Title: PlantScape and EBI
1HC900
Hybrid Controller
PlantScape and EBI Universal Modbus Driver
Interface
Ethernet LAN / WAN
2Requirements
- System Requirement
- PlantScape Vista/SCADA, R400 or R500.1
- - Station 1.1 (Build 1358)
- Experion PKS, R100
- HBC EBI R200.1
-
- Driver Requirement
- Universal Modbus Driver (also referred to as
UMB driver)) for above releases (updated for
Ethernet Interface to HC900 and Trendview via
Modbus/TCP)
Universal Modbus is a Honeywell term. The
driver uses the documented Modbus address map
that applies to many Honeywell products in
common. It means that the modbus addresses for
similar parameters, such as the PV of loop 1, in
different products are the same, or universal.
3Products Supported by UMB Driver
Universal Modbus (UMB) Driver Supports
- UDC 2300, 3300, 5300 Controllers
- DPR 180, 250 Recorders
- DR 4300, 4500 Recorders
- VPR100, VRX 100, 180 Recorders
- UMC800
- HC900 (Ethernet)
- TrendView Recorders (Ethernet)
- All I/O, Pen Values
4Simplest Topology
Single HC900 Controller Connection
- PlantScape or EBI Server PC with Universal
Modbus Driver -User Station
RS-485 twisted pair, 2000 Ft (600 m)
Ethernet 10Base-T Crossover cable 328 Ft (100 m)
PS
HC900
1042 OI or 559 OI
Unit Process
5Expanded Topology
Multi-Controller, Multi-PC Connection
To other network
PlantScape or EBI User Station
PlantScape or EBI Server / Station
Switchor Router
Ethernet 10Base-T
100m each
1042 OI
559 OI
Switch
HC900
Peer-to-Peer Communications
Hub
Process A
Remote I/O Racks
Ethernet 10Base-T 100m each
Process B
Process D
Process C
6Universal Modbus Driver for HC900
- QuickBuilder database acronym (named
parameter) entry for - I/O (1st rack only, other racks use hexadecimal
addressing) - Signal Tags, 1 to 1000 (read only)
- Variables, 1 to 600 (read and write)
- Control loops, 1 to 24 (loops 25-32 use hex
addresses for loop parameters) - SP Programmers 1- 4 (requires only 1 Point
assignment per programmer) - SP Schedulers 1 and 2
- Provides standard displays for SP Programmers 1-
4, SP profile pre-plot and PV trending, and
recipe management for up to 1000 recipes
(Variables only), 1000 profiles, and 1000
combined recipes (programmers and Variables). - Note SP Programmers 5 through 8 addressing not
supported in PlantScape) - Supports HC900 Digital Signal Tags and
Variables for assignment to PlantScape Digital
Status Points - All other non-named parameters use Modbus
hexadecimal addressing - Supports UMC800 in addition to HC900 (up to
UMC800 specification limits)
7UMB Driver Availability
PlantScape
- Specify Universal Modbus driver when ordering
- For R400 and R500.1, download upgrade from
- Industry Solutions SSOL (Solution Support
OnLine) website - 3. Follow readme file for installation
instructions
Experion PKS
- Specify Universal Modbus driver when ordering
- (updated version is available with Experion
PKS)
HBC EBI
- Specify Universal Modbus driver when ordering
- For R200.1, download upgrade from
- HBC Support website
- 3. Follow readme file for installation
instructions
8Standard Group Display
Standard Station Group Display, Loops 1-24 with
Universal Modbus driver
Analog Composite Points for control loops
Mode Selections AUTO-LSP AUTO-RSP
MAN-LSP MAN-RSP (based on using this mode
format)
9Database Preparation
Prior to QuickBuilder Database entry
- Print out the following HC Designer Reports for
each HC900 - configuration
- Tag Information Report lists all Signal Tags
and Variables by - number with tag names and descriptors
for association - Block Modbus Addresses lists major (principal)
blocks by - number such as loops, setpoint
programmers, sequencers, etc.
The numbers entered for HC900 control loops,
signal tags, variables, etc. in QuickBuilder
correspond to those listed in these reports.
10Station Display Loop Point Detail