Title: Foundations of Real Estate Management
1BOMA International
Foundations of Real Estate Management
TM
Module 3 Building Operations I Heating,
Ventilating, and Cooling the Building
2Objectives
- List the three components of the HVAC system
- List the three tasks of the ventilation system
- Explain why it is important to balance outside
air and exhaust air pressures, and tell what
happens in a commercial building if the pressures
are uneven - Trace the flow of air through the duct work
distribution system
3Objectives
- Describe how electric reheat coils in a VAV box
provide heat - Describe how baseboard heating systems provide
heat - Describe the refrigeration cycle
- Describe the chilled water cycle
- Describe the condenser water cycle
- List at least five methods to improve efficiency
of heating and cooling functions
4HVAC
Heating Ventilating Air Conditioning
5Ventilation
- Provides outside air
- Removes stale air
- Filters
6Ventilation
Photo courtesy of PM 101
Outside Air Damper
7Ventilation
Photo courtesy of Transwestern
Variable Frequency Drive
8Ventilation
Its a continuum No outside air
100 outside air Maximum energy efficiency
Minimum energy efficiency Minimum IAQ
Maximum IAQ
9Ventilation
Free cooling Using outside air to condition
the space
10Ventilation
Exhaust Removing odors and carbon
dioxide
11Ventilation
Separate exhaust for kitchens and restrooms
12Ventilation
Ensure restaurant tenants clean their exhaust
system regularly
13Ventilation
- Plenum Return
- Ducted Return
14Ventilation
- Partition Walls
- Demising Walls
- Fire Dampers
- Protection
15Ventilation
Photos courtesy of Transwestern
16Humidity
- ASHRAE recommends 50 relative
humidity (range of 30-60) - Dehumidification
- Humidification (rare)
17Pressure
The Goal Pressure In Pressure Out
18Pressure
- Over Pressurization
- More air is brought in than is exhausted
- Inoperable exhaust fan, incorrect VFD settings
- Front doors will not close properly
- People feel pressure (like on airplane)
- HVAC becomes inefficient
19Pressure
- Under Pressurization
- More air exhausted than brought in
- Inoperable outside air fan, incorrect VFD
settings - Front doors hard to open
- HVAC becomes inefficient
- Façade will leak
20Filtration
- Filters remove dust, debris, insects, and other
contaminants - Pleated filters v. fiberglass filters
- HEPA filters
- Charcoal filters for odors
- Changed routinely
21Air Distribution
- Air Handler
- Trunk Line
- Branch Line
- VAV Boxes/Terminal Units
- Supply Air Diffusers
22Air Distribution - Zoning
- Areas of the building operate differently from
one another - Zones determined by
- Function/Use
- Location
23Air Distribution
Air Handling Unit (AHU) or Air Handler
24Air Distribution
VAV Box controlled by a thermostat
25Air Distribution
Supply Air Diffuser
26Air Distribution
Trunk and Branch Ducts VAV Boxes and Supply Air
Diffusers
27Thermostat
- Types
- Pneumatic
- Direct Digital Control (DDC)
- Set point temperature
- Impossible to please everyone
- Location
28Thermostat
- ASHRAE-recommended set points
- 71o F for heating (68-75o F)
- 76o F for cooling (73-79o F)
- Balance tenant comfort with energy efficiency
29Thermal Layering
Heat Rises Top 1/3 is warmest
Temperature is measured in the middle 1/3 (On
top of the desk)
Bottom 1/3 is coolest (space heaters)
30Space Heaters
31Heating
32Heating
- Fuel Sources
- Electricity
- Natural Gas
- Heating Oil
33Heating
34Heating
- In most buildings, heating occurs only around
perimeter not in core - Air handler provides cooling to entire building
- Electric heaters in perimeter VAV boxes heat
perimeter as needed
35Heating
- Baseboard heating
- Electric
- Hot water or steam
- Under floor or sidewalk (radiant)
- Interlock
36Cooling
37Cooling
- Just 3 Loops
- Refrigerant Loop
- Chilled Water Loop
- Condenser Water Loop
- The loops do not mix!
38Cooling
- The Refrigeration Loop/Cycle
- Refrigerant
- Compressor
- Condenser
- Expansion Valve
39Cooling
- Refrigerant
- Fluid that absorbs heat
- Moves from liquid to gas (add heat) and back to
liquid (remove heat) easily - Boiling point is low 50-60o F
- Gas at room temperature
40Cooling
- Compressor
- Applies pressure
- Changes refrigerant from low pressure gas to a
high pressure, super-heated vapor
41Cooling
- Condenser
- Rejects heat outside building
- Either air cooled or water cooled
- Enters as a super-heated vapor
- Leaves as a high temperature, high pressure
liquid
42Cooling
- Expansion Valve
- Sprays liquid into a fine mist
- Reduces pressure and cools refrigerant
43Cooling
- Evaporator
- Transfers heat from building to refrigerant
- Heating the refrigerant causes it to boil
- Heated refrigerant then passes to compressor and
the cycle continues
44Cooling
- The refrigeration cycle is nothing more than
changing the refrigerant from a liquid to a gas
and back to a liquidover and over again - Its a closed loop system
45Cooling
46Cooling
Heat always moves from higher to lower
temperature
47Coils and Bundles
- Coils
- Transfer heat between air and refrigerant
- Bundles
- Transfer heat between liquid and refrigerant
48Coils and Bundles
Coils
49Coils and Bundles
Shell and Tube Bundles
50Moving Heat from Inside to Outside
- Chilled Water Loop
- Rejects heat from occupied spaces to the
refrigerant - Condenser Loop (air-cooled) or Condenser Water
Loop (water-cooled) - Rejects heat from the refrigerant to outside of
the building
51Cooling
- Chilled Water Loop
- Water treatment is critical
- Picks up heat in evaporator coil (in AHU) and
takes heat to refrigerant loop - Cooler chilled water returns to evaporator coil
to start process over again - As heat is removed, cooler air is blown through
duct system by the AHU
52Cooling
- Condenser Water Loop
(water-cooled) - Water treatment is critical
- Picks up heat in refrigerant
loop loop and takes heat to
heat to cooling tower
53Cooling
- Cooling Tower
- Condenser water pipes bathed in cool water
sprayed inside cooling tower. Large fans also
help transfer heat - Heat is transferred to outside
- Cooler condenser water is pumped back inside to
start cycle again
54Cooling
- Condenser Loop (air-cooled)
- Air is blown over refrigerant loop to reject
heat
55Cooling
- Water- or Air-Cooled Systems
- Chillers
- Self-Contained Units (SCUs)
- Air-Cooled Systems
- Rooftop Units (RTUs)
- Split System
- Heat Pump
56Cooling
Chiller
Photo courtesy of PM 101
57Cooling
Self-Contained Unit (SCU)
Photos courtesy of PM 101
58Cooling
Rooftop Unit (RTU)
Photo courtesy of Thomas J. Easley
59Cooling
Split System
Photo courtesy of Thomas J. Easley
60Cooling
Heat Pump
61Piped Systems
- Types
- 2 Pipe
- 4 Pipe
- Fan coil units
62Free Cooling
Rejecting heat without using the
compressor Flat plate heat exchanger
Photo courtesy of Transwestern
63Control Systems
- Building Automation System (BAS)
- Energy Management System (EMS)
64Controlling HVAC Costs
- Optimize EMS
- Use free cooling
- Pay attention to weather
- Coasting
- Check temperatures with hand-held thermostat
- Control tenant adjustment abilities
- Aggressive water treatment
- Keep all components clean