricity per year
- 310,119 to 571,747 kWh per year
-
9Dimming Controls
- Dimming controls offer occupants more control
over their environment. - They can be used in patient rooms, offices, and
exam rooms. - Occupancy sensors save more in offices then
dimmers do. - Dimming controls, in exam rooms, have no
research on potential savings. - Patient rooms
- Implement dimmers during renovations or new
construction. - There are 730 patient rooms.
- The chart below shows the estimated savings per
year if dimmers were placed in patient rooms. -
10Air Audit
Equipment used UE Systems 9000 Ultrasonic Leak
Detector Compressed Air 20 leaks for a total
loss of 74.8 CFM Total loss of 7,862.98 and
157,260 kWh per year Medical Air 11 leaks for a
total loss of 22.9 CFM Total loss of 3,009.06
60,181 kWh per year Steam 5 leaks for a total
loss of 35.12 lb/hr Total loss of 3,999 and
331 Mbtu per year Total 14,871, 217,441 kWh,
and 331 Mbtu per
year
11Energy Star Products
- Product Savings (1 unit per year) Total
Savings (per Year) - CRT/LCD Monitor 8 10,500
- TV 3 2,190
- Vending Machine 140 10,500
- Computer 6 3,600
- LED Exit Signs 12 6,000
- Other products
- Copiers, printers, refrigerators, DVDs, fax,
and food service equipment - Total Savings
- 27,090 per year
- 500,000 kWh per year
12 Monitor Power Management
- This free software from Energy Star puts all
monitors on the network into sleep mode after a
pre-determined time. - Estimated savings per monitor 10-20
- Total Savings (based on 1,500 monitors)
- 15,000 to 30,000 per year
- 300,000 to 600,000 kWh per year
- Cisco Systems Success Story
- 20,000 monitors
- Total savings of 528,000 or 26 per monitor
per year - Only 16 hours of IT time to implement
-
13Energy Awareness Program
- Newsletter Ad
- Makes sure employees are an active part of
energy savings. - Fact Sheets
- Will remind people of energy conservation acts
and benefits. - Posters
- Constant reminder to turn off
- the lights and office equipment
at night. - Total Estimated Savings (from
- Energy Star)
- 30,000-76,000 per year
- 600,000-1,520,000 kWh per year
14Total Savings
15Total Savings
Total Savings in Energy per Year 197,347 to
291,298 3,825,306 to 5,704,078 kWh
16Questions?