Title: Fundamentals of Distance Protection
1Fundamentals of Distance Protection
2Outline
- Transmission line introduction
- What is distance protection?
- Non-pilot and pilot schemes
- Redundancy considerations
- Security for dual-breaker terminals
- Out-of-step relaying
- Single-pole tripping
- Series-compensated lines
3Transmission Lines
- A Vital Part of the Power System
- Provide path to transfer power between
generation and load - Operate at voltage levels from 69kV to 765kV
- Deregulated markets, economic, environmental
requirements have pushed utilities to operate
transmission lines close to their limits.
4Transmission Lines
- Classification of line length depends on
- Source-to-line Impedance Ratio (SIR), and
- Nominal voltage
- Length considerations
- Short Lines SIR gt 4
- Medium Lines 0.5 lt SIR lt 4
- Long Lines SIR lt 0.5
5Typical Protection SchemesShort Lines
- Current differential
- Phase comparison
- Permissive Overreach Transfer Trip (POTT)
- Directional Comparison Blocking (DCB)
6Typical Protection SchemesMedium Lines
- Phase comparison
- Directional Comparison Blocking (DCB)
- Permissive Underreach Transfer Trip (PUTT)
- Permissive Overreach Transfer Trip (POTT)
- Unblocking
- Step Distance
- Step or coordinated overcurrent
- Inverse time overcurrent
- Current Differential
7Typical Protection SchemesLong Lines
- Phase comparison
- Directional Comparison Blocking (DCB)
- Permissive Underreach Transfer Trip (PUTT)
- Permissive Overreach Transfer Trip (POTT)
- Unblocking
- Step Distance
- Step or coordinated overcurrent
- Current Differential
8What is distance protection?
- For internal faults
- IZ V and V approximately in phase (mho)
- IZ V and IZ approximately in phase (reactance)
9What is distance protection?
- For external faults
- IZ V and V approximately out of phase (mho)
- IZ V and IZ approximately out of phase
(reactance)
10What is distance protection?
IntendedREACH point
Z
RELAY
11Source Impedance Ratio, Accuracy Speed
Relay
Line
System
Consider SIR 0.1
12Source Impedance Ratio, Accuracy Speed
Relay
System
Line
Voltage at the relay
Consider SIR 30
13Challenges in relay design
- Transients
- High frequency
- DC offset in currents
- CVT transients in voltages
14Challenges in relay design
- Transients
- High frequency
- DC offset in currents
- CVT transients in voltages
15Challenges in relay design
Sorry Future (unknown)
- In-phase internal fault
- Out-of-phase external fault
16Transient Overreach
- Fault current generally contains dc offset in
addition to ac power frequency component - Ratio of dc to ac component of current depends
on instant in the cycle at which fault occurred - Rate of decay of dc offset depends on system X/R
17Zone 1 and CVT Transients
- Capacitive Voltage Transformers (CVTs) create
certain problems for fast distance relays applied
to systems with high Source Impedance Ratios
(SIRs) - CVT-induced transient voltage components may
assume large magnitudes (up to 30-40) and last
for a comparatively long time (up to about 2
cycles) - 60Hz voltage for faults at the relay reach point
may be as low as 3 for a SIR of 30 - the signal may be buried under noise
18Zone 1 and CVT Transients
- CVT transients can cause distance relays to
overreach. Generally, transient overreach may be
caused by - overestimation of the current (the magnitude of
the current as measured is larger than its actual
value, and consequently, the fault appears closer
than it is actually located), - underestimation of the voltage (the magnitude of
the voltage as measured is lower than its actual
value) - combination of the above
19Distance Element Fundamentals
XL
R
XC
20Impedance locus may pass below the origin of the
Z-plane - this would call for a time delay to
obtain stability
21CVT Transient Overreach Solutions
- apply delay (fixed or adaptable)
- reduce the reach
- adaptive techniques and better filtering
algorithms
22CVT Transients Adaptive Solution
- Optimize signal filtering
- currents - max 3 error due to the dc component
- voltages - max 0.6 error due to CVT transients
- Adaptive double-reach approach
- filtering alone ensures maximum transient
overreach at the level of 1 (for SIRs up to 5)
and 20 (for SIRs up to 30) - to reduce the transient overreach even further an
adaptive double-reach zone 1 has been implemented
23CVT Transients Adaptive Solution
- The outer zone 1
- is fixed at the actual reach
- applies certain security delay to cope with CVT
transients
- The inner zone 1
- has its reach dynamically controlled by the
voltage magnitude - is instantaneous
24Desirable Distance Relay Attributes
- Filters
- Prefiltering of currents to remove dc decaying
transients - Limit maximum transient overshoot (below 2)
- Prefiltering of voltages to remove low frequency
transients caused by CVTs - Limit transient overreach to less than 5 for an
SIR of 30 - Accurate and fast frequency tracking algorithm
- Adaptive reach control for faults at reach points
25Distance Relay Operating Times
26Distance Relay Operating Times
35ms
25ms
30ms
20ms
15ms
27Distance Relay Operating Times
SLG faults
LL faults
3P faults
28Actual maximum reach curves
29Maximum Torque Angle
- Angle at which mho element has maximum reach
- Characteristics with smaller MTA will
accommodate larger amount of arc resistance
30Mho Characteristics
Traditional
Directional angle slammed
Directional angle lowered and slammed
Both MHO and directional angles slammed (lens)
31Load Swings
XL
LOOKING INTO LINE normally considered forward
Reach
Load Trajectory
Operate area
No Operate area
Typical load characteristic impedance
R
32Load Swings
Lenticular Characteristic
Load swing
33Load Encroachment Characteristic
The load encroachment element responds to
positive sequence voltage and current and can be
used to block phase distance and phase
overcurrent elements.
34Blinders
- Blinders limit the operation of distance relays
(quad or mho) to a narrow region that parallels
and encompasses the protected line - Applied to long transmission lines, where mho
settings are large enough to pick up on maximum
load or minor system swings
35Quadrilateral Characteristics
36Quadrilateral Characteristics
Ground Resistance (Conductor falls on ground)
R
Resultant impedance outside of the mho operating
region
XL
37Distance Characteristics - Summary
Mho
Quadrilateral
Lenticular
JX
R
Better coverage for ground faults due to
resistance added to return path
Standard for phase elements
Used for phase elements with long heavily loaded
lines heavily loaded
38Distance Element Polarization
- The following polarization quantities are
commonly used in distance relays for determining
directionality - Self-polarized
- Memory voltage
- Positive sequence voltage
- Quadrature voltage
- Leading phase voltage
39Memory Polarization
- Positive-sequence memorized voltage is used for
polarizing - Mho comparator (dynamic, expanding Mho)
- Negative-sequence directional comparator (Ground
Distance Mho and Quad) - Zero-sequence directional comparator (Ground
Distance MHO and QUAD) - Directional comparator (Phase Distance MHO and
QUAD) - Memory duration is a common distance settings
(all zones, phase and ground, MHO and QUAD)
40Memory Polarization
Static MHO characteristic (memory not established
or expired)
ZL
Dynamic MHO characteristic for a reverse fault
Dynamic MHO characteristic for a forward fault
Impedance During Close-up Faults
ZS
41Memory Polarization
Static MHO characteristic (memory not established
or expired)
ZL
Dynamic MHO characteristic for a forward fault
RL
ZS
Memory PolarizationImproved Resistive Coverage
42Choice of Polarization
- In order to provide flexibility modern distance
relays offer a choice with respect to
polarization of ground overcurrent direction
functions - Voltage polarization
- Current polarization
- Dual polarization
43Ground Directional Elements
- Pilot-aided schemes using ground mho distance
relays have inherently limited fault resistance
coverage - Ground directional over current protection using
either negative or zero sequence can be a useful
supplement to give more coverage for high
resistance faults - Directional discrimination based on the ground
quantities is fast - Accurate angular relations between the zero and
negative sequence quantities establish very
quickly because - During faults zero and negative-sequence currents
and voltages build up from very low values
(practically from zero) - The pre-fault values do not bias the developing
fault components in any direction
44Distance Schemes
Non-Pilot Aided Schemes (Step Distance)
Pilot Aided Schemes
Communication between Distance relays
No Communication between Distance Relays
45Step Distance Schemes
- Zone 1
- Trips with no intentional time delay
- Underreaches to avoid unnecessary operation for
faults beyond remote terminal - Typical reach setting range 80-90 of ZL
- Zone 2
- Set to protect remainder of line
- Overreaches into adjacent line/equipment
- Minimum reach setting 120 of ZL
- Typically time delayed by 15-30 cycles
- Zone 3
- Remote backup for relay/station failures at
remote terminal - Reaches beyond Z2, load encroachment a
consideration
46Step Distance Schemes
Local
Z1
BUS
BUS
Z1
Remote
47Step Distance Schemes
Local
End Zone
Z1
BUS
BUS
Z1
End Zone
Remote
48Step Distance Schemes
Local
Z1
Breaker Tripped
BUS
BUS
Breaker Closed
Z1
Remote
49Step Distance Schemes
Local
Z2 (time delayed)
Z1
BUS
BUS
Z1
Z2 (time delayed)
Remote
50Step Distance Schemes
Z3 (remote backup)
Z2 (time delayed)
Z1
BUS
BUS
51Step Distance Protection
52Distance Relay Coordination
Local Relay
Remote Relay
53Need For Pilot Aided Schemes
BUS
BUS
Local Relay
Remote Relay
Communication Channel
54Pilot Communications Channels
- Distance-based pilot schemes traditionally
utilize simple on/off communications between
relays, but can also utilize peer-to-peer
communications and GOOSE messaging over digital
channels - Typical communications media include
- Pilot-wire (50Hz, 60Hz, AT)
- Power line carrier
- Microwave
- Radio
- Optic fiber (directly connected or multiplexed
channels)
55Distance-based Pilot Protection
56Pilot-Aided Distance-Based Schemes
- DUTT Direct Under-reaching Transfer Trip
- PUTT Permissive Under-reaching Transfer Trip
- POTT Permissive Over-reaching Transfer Trip
- Hybrid POTT Hybrid Permissive Over-reaching
Transfer Trip - DCB Directional Comparison Blocking Scheme
- DCUB Directional Comparison Unblocking Scheme
57Direct Underreaching Transfer Trip (DUTT)
- Requires only underreaching (RU) functions which
overlap in reach (Zone 1). - Applied with FSK channel
- GUARD frequency transmitted during normal
conditions - TRIP frequency when one RU function operates
- Scheme does not provide tripping for faults
beyond RU reach if remote breaker is open or
channel is inoperative. - Dual pilot channels improve security
58DUTT Scheme
Â
Zone 1
Bus
Bus
Line
Zone 1
59Permissive Underreaching Transfer Trip (PUTT)
- Requires both under (RU) and overreaching (RO)
functions - Identical to DUTT, with pilot tripping signal
supervised by RO (Zone 2)
60PUTT Scheme
Rx PKP
Local Trip
Zone 2
OR
Zone 1
61Permissive Overreaching Transfer Trip (POTT)
- Requires overreaching (RO) functions (Zone 2).
- Applied with FSK channel
- GUARD frequency sent in stand-by
- TRIP frequency when one RO function operates
- No trip for external faults if pilot channel is
inoperative - Time-delayed tripping can be provided
62POTT Scheme
63POTT Scheme
POTT Permissive Over-reaching Transfer Trip
End Zone
BUS
BUS
64POTT Scheme
Remote Relay
Local Relay
65POTT Scheme
Communications Channel(s)
POTT TX 1
A to G
POTT RX 1
POTT TX 2
B to G
POTT RX 2
POTT TX 3
C to G
POTT RX 3
POTT TX 4
Multi Phase
POTT RX 4
Local Relay
Remote Relay
66POTT Scheme Current reversal example
Local Relay
Remote Relay
67POTT Scheme Echo example
Open
Local Relay
Remote Relay
68Hybrid POTT
- Intended for three-terminal lines and weak
infeed conditions - Echo feature adds security during weak infeed
conditions - Reverse-looking distance and oc elements used to
identify external faults
69Hybrid POTT
70Directional Comparison Blocking (DCB)
- Requires overreaching (RO) tripping and blocking
(B) functions - ON/OFF pilot channel typically used (i.e., PLC)
- Transmitter is keyed to ON state when blocking
function(s) operate - Receipt of signal from remote end blocks tripping
relays - Tripping function set with Zone 2 reach or
greater - Blocking functions include Zone 3 reverse and
low-set ground overcurrent elements
71DCB Scheme
72Directional Comparison Blocking (DCB)
End Zone
BUS
BUS
73Directional Comparison Blocking (DCB) Internal
Faults
Local Relay
Remote Relay
74Directional Comparison Blocking (DCB) External
Faults
Local Relay
Remote Relay
75Directional Comparison Unblocking (DCUB)
- Applied to Permissive Overreaching (POR) schemes
to overcome the possibility of carrier signal
attenuation or loss as a result of the fault - Unblocking provided in the receiver when signal
is lost - If signal is lost due to fault, at least one
permissive RO functions will be picked up - Unblocking logic produces short-duration TRIP
signal (150-300 ms). If RO function not picked
up, channel lockout occurs until GUARD signal
returns
76DCUB Scheme
Â
77Directional Comparison Unblocking (DCUB)
End Zone
BUS
BUS
78Directional Comparison Unblocking (DCUB) Normal
conditions
Load Current
FSK Carrier
FSK Carrier
GUARD1 TX
GUARD1 RX
Local Relay
Remote Relay
GUARD2 TX
GUARD2 RX
NO Loss of Guard
NO Loss of Guard
NO Permission
NO Permission
Communication Channel
79Directional Comparison Unblocking (DCUB) Normal
conditions, channel failure
Load Current
FSK Carrier
FSK Carrier
GUARD1 TX
GUARD1 RX
Local Relay
Remote Relay
GUARD2 TX
GUARD2 RX
Communication Channel
80Directional Comparison Unblocking (DCUB) Internal
fault, healthy channel
FSK Carrier
FSK Carrier
GUARD1 TX
GUARD1 RX
Local Relay
Remote Relay
GUARD2 TX
GUARD2 RX
Communication Channel
81Directional Comparison Unblocking (DCUB) Internal
fault, channel failure
FSK Carrier
FSK Carrier
GUARD1 TX
GUARD1 RX
Local Relay
Remote Relay
GUARD2 TX
GUARD2 RX
Communication Channel
82Redundancy Considerations
- Redundant protection systems increase
dependability of the system - Multiple sets of protection using same protection
principle and multiple pilot channels overcome
individual element failure, or - Multiple sets of protection using different
protection principles and multiple channels
protects against failure of one of the protection
methods. - Security can be improved using voting schemes
(i.e., 2-out-of-3), potentially at expense of
dependability. - Redundancy of instrument transformers, battery
systems, trip coil circuits, etc. also need to be
considered.
83Redundant Communications
End Zone
BUS
BUS
AND Channels
OR Channels
POTT Less Reliable
POTT More Reliable
Communication Channel 1
DCB More Secure
DCB Less Secure
Communication Channel 2
More Channel Security
More Channel Dependability
84Redundant Pilot Schemes
85Pilot Relay Desirable Attributes
- Integrated functions
- weak infeed
- echo
- line pick-up (SOTF)
- Basic protection elements used to key the
communication - distance elements
- fast and sensitive ground (zero and negative
sequence) directional IOCs with current, voltage,
and/or dual polarization
86Pilot Relay Desirable Attributes
- Pre-programmed distance-based pilot schemes
- Direct Under-reaching Transfer Trip (DUTT)
- Permissive Under-reaching Transfer Trip (PUTT)
- Permissive Overreaching Transfer Trip (POTT)
- Hybrid Permissive Overreaching Transfer Trip (HYB
POTT) - Blocking scheme (DCB)
- Unblocking scheme (DCUB)
87Security for dual-breaker terminals
- Breaker-and-a-half and ring bus terminals are
common designs for transmission lines. - Standard practice has been to
- sum currents from each circuit breaker externally
by paralleling the CTs - use external sum as the line current for
protective relays - For some close-in external fault events, poor CT
performance may lead to improper operation of
line relays.
88Security for dual-breaker terminals
Accurate CTs preserve the reverse current
direction under weak remote infeed
89Security for dual-breaker terminals
Saturation of CT1 may invert the line current as
measured from externally summated CTs
90Security for dual-breaker terminals
- Direct measurement of currents from both circuit
breakers allows the use of supervisory logic to
prevent distance and directional overcurrent
elements from operating incorrectly due to CT
errors during reverse faults. - Additional benefits of direct measurement of
currents - independent BF protection for each circuit
breaker - independent autoreclosing for each breaker
91Security for dual-breaker terminals
- Supervisory logic should
- not affect speed or sensitivity of protection
elements - correctly allow tripping during evolving
external-to-internal fault conditions - determine direction of current flow through each
breaker independently - Both currents in FWD direction ? internal fault
- One current FWD, one current REV ? external fault
- allow tripping during all forward/internal faults
- block tripping during all reverse/external faults
- initially block tripping during evolving
external-to-internal faults until second fault
appears in forward direction. Block is then
lifted to permit tripping.
92Single-pole Tripping
- Distance relay must correctly identify a SLG
fault and trip only the circuit breaker pole for
the faulted phase. - Autoreclosing and breaker failure functions must
be initiated correctly on the fault event - Security must be maintained on the healthy
phases during the open pole condition and any
reclosing attempt.
93Out-of-Step Condition
- For certain operating conditions, a severe
system disturbance can cause system instability
and result in loss of synchronism between
different generating units on an interconnected
system.
94Out-of-Step Relaying
- Out-of-step blocking relays
- Operate in conjunction with mho tripping relays
to prevent a terminal from tripping during severe
system swings out-of-step conditions. - Prevent system from separating in an
indiscriminate manner. - Out-of-step tripping relays
- Operate independently of other devices to detect
out-of-step condition during the first pole slip. - Initiate tripping of breakers that separate
system in order to balance load with available
generation on any isolated part of the system.
95Out-of-Step Tripping
The locus must stay for some time between the
outer and middle characteristics
When the inner characteristic is entered the
element is ready to trip
Must move and stay between the middle and inner
characteristics
96Power Swing Blocking
- Applications
- Establish a blocking signal for stable power
swings (Power Swing Blocking) - Establish a tripping signal for unstable power
swings (Out-of-Step Tripping) - Responds to
- Positive-sequence voltage and current
97Series-compensated lines
- Benefits of series capacitors
- Reduction of overall XL of long lines
- Improvement of stability margins
- Ability to adjust line load levels
- Loss reduction
- Reduction of voltage drop during severe
disturbances - Normally economical for line lengths gt 200 miles
98Series-compensated lines
- SCs create unfavorable conditions for protective
relays and fault locators - Overreaching of distance elements
- Failure of distance element to pick up on
low-current faults - Phase selection problems in single-pole tripping
applications - Large fault location errors
99Series-compensated linesSeries Capacitor with MOV
100Series-compensated lines
101Series-compensated linesDynamic Reach Control
102Series-compensated linesDynamic Reach Control
for External Faults
103Series-compensated linesDynamic Reach Control
for External Faults
104Series-compensated linesDynamic Reach Control
for Internal Faults
105Distance Protection Looking Through a Transformer
- Phase distance elements can be set to see beyond
any 3-phase power transformer - CTs VTs may be located independently on
different sides of the transformer - Given distance zone is defined by VT location
(not CTs) - Reach setting is in ?sec, and must take into
account location ratios of VTs, CTs and voltage
ratio of the involved power transformer
106Transformer Group Compensation
- Depending on location of VTs and CTs, distance
relays need to compensate for the phase shift and
magnitude change caused by the power transformer
107Setting Rules
- Transformer positive sequence impedance must be
included in reach setting only if transformer
lies between VTs and intended reach point - Currents require compensation only if
transformer located between CTs and intended
reach point - Voltages require compensation only if
transformer located between VTs and intended
reach point - Compensation set based on transformer connection
vector group as seen from CTs/VTs toward reach
point
108Distance Relay Desirable Attributes
- Multiple reversible distance zones
- Individual per-zone, per-element characteristic
- Dynamic voltage memory polarization
- Various characteristics, including mho, quad,
lenticular - Individual per-zone, per-element current
supervision (FD) - Multi-input phase comparator
- additional ground directional supervision
- dynamic reactance supervision
- Transient overreach filtering/control
- Phase shift magnitude compensation for distance
applications with power transformers
109Distance Relay Desirable Attributes
- For improved flexibility, it is desirable to have
the following parameters settable on a per zone
basis - Zero-sequence compensation
- Mutual zero-sequence compensation
- Maximum torque angle
- Blinders
- Directional angle
- Comparator limit angles (for lenticular
characteristic) - Overcurrent supervision
110Distance Relay Desirable Attributes
- Additional functions
- Overcurrent elements (phase, neutral, ground,
directional, negative sequence, etc.) - Breaker failure
- Automatic reclosing (single three-pole)
- Sync check
- Under/over voltage elements
- Special functions
- Power swing detection
- Load encroachment
- Pilot schemes
111Questions?