Title: ventilation
1Ventilation Management in ECH
Dr. Rashid Sohail
2Ventilation
- Ventilation is
- Moving FRESH AIR INTO a house and moving STALE
AIR OUT of the house - Sending UNWANTED heat, EXCESS moisture, ammonia,
OUT of the house and - AIR MIXING to get heat, moisture, ammonia INTO
THE AIR that leaves the house.
3Objectives
- Provide a suitable environment to facilitates
- Maximum livability
- To take maximum growth rate
- To take better feed conversion
4WHAT IS STATIC PRESSURE
- Definition
- Static pressure is the difference between the
inside and outside atmospheric pressure - Units expressed in units of inches of water
colum (WC) and pascals - 1 w c 250 pascals
- When ext. fan runs, it creates negative pressure
in the house.Inside and outside pressure
difference (static pressure) rises and allows to
move the air into the house
5EXH.FAN VS STATIC PRESSURE
6 MANOMETER
MEASURING INSTRUMENT OF STATIC PRESSURE
7WHY IT IS NECESSARY
- To maintain the maximum level of freshness in a
house. - To remove stale air containing excess amount of
waste gases(ammonia,co2,co) - To maintain optimum level of Temperature and RH
according to the need of bird.
8COMPARISON (AIR PATTERN)
Insufficient static pressure.
Proper static pressure
Static pressure too high.
9STATIC PRESSURE VS TEMP. DIFFERENCE
10Air Quality
Oxygen(O2) more than 19.6
Carbon Dioxide(CO2)less than 0.3
Carbon Monoxide(CO) less than 10 PPM
Ammonia(NH3)less than 10 PPM
Dust less than 3.4 mg/m3
Relative humidity (RH) 45-65
11The bird!
12Where is the most heat coming from?
13BODY HEAT PRODUCTIONOF POULTRY
- A 2-kilogram (4.4 lbs.) bird with a daily weight
gain of 65 grams (14.3 lbs/100) takes in about
500 kcal daily.
- Of this, 130 kcal are used for growth, the
remaining 370 kcal must be excreted in one form
or another.
14Methods of heat loss
15 Ventilation goals
- Proper temperature
- Optimum humidity
- Adequate fresh air
- No noxious gases
16Types of ventilations
- Natural Ventilation
- Forced Ventilation
17Types of Forced Ventilation
- Minimum ventilation
- Transitional ventilation
- Tunnel ventilation
18Conti.
- Natural Ventilation
- Only Minimum ventilation is available but
no mechanical vent. - Minimum Ventilation
- Low air velocity but long air exchange
during brooding and cold weather. - Transition Ventilation
- Low air velocity, better air exchange
rate. - Summer Ventilation
- Temperature control, high air speed to
reduce effective temperature.
19VENTILATION PARAMETERS
- Tunnel fans capacity.
- Cooling pads.
- Minimum ventilation fans.
- Air inlets.
- Climate controller.
- Insulation.
20Volume of air in a house
- Length x Width x Average height
- Example
- Length 328 feet
- Width 46 feet
- Average height
- 10 feet
- Volume 328 x 46 x 10 150,880 feet3
21Tunnel fan capacity
- Depends upon
- House area
- Bird target wt.
22On the basis of cross sectional area of house and
desired velocity
- Cross Section W x H 46 X 9
- Desired Velocity 600 ft./min.
- CONE FANS
- 600 x 46 x 9/26000CFM 10
-
- BOX FANS
- 600 x 46 x 9/20000CFM 12
-
23On the basis of body wt.
- Cone fans
- 25000 birds x1.9kg. x 4cfm/kg. body wt./
26000(cfm) 8 - Box fans
- 25000 birds x1.9kg. x 4cfm/kg. body wt./
20000(cfm) 10
24CONE FANgtgt26000 CFM
25Cooling pads area
26- Normal pad dimensions
- 6.5 x 2.0 x 6.0
- One pad area will be 13 sq. ft.
27(No Transcript)
28Minimum ventilation fans
- capacity for minimum ventilation should be
25-30 of total ventilation.
Air inlets/Vents
82600 x / 700 cfm
118 sq. ft. 118/2.1875(7 x45)
54 Vents
29Air speed/air exchange
- During brooding there is no need of air speed
across the birds but proper air exchange is a
must - After brooding the air speed across the birds to
be 1.5 m/s to 2.5 m/s
30Air inlet area
- Total CFM of the fans standard CFM per square
feet / Minute of 6 inch Pads - Note
- For 6 inch cool pads (45 x 45 or 30 x 30)
- 400 CFM per 1 ft2
31(No Transcript)
32Air baffels
- Air baffles can be installed to reduce cross
section of the house and to increase air velocity
along the house.
33Relative Humidity (RH)
- RH is the amount of moisture in the air
compared to the maximum amount of moisture the
air can hold relative to the dry bulb
temperature.
34Insulation
35(No Transcript)
36Insulating Walls
37Time calculation for minimum ventilation
- Suppose as we have 25000 birds, then
- 0.5 cfm/kg. is required for winter season.
- 1.00 cfm/kg. is required for summer season.
38In case of winter season
- 25000 x0.04kg. x0.5/10000 cfm0.05 min
- 0.05 x30015 sec.
- It means that fan will be on for 15 sec. and off
for 285 sec. - If 1sq.in. air inlet is opened then 4 cfm will
pass through.
39In the case of summer season
- 25000 x0.04kg. x1/10000 0.1min
- 0.1 x300 30 sec.
- It means that fan will run for 30 sec. and off
for 270 sec.
40What air speed we need in house to cool our birds
?
- Depends upon a number of factors
- Temperature
- Bird size/age
- Density
- Humidity
41Estimated effective temperature reduction when
air temp is 85-90F
Air velocity Bird age
Ft/min 1 week 4 weeks 7 weeks
100 -4 -2
200 -12 -5 -2
300 -22 -10 -4
400 -15 -7
500 -18 -10
Air Velocity Bird Age
42HEAT STRESS INDEX TABLE
C F 60 65 70 75 80 85 90 95 99
35 95 155 160 165
32.2 90 150 155 160 165
29.4 85 145 150 155 160 165
26.7 80 140 145 150 155 160 165
23.9 75 135 140 145 150 155 160 165
21.1 70 130 135 140 145 150 155 160 165 164
TEMPEATURE. RELATIVE HUMIDITY
43Air speed and air temperature
- The higher the temperature, greater amount of
wind speed required. - The higher temperature, the more younger birds
benefited from wind speed. - Excessive air movement can be problematic when
air temperature are relatively low.
44Bird cooling and Relative humidity
- As humidity increases, effectiveness of panting
decreases. - As humidity increases, the cooling produced by
pads decreases. - 20 increases in relative humidity evaporative
pad cooling decreases by 25.
45Air speed and Relative humidity
- The more humid climate the more speed you need.
- The longer tunnel opening the larger dead spot
and more humid.
46Potential problems
- Not uniform temperature in the house
- Proper insulation of the house.
- First go on tunnel ventilation, then cooling.
- Increased heating cost
- Center house brooding.
- Proper insulation.
47Potential problems
- Uneven ventilation
- Excessive leakage near the pads area, doors,
windows, and air inlets. - Litter caking
- During Winter
- Improper minimum ventilation.
- Requires proper air inlets opening along with
proper no. of 36 fans. - During Summer
- Low air movement.
- Proper ventilation. (First go on tunnel
ventilation, then cooling).
48Fan setting during summer season
Age (weeks) Temperature(C) Tunnel fans Evap. Cooling(C) PUMP CLOSE(C)
1 32.5 F1 36 4
2 30.5,31.5 F1,F2 34 4
3 28.5,29,29.5,30 F1,F2,F3,F4 32 4
4 26.5,27,27.5,28,28.5,29 F1,F2,F3,F4,F5,F6 30 4
5 24.5,25,25.5,26,26.5,27,27.5,28 F1,F2,F3,F4,F5,F6,F7,F8 28 4
6 23.5,24,24.5,25,25.5,26,26.5,27,27.5,28 F1,F2,F3,F4,F5F6,F7,F8,F9,F10 28 4