Title: LM10
1LM10
- A Motor Management System for Low Voltage Motor
Control
2Presentation Agenda
- GE Multilin Business Recap
- LM10 Motor Protection System Product Details
- Equipment Integration Considerations
- Frequently Asked Questions
- QA
3GE Multilin Business Recap
4(No Transcript)
5GE Multilin Broad Product Portfolio . . .
M60
469
369
G60
269 Plus
G30
Motor Protection
239
Generator Protection
489
MM2
SPM
MPM
489L
LM10
MIGII
EPM 9000
T60
EPM 9800
PQMII
EPM 6000
T35
Metering
Transformer Protection
EPM 5000
EPM 2000
745
EPM 1000
L90
JungleMux
L60
TN1U
D60
Transmission Line Protection
TN1Ue
Multinet
D30
Communications
FAC1000/2000
Accessories
F485
B30
B90
Bus Protection
MIB
Voltage Transformers
Current Transformers
HIM
Instrument Transformers
F60
Control Transformers
750/760
Feeder Protection
F35
URC
F650
Low-End To Full-Featured Products
735/737
MIFII
FM2
6LM10 Motor Protection System Product Details
7LM10
- A modular approach to electronic motor protection
control - Pick choose the desired components (Base Unit,
PDU, CT sensor pack) - Designed for GE Evolution MCC but applicable to
any LV MCC - Fits into standard motor control center buckets
- More than an Overload relay
- Converges several device requirements
- PLC I/O
- Timing Relays
- Load Sensing Relays
- Ground Fault Relays
- Over and Under Voltage
- Open Protocol (DeviceNet) compatible with all
popular PLCs - Standard on LM10
- SCADA and DCS adaptable
- Easy to use and install
- Ammeter, Voltmeter
- Power Meter
- Elapsed Motor Hours
- Factory wiring
8LM10
- Applications
- Low voltage motors up to 500HP
- Motor Types
- Full Voltage non-reversing (FVNR)
- Full Voltage reversing (FVR)
- Reduced Voltage (RV)
- Two Speed- one winding (2S1W)
- Two Speed-two winding (2S2W)
- Custom Motor Type (Custom)
9LM10
10LM10
CT Connections 75 to 8005 A ratio
- CT VT Inputs
- Two sets of 3 phase CT inputs
- One set with either CT sensor pack or direct
connect 75A to 8005 A ratio CTs - 2nd Three Ph CT input for two speed motors
- Connect 20A ground fault sensor pack or 1001
core balance CT - Voltage input via CPT (provides control power,
volt/power/PF metering, over/undervoltage)
2nd 3 phase CT Input For Two Speed Motors
11LM10
- 7 Digital Inputs
- Stop control input
- Reset control input
- Contactor status inputs (Aux Sens1, Aux Sens2)
- Start control inputs for RUN1 and RUN2
- DeviceNet control switch input (Control)
- (disables RUN1 and RUN2 inputs, Stop and Reset
not affected) - 4 Relay Outputs
- NEMA C150 pilot duty ratings
- Two relays to control the coils of motor
contactor (enabled by RUN1 or RUN2 inputs) - One relay to annunciate ground fault status
- Additional programmable relay for fault status
indication (overcurrent, jam, stall, unbalance,
aux sense fault, load loss, power failure,
DeviceNet fault, over/undervoltage) - Power Supply Input
- 96 to 140VAC range
- Autorestart feature of up to 4 s
12LM10 Components
Base Unit
Form Factor Small, fits in most MCCs
Trip Class Selector Up to 4 different NEMA
overload trip classes (Class 10, 15, 20 or 30)
DeviceNet Connector Std Harris 5Pin Micro
connector (allows daisy chain from one unit to
another)
Status LEDs (MS) Module Status (NS) Network
Status (OC) Overcurrent Trip (GF) Gnd Fault
Trip (CUB) O/C Unbalance
RJ11 6C Telephone Jack Used to connect to either
PDU or PC PC cable included, connect via Com1
Hardware Selectable MAC ID Baud Rate (Up to 63
address 500kbps)
Programmable Display Unit
CT Sensor Pack
4x16 LCD Used for to program and display metering
and trip data
Pwr Trip LEDs
Self powered from LM10 Base Unit
Wide variety of commonly used CT blocks, one stop
shopping for our customers
13LM10 Base Unit
Trip Class Selector Up to 4 different NEMA
overload trip classes (Class 10, 15, 20 or 30)
DeviceNet Connector Standard Harris 5Pin Micro
connector (allows daisy chain from one unit to
another)
RJ11 6C Telephone Jack Used to connect to either
PDU or PC PC cable included, connect via Com1
Status LEDs (MS) Module Status (NS)
Network Status (OC) Overcurrent
Trip (GF) Gnd Fault Trip (CUB) O/C Unbalance
Hardware Selectable MAC ID Baud Rate (Up to 63
address 500kbps)
14LM10 Base Unit
Dual row phoenix terminal block
15Protection Control
- Overcurrent Trip
- Current in any phase greater than 1.2 x FLA, the
unit calculates the time to trip - Separate calculations are performed for cold and
hot motors - Once the fault condition is reached, the LM10
unit will not reset until an appropriate
cool-down period has elapsed - Overcurrent function can not be disabled
16Protection Control
17Protection Control
- Cool Down Time
- Upon an Overcurrent, Jam or Stall fault, the LM10
forces a cool-down period before the motor may be
restarted - The time to reset is calculated as a function of
Trip Class and FLA a the time of trip - While the motor is in the cool-down time delay,
the PDU status screen will show a number
decrementing from 99. Once the number reaches 0,
the motor can be restarted and the READY TO RUN
message will be displayed
18Protection Control
- Current Unbalance Trip
- Trips if the phases are unbalanced
- If the average current exceeds the FLA, then the
average current is used in the calculations - Programmable trip setting between 2 and 25 FLA
- Time delay settable between 0 and 255 seconds
- 6 current unbalance equates to a 1 voltage
unbalance - A 4 voltage unbalance equates to a 24 current
unbalance and will frequently cause motor damage - This function can be disabled
- Ground Fault Trip
- Programmable trip setting between 0.4 and 20A
- Time delay settable between 0.5 and 2.5 seconds
- This function can be disabled
19Protection Control
- Over/Undervoltage Trip
- Maximum minimum trip levels are hard coded into
LM10 - Undervoltage trip level is 80 (or 96V)
- Overvoltage trip level is 117 (or 140V)
- This function can not be disabled
- Jam Protection
- According to NEMA or IEC MG 1-1998 part 12, page
21, polyphase motors 600 V or less not exceeding
500 horsepower shall be capable of withstanding a
current not less than 1.5 times the full load
rated current for not less than two minutes when
the motor is at normal operating temperature.
For relatively low over-current conditions,
particularly on higher NEMA Class motors,
trip times could be considerably longer than 2
minutes. Therefore, a separate Jam fault is
available because the standard time overcurrent
curve may not protect in this range. - Jam level can be set between 100 and 250 of FLA
- Time delay settable between 0 and 1000 seconds
- This function can be disabled
20Protection Control
- Stall Protection
- According to NEMA or IEC MG 1-1998 part 12, page
21, polyphase motors 600 V or less not exceeding
500 horsepower shall be capable of withstanding
locked-rotor current (6 times FLA) for not less
than 12 seconds when the motor is at normal
operating temperature. - Cold motor trip times for a 6 FLA fault are
determined by trip class. For example, a NEMA
Class 20 motor at 6 FLA would trip in 20
seconds. A separate Stall fault is available
which would allow the user to reduce the trip
time for large overcurrent situations. - Stall level can be set between 330 and 600 of
FLA - Time delay settable between 0 and 30 seconds
- This function can be disabled
- Load Loss Trip
- Load loss is based on watts
- Power Factor calculated is phase relationship
between voltage and phase C current - Load loss level can be set between 15 and 85 of
Full Load - Time delay settable between 0 and 255 seconds
- This function can be disabled
21Protection Control
- Auxiliary Sense Failure
- Detects that a LM10 relay contact (RUN1 or RUN2)
did not open/close according to its command and
will shut down the relay - Time delay settable between 0.1 and 25.0 seconds
- This function can be disabled
- Power Loss Autorestart Feature
- Power loss when running
- LM10 will be able to recover from a power loss of
up to 4 seconds and return to its previous run
state - Enabling autorestart allows the unit to restart
the motor without operator intervention using a
momentary Run input - The default condition, Disabled, would require
the operator to restart the motor after the LM10
regains power - Potential safety hazards must be considered and
the appropriate setup chosen for each individual
application - Run 1 to Run 2 or Run 2 to Run 1
- Delay between forward and reverse or between
speeds
22Programmable Display Unit (PDU)
- Method of configuring monitoring LM10 units
- Configuring setpoints time delays
- Viewing metering history data
- RJ11 (6 conductor) cable between PDU and LM10
base unit - LEDs
- Solid Green Power LED (flashes when
configuring) - Flashing Red Trip LED
- Trip Class, MAC ID and Baud Rate set on LM10 base
unit only - Keypad with
- Up down arrows
- ENTER key
- HISTORY key
- STATUS key
- CONFIG key
- RESET key (also esc or back key)
23enerVista LM10 Setup Software
- Computers 9-pin RS232 port connected to PDU port
of LM10 base unit - New LM10 configuration file can be created and
saved - Existing LM10 configuration can be retrieved and
saved - Existing configuration file can be altered and
downloaded into different LM10 - View metering values, status and history by
clicking keys
24Monitoring Metering
- Real-Time Metering
- Phase A Current
- Phase B Current
- Phase C Current
- Ground Current
- Voltage
- kW
- Power Factor
- Average Current
- Current Unbalance
- Elapsed Motor Hours (user can reset)
- Trip History
- Last 10 faults
- Maintained in non-volatile memory
- Phase A Current
- Phase B Current
- Phase C Current
- Ground Current
25User Interfaces
- DeviceNet Protocol
- Standard on LM10
- Allows user to control monitor LM10 units over
a network - Optional Programmable Display Unit (PDU)
- Local configuration monitoring
- RS232 Connection to PC using enerVista LM10 Setup
Software - Password Protection
- Settable from 0 to 65535
26DeviceNet Protocol
- Supports Polled, Change of State (COS), Cyclic
I/O Messaging and Explicit Messaging - MAC Address can between 0 and 63
- Baud Rate can be 125kbps, 250kbps or 500kbps
- DeviceNet Fault
- If enabled, the LM10 will consider a DeviceNet
network failure as a fault and operate relay
outputs and record into history report - Control Input Option
- Terminal 21 determines how the RUN commanded is
controlled - If power is applied to the terminal, then the
DeviceNet network has RUN control - RESET STOP functions are not affected
27Specification for LM10
Optional Key Pad Programmer LCD Display NEMA
12 Surface Door Mounted or Hand held No
screws Program Memory Power Metering ( KW, PF, Ph
Amps)
CTSensor-Pack 1/2-27 FLA for NEMA Size 1 5-90
FLA for NEMA Size 2 3
CTs with 5A secondary 30-540 FLA NEMA Size 4 to 6
Relay Input-Output
Programmable Points HV- Low Voltage
Threshold LV- High Voltage Threshold VUB- Voltage
Unbalance- OC- Over Current-
LED CUB- Current Unbalance LED GF-
Residual Zero Sequence LED LL- Load Loss with
time Delay TC- Time overcorrect Class
10/15/20/30 Time Delay on GF Timer Delay Between
Run commands Auto-Restart After Power Failure
Maintained or Momentary control communication
Address
Rating 100V-120V 50/60Htz Control
Power 200-7.2KV, 3Ph 50/60Htz. System Range
PC Software EnerVista Windows Set up software
Accuracy Power 5 Voltage 1 Current
3 Timer 5 1 second Power Consumption lt 5Watts
28LM10 Order Code
Note Please see on-line store for the most
up-to-date pricing and option availability
29Equipment Integration Considerations
30LM10 is Tightly Integrated Into GE MCC
- The LM10 is fully integrated into Evolution MCC
- Factory communication wiring uses 5-Pin Brad
Harrison style connectors - Additional I/O, via a variety of Off the Shelf
DeviceNet I/O Blocks (GE and others), is
available - The LM10 has, and will maintain, ODVA approval,
and supply an EDS file
and can Integrate with Others
31Typical Low Voltage MCC Architecture
Ethernet
DeviceNet
- Application Reqts
- Protection
- Configuration
- Remote Start/Stop
- Phase Metering
- Motor Status
PLC
HMI
LM10
LM10
LM10
LM10
LM10
LM10
LM10
LM10
32Programmable Display Unit mounted in Evolution
Series E9000 MCC
Evolution MCC
33LM10 Unit mounted in Evolution Series E9000 MCC
CT Sensor Pack
LM10 Base Unit
Brad Harrison style Connector
34Frequently Asked Questions
35Some Frequently Asked Questions
- What about Remote IO?
- A wide selection of DeviceNet Remote IO is
available from PLC manufacturers as well as from
GE Mebane (MS2000IO). This IO is intended to
work as part of a PLC/DCS system. - Does this work with an HMI?
- Yes. You can configure this to work with an HMI
either via the PLC/DCS controller or via a PC
based DeviceNet card. - Does this have ODVA?
- As we come out with firmware revisions, we will
apply and maintain ODVA. - On the subject of firmware, can I flash new
firmware upgrades into the LM10? - No. The LM10s firmware is stored on a EPROM
chip and not on flash memory. - What about cables?
- You can obtain a 3 cable when ordering the
unit. Other DeviceNet cables can be ordered via
your local PLC distributor. - What types of DeviceNet Communications does the
LM10 support? - LM10 supports unsolicited DeviceNet messaging,
and specific values via polled messaging. Please
consult the manual for specifics. - Who supports the LM10?
- GE Multilin supports the LM10 just as with all
GE Multilin Devices. Please contact our Customer
Support Team - at 1-800-547-8629. For equipment
integration considerations, please contact the
MCC equipment OEM. - Where can I get information on size, specs,
mounting, and wiring information? - All product information (manuals, cut sheets,
etc.) are available on the web.
http//www.geindustrial.com/cwc/products?pnlid6i
dlm10
36Thank you for your time. QA