Title: Intelligent Energy Management Made Simple


1
Intelligent Energy Management Made Simple
2
Cooling problems
  • Server manufacturers specify inlet air
    temperatures
  • Conventional controls dont measure it
  • Overcooling
  • Inefficiency
  • Hot spots

3
Cooling control is difficult
  • Open plan design
  • All cooling units affect all areas
  • Redundant cooling units
  • Can lead to fighting
  • Custom control software is expensive and
    unreliable
  • Cant have a PhD commission every datacenter

4
What we do
lt 2yr ROI
Control
Analysis
Insight
5
How we do it
  • Measure inlet air temps
  • Supervisory control
  • Learning algorithms
  • Installed in days

Wireless Module
Temperature Probes
6
Recommended deployment strategy
  • Install controls first
  • Immediate automated energy savings
  • Excellent complement to IT-side best practices
  • Persistent Commissioning
  • Determine where and how to improve
  • Cost effective deployment of best practices

7
Case Study 1 Franchise Tax Board
  • The Data center
  • 10,000 SF
  • 12 CRAHs (22 tons each)
  • 40 built out
  • The solution
  • 50 wireless inlet server temperature sensors
  • 4 VFDs installed
  • Re-arranged tiles
  • Reset setpoints of CRAHs
  • Automatic start-stop of CRAHs

8
Case Study 1 Energy Savings
  • Software shut off 6-8 CRAH units
  • All temperatures within ASHRAE recommended range
  • 310,000 kWh/year saved
  • 245,000 kWh/year fan savings
  • 65,000 kWh/year chiller savings
  • 27,900/year saved (0.09/kWh)
  • 58 reduction in fan energy usage
  • 13.4 reduction of total datacenter energy usage

9
Case Study 2 Bay Area
  • The Data center
  • 5,000 SF
  • 6 CRAHs (22 tons each)
  • 130 racks
  • The solution
  • 48 inlet air temperature sensors
  • 6 VFDs with wireless controls
  • No other efficiency measures taken
  • One-day installation

10
Case Study 2 Energy Savings
  • 300,000 kWh/year saved
  • 218,000 kWh/year verified fan savings
  • 82,000 kWh/year estimated chiller savings
  • 27,000/year saved (0.09/kWh)
  • 80 reduction in fan energy usage
  • 17 reduction of total datacenter energy usage

11
Customer perspective
12
Summary
  • Excellent ROI from supervisory cooling control
  • Quick and non-intrusive installation
  • Enables cost-effective application of best
    practices
  • Excellent complement to IT-side best practices