Energy Audit of AHU, HVAC - PowerPoint PPT Presentation

About This Presentation
Title:

Energy Audit of AHU, HVAC

Description:

Check our new presentation on energy audit for AHU, illustrating money saving and power saving for one of our client. – PowerPoint PPT presentation

Number of Views:374
Slides: 11
Provided by: mgcs123
Category: Other

less

Transcript and Presenter's Notes

Title: Energy Audit of AHU, HVAC


1
MGCS-Energy Audit Company
2
CASE STUDY AHU ( Air Handling Unit)
3
  • Technical Specifications of AHU
  • Double skinned type AHU with PUF (25 mm thick)
    are provided with EFF1 level motors.
  • Blower with paddle blade impeller are provided.
  • The belts are V-Belt. Chilled water coil of
    copper tube with finned aluminum fins provided.
  • Chiller coils with 6 rows with 12 fins per inch
    spacing provided.
  • The fan is so designed with outlet velocity
    restriction upto maximum 10 m/sec. 50mm thick air
    filter with 3 ply HDPE with 2 layers of aluminum
    provided.
  • The ducts are of galvanized sheet with suitable
    insulation and support.

4
  • Location Details
  • There are 12 nos of Air handling unit in the
    premises.
  • Motors are operated through Star-Delta and DOL
    starter.
  • There is no controlling of chilling water or
    other sensor to control AHU.

5
Schematic Layout of AHU
Schematic Diagram of AHU
6
Performance of AHU
7
  • TECHNICAL EVALUATION
  • From Above Table, 5 out 9 AHU Specific energy
    consumption kW/TR is higher than design.
  • RPM of fan also has been derived through formula
    as it connected through V-Belt.
  • Through static pressure it can conclude there is
    no obstacles in return air path, G-5 G-6
    considerably on higher side.
  • Disadvantage of V-Belt
  • There is a power transmission loss of about 5-7,
    when V-Belts WEDGE IN and WEDGE OUT of the
    grooved pulley.
  • Advantage of running in Flat Belt
  • Prevents elongation due to moisture absorption.
  • Ensure Better Grip of Pulley.
  • Energy Saving of at least 5-7.

8
Energy Saving Recommendation Conversion of
V-Belt to Flat belt in all AHUs between Motor
and Fan. Result of the outcome Energy saving
of at least by 5-7
9
Energy Saving Calculations Total Consumption in
AHU 63.05 KW Energy Saving _at_ 7
4.413 kW Energy saving per annum 4.413 X 10
X 240 ( 10 hours ,240 days of working)

10592.4 kWh Monetary Saving
Rs 1.18,105.2/- Investment
50,000/- Payback
5 Months Annual GHG Mitigation 8.78 ton
of CO2
10
Energy Conservation-need of the hour
Contact us now save on Energy Money
Write us at hina.gupta_at_mgcs.net.in for
any query L
-011-49040941/42/43
Write a Comment
User Comments (0)
About PowerShow.com