10' Dynamic Behavior of ClosedLoop Control Systems - PowerPoint PPT Presentation

1 / 26
About This Presentation
Title:

10' Dynamic Behavior of ClosedLoop Control Systems

Description:

Alternative form of the standard block diagram. of a feedback control system ... Block diagram for level control system. If a proportional controller is used, ... – PowerPoint PPT presentation

Number of Views:134
Avg rating:3.0/5.0
Slides: 27
Provided by: infosys
Category:

less

Transcript and Presenter's Notes

Title: 10' Dynamic Behavior of ClosedLoop Control Systems


1
10. Dynamic Behavior of Closed-Loop Control
Systems
  • Feedback control loop( or closed-loop system)
    the combination of the process, the feedback
    controller, and the instruments.

10.1 Block Diagram Representation
2
10.1.1 Process
Figure 10.2. Inputs and output of the process.
  • Dynamic model of a steam-heated, stirred tank

3
  • Assume that the dynamics of the heating coil are
    negligible since the dynamics are fast compared
    to the dynamics of the tank contents. ? Left
    side of (10.2) equal to zero!

Substituting (10.4) into (10.1) gives
4
Figure 10.3. Block diagram of the process.
5
10.1.2 Thermocouple and Transmitter
  • Assume that the dynamic behavior of the
    thermocouple and transmitter can be approximated
    by a first-order transfer function

Figure 10.4. Block diagram for the thermocouple
and temperature transmitter.
6
10.1.3 Controller
  • Assume that a proportional plus integral
    controller is used

Figure 10.5. Block diagram for the controller.
7
10.1.4 Current-to-Pressure(I/P) Transducer
Figure 10.6. Block diagram for the I/P
transducer.
Figure 10.7. Block diagram for the control
valve.
8
  • Complete block diagram

Figure 10.8. Block diagram for the entire control
system.
9
10.2 Closed-Loop Transfer Functions
  • The standard notations.

10
Figure 10.9. Standard block diagram of a feedback
control system
  • In Figure 10.9. each variable is the Laplace
    Transform of a deviation variable.
  • Feedforward path the signal path from to
    through blocks ,
  • and .
  • Feedback path the signal path from to the
    comparator through .

11
Figure 10.10. Alternative form of the standard
block diagram of a feedback control system
12
10.2.1 Block Diagram Reduction
  • It is often convenient to combine several blocks
    into a single block.
  • Example

Figure 10.11. Three blocks in series.
13
10.2.2 Set Point Changes( Servo Problem)
Figure 10.9. Standard block diagram of a feedback
control system
  • Desired closed-loop transfer function,

14
10.2.2 Load Changes( Regulatory Problem)
  • Desired closed-loop transfer function,

15
10.3 Closed-loop Responses of Simple Control
Systems
In this section, we consider the dynamic behavior
of several elementary control problems for load
variable and set-point changes.
  • For the liquid-level control system

Figure 10.10. Liquid-level Control System
16
q1 the load variable. q2 the manipulated
variable. Assumption 1. The liquid density r
and the cross-sectional area of the tank A are
constant. 2. The flow-head relation is linear,
q3 h/R. 3. The transmitter and control
valves have negligible dynamics. 4. Pneumatic
instruments are used.
  • Mass balance for the tank contents.
  • Transfer Function

Where, KP R, t RA
17
Assuming that the dynamics of the level
transmitter and control valve, the corresponding
transfer functions can be written as Gm(s) Km
and Gv(s) Kv .
  • Block diagram for level control system

Figure 10.11. Block diagram for level control
system
18
  • Proportional Control and Set-Point Change

If a proportional controller is used, then Gc(s)
Kc . The closed-loop transfer function for
set-point changes is given by
where,
KOL is the open-loop gain, KOL Kc Kv Kp Km (KOL
gt 0 for stability ? chapter 11) Thus since t1 lt t
, one consequence of feedback control is that it
enables the controlled process to respond more
quickly than the uncontrolled process. ? The
reason for the introduction of feedback control
19
The closed-loop response to a unit step change of
magnitude M in set point is given by
Figure 10.12. Step response for proportional
control (set-point change)
20
The offset ( steady-state error) is defined as
Since KOL Kc Kv Kp Km Kc ?, KOL ?,
offset ? if Kc ? ?, offset ? 0
21
  • Proportional Control and Load Changes

The closed-loop transfer function for load
changes is given by
where,
The closed-loop response to step change of
magnitude M in load
The same situation can be observed as set point
change case
22
  • PI Control and Load Changes

The closed-loop transfer function for load change
is given by
This transfer function can be rearranged as a
second-order one.
where, K3 tI / KcKvKm
23
For a unit step change in load,
because of the exponential term in (10.39).
For set-point change, offset will be zero too!
Addition of Integral action ? Elimination of
offset for step changes of load and set-point
24
  • PI Control of an Integrating Process

Figure 10.13. Liquid-level control system with
pump in exit line
This system differs from the previous example in
two ways 1. The exit line contains a pump 2. The
manipulated variable is the exit flow rate rather
than an inlet flow rate.
25
The process and load transfer functions are given
by
The closed-loop transfer function for load changes
where, K4 -tI / KcKvKm
KOL KcKvKpKm , Kp - 1/A
26
  • The effect of tI

tI ? ?
?
? closed-loop responses less oscillatory
  • The effect of Kc

Kc ? ? z4 ? ? closed-loop responses less
oscillatory
  • The effect of Kc for the stable process except
    the integrating process

Kc ? ? closed-loop responses more oscillatory
Write a Comment
User Comments (0)
About PowerShow.com