Title: Protection of Industrial Power Systems
1Protection of Industrial Power Systems
Mine Equipment Design Selection and Maintenance
2Faults
- Any abnormal state of the system
- Open circuit faults
- less common
- of less concern
- often followed by a short-circuit fault
- but may be a hazard for personnel
- Short-circuit faults
- due to short circuits
- more common and more severe consequences
- Overload currents
- Overvoltage ( voltage surges and transients) due
to - lightning strikes
- switching
3Dangers From Short Circuit (S/C) Faults
- If allowed to persist for an extended period S/C
faults may cause - Reduced stability of the power system
- Damage to the equipment in the vicinity of the
fault - Explosions in equipment containing insulating oil
followed by fire, injuries to personnel and
damage to other equipment - Cascading effect - disruption in a large power
system service area due to successive action of
protective devices
4(No Transcript)
5Role of System Protection
- to detect faults
- to selectively isolate faulted parts of the
system - to permit short clearance time to limit the fault
power - if a protection device fails, the upstream
protection device must provide the
protection - selectivity(discrimination)
- a fault is detected by a number of protection
devices, but only the protection device closest
(and above) to the fault location is triggered
6Requirements of Protection of Wiring
- Must carry its rated current continuously without
overheating or deterioration - Small overloads of short duration should not
activate them - Small overloads of duration long enough to cause
overheating should activate them - protection must open the circuit before the
damage is caused by fault currents - Must be discriminative - only faulty circuit is
isolated and other circuits remain unaffected and
operative
7Protective Devices
- Most commonly used are
- Fuses
- Circuit Breakers
- Relays
- Reclosers
- Combination of those
- They have different switching(tripping or
pre-arcing) characteristic - is pre-arcing time vs. current - the elapsed
time between the commencement of the current
(large enough to melt the fuse or open circuit
breaker contacts) and the instant of melting or
opening.
8(No Transcript)
9Reactors at Mining Sites (left) for Filtering
electrical noise (disturbances) produced by heavy
machinery. HV transformer with bushings (right).
10Grading of Series-Connected Fuses
- Absolute discrimination (selectivity) is achieved
if the ratio of the current ratings for these two
fuses is 1.6. (Fig.1.3/18)
11Grading of Circuit Breakers
12Grading of Circuit Breakers
13Typical Protection System
- Transducer (sensor)
- detects the increase of current and drop of
voltage due to short circuit in the system - CT (current transformer) or VT(voltage
transformer) - Relay
- read the signal from transducer
- energize the tripping circuit of the circuit
breaker - Circuit Breaker
- open their contacts to disconnect the section
with the fault
14Circuit Breaker (left), Current Transformer
(middle), Voltage Transformer (right)
15Overcurrent Protection Current Transformers
Circuit breakers
16- Rated Switching Capacity
- Is the maximum value of the short-circuit current
that the protection device can clear correctly. - Back-up protection
- in case of fault larger than rated switching
capacity the back-up must activate the upstream
(above) protection device - Zone protection
- protects sections of power system distribution
- zones overlap
- Motor Protection
- HRC fuses,
- fuzecontactorthermal overload relay
- switch gear assemblies with thermistor protection
devices (for motors operating in tough
conditions) - motors with thermally critical rotor must have
overload relay.