Title: Tier II: Case Studies
1(No Transcript)
2Tier II Case Studies
-
- Section 2
- Heat Exchange Network Optimization by Thermal
Pinch Analysis
3Optimization Problems
- There are many different types of optimization
problems - It is important to recognize that an optimization
problem exists even if it does not immediately or
easily lend itself to one of the previously
described analytical methods of optimization - Sometimes an alternative method that is more case
specific must be used
4Optimization Problems
- A common example of one of these problems is the
optimization of a heat exchange network - Without knowing what the maximum possible network
integration is, and the minimum possible heating
and cooling utilities required, it can be very
difficult to design an optimized heat exchange
network
5Optimization of Utility Use in a Heat Exchange
Network
- Heating and cooling utilities consumption can be
treated as an optimization problem - The goal is to minimize the amount of heating and
cooling utilities being used by optimizing the
heat exchange network - A different method will be used for this type of
optimization than what was seen previously
6Constraints
- Total heating (QH) and total cooling (QC) used
will still need to be minimized according to a
set of constraints - These constraints are
- The target temperature of individual streams
- The minimum approach temperature in a heat
exchanger
7Constraints
- Objective function
- Minimize QH QC
- Constraints
- T2i ai , T1i bi
- t1i ci , t2i di
- DTmin k
8Minimum Approach Temperature
T1 hot out T2 hot in t1 cold in t2 cold
out
9Minimum Approach Temperature
- To get the outlet temperature of one stream
closer to the inlet temperature of the other
stream, exchanger area must be increased,
increasing capital cost - Decreased exchanger area means decreased capital
cost, but increased utilities cost to make up for
lost heat exchange capacity
10Using Minimum Approach Temperature to Tradeoff
Capital vs. Operating Costs
- This graph demonstrates the tradeoff between
capital and operating costs a decrease in one
is met with an increase in the other
11Minimum Approach Temperature
- The optimum exchanger size exists where the total
annualized cost is minimized - This typically will correspond to a minimum
approach temperature, DTmin of about 10oC - This DTmin 10oC is a rule of thumb it can
change depending on the fluid service and the
type of heat exchanger employed
12Minimum Approach Temperature
- Thermal Equilibrium
- T t
- Practical Feasibility
- T t DTmin
- This must be included in the coming analysis
13Graphical Method Thermal Pinch Analysis
- To optimize a heat exchange network, an example
of the graphical method to determine the thermal
pinch point will first be examined - The same example will then be solved using the
algebraic method for comparison
14Stream Data
- Using the stream supply and target temperatures,
the enthalpy change of each stream must be
calculated - Enthalpy change
- DH FiCpi(T2i T1i) HHi
- FiCpi(t2i t1i) HCi
- FiCpi flow rate x specific heat (kW/K)
15Stream Data
16Stream Data
- Stream data is then plotted as a series of
straight line segments in order of ascending
temperature - Each consecutive segment begins at the enthalpy
level where the previous segment finished - A hot stream is any that must be cooled, while
a cold stream is any that must be heated,
regardless of supply temperature
17Hot Streams
18Cold Streams
19Composite Stream Curves
- Next the composite curves of the hot and cold
streams must be constructed - These composite curves represent the total amount
of heat to be removed from the hot streams and
the total amount of heat that must be added to
the cold streams to reach the target stream
temperatures
20Hot Composite Stream Construction
H3
H2
H1
T11
T21
T12
T22
T13
T23
21Hot Composite Stream Construction
Hot composite stream
22Cold Composite Stream Construction
C3
C2
C1
t13
t22
t21
t11
t12
t23
23Cold Composite Stream Construction
Cold composite stream
24Optimizing the Heat Exchange Network
- The cold composite stream must now be
superimposed over the hot composite stream to
perform the thermal pinch analysis - This will give the minimum amount of utilities
required to reach the target states - Note how the temperature axis is shifted for the
cold composite stream to account for the minimum
approach temperature
25No Heat Integration
Total hot utility required
Cold composite stream
QH,max 65,000 kW
Total cold utility required
Hot composite stream
QC,max 67,000 kW
QC QH 132,000 kW
26No Heat Integration
- With no heat integration, the amount of energy
required to reach the target state is maximized - In this case the total amounts of energy required
are - Cooling utility, QC 67,000 kW
- Heating utility, QH 65,000 kW
- Total utilities QC QH 132,000 kW
- Clearly there is room for optimization
27Partial Heat Integration
- By moving the cold composite stream down a bit, a
partially integrated heat exchange network is
graphically represented - Some heat is transferred from hot streams to cold
streams to approach the temperature targets
28Partial Heat Integration
Cold composite stream
Hot composite stream
QC QH 102,000 kW
29Partial Heat Integration
- This heat exchange network is only partially
optimized and already utility consumption is
reduced by 30,000 kW - The utilities required are
- Cooling utility, QC 52,000 kW
- Heating utility, QH 50,000 kW
- Total utilities QC QH 102,000 kW
- Clearly further integration can provide
significant energy savings
30Optimized Heat Integration
- To determine the optimized heat exchange network,
the thermal pinch point must be found - This is accomplished by moving the cold composite
stream down just until one point on the line
meets a point on the hot composite line - This point is the thermal pinch point
31Optimized Heat Integration
QH,min 8,500 kW
Cold composite stream
Integrated heat exchange 56,500 kW
Pinch point
Hot composite stream
QC,min 10,500 kW
240
QC QH 19,000 kW
32Optimized Heat Integration
- The heat exchange network is now fully optimized
- Total required utilities are minimized
- Minimum cooling utility, QC,min 10,500 kW
- Minimum heating utility, QH,min 8,500 kW
- Minimum total utilities QC QH 19,000 kW
- No heat is passed through the pinch point
33Passing Heat through the Pinch Point
- To have an optimized heat exchange network, it is
critical that no heat is passed through the
thermal pinch point - By passing an amount of heat, a, through the
pinch point, an energy penalty of 2a is added to
the total utilities requirement - It is very important to maximize integration in a
heat exchange network
34Passing Heat Through the Pinch Point
QH QC QH,min QC,min 2a
35Crossing the Pinch Point
- It would appear that extra energy can be saved by
lowering the cold composite stream line further - This does not work however because it creates a
thermodynamically infeasible region - For this to work, heat would have to flow from
the cooled hot streams to the heated cold streams
- from a cold source to a hot source
36Crossing the Pinch Point
Cold composite stream
Pinch point
Hot composite stream
Infeasible region
37Disregarding DTmin
- Another tempting error is to disregard the
minimum approach temperature - By disregarding a minimum approach temperature,
the absolute minimum thermodynamically possible
utility requirements are obtained - Although this is thermodynamically possible, it
is not practically feasible as it would require
an infinitely large heat exchanger area - This would obviously cost far more than the
relatively small energy savings are worth
38Disregarding DTmin
QH,min thermo.
QC,min thermo.
240
39Algebraic Method
- This same problem will now be solved using the
algebraic method - This will involve producing a temperature
interval diagram, tables of exchangeable heat
loads, and cascade diagrams
40Stream Data
From before
41Temperature Interval Diagram
- The first step is to construct the temperature
interval diagram - This diagram shows the starting and finishing
temperatures of each stream - An interval begins at a streams starting or
finishing temperature, and it ends where it
encounters the next beginning or finishing
temperature of a stream - Draw horizontal lines across the table at each
arrows head and tail, with the intervals lying
between these lines - Note how the cold stream temperature scale is
staggered by 10 degrees
42Temperature Interval Diagram
43Table of Exchangeable Heat Loads
- The next step is to construct tables of
exchangeable heat loads for the hot and cold
streams - These tables show the amount of energy that must
be added or removed from a stream over a
particular interval - These energy values are calculated as
- DHj,i FCpjDTi, where DTi is the positive
temperature difference across the interval, and j
denotes the stream number
44Table of Exchangeable Heat Loads
45Table of Exchangeable Heat Loads
46Cascade Diagrams
- Using the information from the heat load tables,
the cascade diagrams can now be constructed - These diagrams will be used to determine the
pinch point and the minimum heating and cooling
utilities required
47Cascade Diagram
- First, the cascade diagram is drawn as it appears
at right, with one box for each interval that
appeared in the temperature interval diagram
48Cascade Diagram
- Next, the total values from the exchangeable heat
load tables are added to the cascade diagram - Hot stream loads enter on the left, cold stream
loads exit on the right
49Cascade Diagram
0
- Now, by subtracting an intervals cold load from
the hot load, and adding the resulting value to
the residual from the previous stage we get the
residual value for the subsequent stage - ri HHi HCi ri-1
12000
7500
5500
-2500
-8500
-5500
-1500
4500
1) 12000 0 0 12000
2) 3000 7500 12000 7500
3) 13000 15000 7500 5500
5) 0 6000 -2500 -8500
6) 12000 9000 8500 -5500
8) 16000 10000 1500 4500
7) 4000 0 5500 -1500
9) 0 2500 4500 2000
4) 7000 15000 5500 -2500
2000
50Thermal Pinch Point
- The thermal pinch point occurs at the largest
negative number
- The absolute value of this number is now added in
at the top to cascade through
51Revised Cascade Diagram
8500
8500
8500
8500
8500
8500
8500
8500
8500
8500
52Revised Cascade Diagram
Qmin,heating
- We now have the final revised cascade diagram
- It can be seen that by adding additional energy
at the top, it will cascade through and also be
present at the bottom
Pinch Point
QH QC QH,min QC,min 2a !
Qmin,cooling
53Optimized Heat Integration
- The heat exchange network is now fully optimized
- Total required utilities are minimized
- Minimum cooling utility, QC,min 10,500 kW
- Minimum heating utility, QH,min 8,500 kW
- Minimum total utilities QC QH 19,000 kW
- As expected, these values are the same as
obtained by using the graphing method
54Design Considerations
- Some design rules to optimize utility
consumption - Do not pass heat through the pinch point
- Do not use cooling utilities at temperatures
above the pinch point - Do not use heating utilities at temperatures
below the pinch point
55Constructing the Heat Exchange Network
- Now that the pinch analysis has been performed,
the heat exchange network can be constructed - It is a good idea to perform the pinch analysis
first because it sets the performance goal of an
optimized heat exchange network - There is no quick method of reliably determining
the minimum number of heat exchangers, but the
following method should help to construct the
network
56Constructing the Heat Exchange Network
- With QC,min and QH,min known, construct a plot
similar to the temperature interval diagram,
except instead of arrows, use boxes that have a
width representing FCp - The area of these boxes corresponds to the heat
exchanged by the stream - Draw a horizontal line across at the pinch point
remember, no heat is to be passed across this
point
57Constructing the Heat Exchange Network
58Constructing the Heat Exchange Network
- Now, add QC,min to the lowest point on the
coldest hot stream and determine the resulting T1
and T2 for this exchange. Note that T1, T2, t1,
and t2 now do not necessarily correspond to the
same values as used earlier and are different for
each exchanger - QC,min FCp(T2 T1)
- Do the same with QH,min, adding it to the highest
point on the hottest cold stream - QH,min FCp(t2 t1)
59Constructing the Heat Exchange Network
60Constructing the Heat Exchange Network
- Now, working out from the pinch point, match up
streams, remembering not to transfer heat across
the pinch point and keeping DTmin in mind - For each matched stream, determine the
temperatures that exist for the inlet and outlet
of the heat exchanger - Qex FCp(T2 T1) FCp(t2 t1)
- Having the table of stream data including
enthalpy change on hand may be helpful for
determining the best way to match a stream
61Matched Streams
62Heat Exchangers
- 4 heat exchangers, plus a heater and a cooler are
needed to meet the optimum heat exchange
requirements of this system
63Conclusion
- There is no quick method that is guaranteed to
give the minimum number of heat exchangers
required every time - However, by first performing a thermal pinch
analysis to determine the maximum heat exchange
possibilities, designing an optimum network
configuration is made a lot easier
64References
- Dr. El-Halwagi lecture notes