Title: Hydraulic Optimization of the Northern Water Supply System
1Hydraulic Optimization of the Northern Water
Supply System
Presentation by Tom Charles, P.E., DEE Jim
Kriss, P.E. Jennifer Wendrowski,
E.I.T. September 2004
2ECCV H206 Water Supply Facility
WTP High Service PS
- Renewable Water Supply Source
- Alluvial Wells and Delivery Network
- Reverse Osmosis Treatment Plant
- 32 Mile Transmission Pipeline
- 2 Pump Stations
- Phase 2 Improvements (Future)
Booster PS
Smoky Hill Storage
3Alternative No. 1 Base Model
409 psi
10 MGD
- System Consists of
- RO WTP
- HSPS
- BPS-1 Tank
- Storage Tanks
- 32 miles of 24-inch pipe
- Problem high discharge pressure from HSPS
24 f
324 psi
4Alternative No.2 Inline Booster Model
143 psi
24 f
10 MGD
205 psi
- System Consists of
- RO WTP
- HSPS
- In-line BPS-2 Tank
- BPS-1 Tank
- Storage Tanks
- 7 miles of 24-inch pipe
- 25 miles of 30-inch pipe
13 MGD
30 f
274 psi
5Alternative No.3 Booster Injection Model
360 psi
24 f
10 MGD
- System Consists of
- RO WTP
- HSPS
- Injection BPS-2 Tank
- BPS-1 Tank
- Storage Tanks
- 7 miles of 24-inch pipe
- 25 miles of 30-inch pipe
213 psi
13 MGD
30 f
266 psi
6Alternative 1 - Pressure Trace for
Suction/Discharge (No Controls)
7Alternative 1 - HGL Envelope (No Controls)
Smoky Hill
BPS 1
HSPS
8Alternative 1 - Pressure Trace for
Suction/Discharge (With Controls)
9Alternative 1 - HGL Envelope (With Controls)
Smoky Hill
BPS 1
HSPS
10Alternative 2 - Pressure Trace for
Suction/Discharge (No Controls)
J-10
J-11
J-4
11Alternative 2 - HGL Envelope (No Controls)
Smoky Hill
BPS 1
BPS 2
HSPS
12Alternative 2 - Pressure Trace for
Suction/Discharge (With Controls)
13Alternative 2 - HGL Envelope (With Controls)
Smoky Hill
BPS 1
BPS 2
HSPS
14Pump Selection - VSD versus CSD
- Meet System Operating Requirements
- Match RO Membrane Skid Production
- Minimize Tank Fluctuations
- Minimize Pump Cycle Time
- Minimize Capital and Operating Costs
- Minimize Pump Room Footprint
152 Duty VFD Pumps, 1 Standby
BPS Pump Head/System Curve 30 inch North
Pipeline Floway 18 MKH (5 stg, 1770 rpm, 11.875
trim), 2 VFDs
165 Duty CSP Pumps, 1 Standby
BPS Pump Head/System Curve 30 inch North
Pipeline Floway 14 JKH (6 stg, 1770 rpm) 5 pumps
17Operating Cost Comparison
- VSP/ CSP Capital Costs Similar
- Justify VFD Capital Cost?
- Annual Billing Estimates
- Present Worth Analysis
- Pump Power Use for Flow Targets
- Monthly Demand Distribution
- System Operation
- Intermittent Winter Operation
- Max Capacity during Summer Peak
18Pump Power Requirements
19Operating Cost Comparison
- VSP/ CSP Capital Costs Similar
- Justify VFD Capital Cost?
- Annual Billing Estimates
- Present Worth Analysis
- Pump Power Use for Flow Targets
- Monthly Demand Distribution
- System Operation
- Intermittent Winter Operation
- Max Capacity during Summer Peak
20Variable Speed Billing Estimate
21Constant Speed Billing Estimate
22Questions Answers