Training GXTMT Models - PowerPoint PPT Presentation

1 / 63
About This Presentation
Title:

Training GXTMT Models

Description:

Find Out the Problem by Debug Flow Chart. LED Display Explanation ... Cause: O/P load is larger than rated load in VA or in Wattage. ... – PowerPoint PPT presentation

Number of Views:70
Avg rating:3.0/5.0
Slides: 64
Provided by: PHOEN2
Category:

less

Transcript and Presenter's Notes

Title: Training GXTMT Models


1
Training - GXT-MT Models
  • By
  • V.Manoj Kumar

2
GXT-MT Models
3
OUTLINES
  • Introduction
  • Feature
  • Main specification
  • I/P
  • O/P
  • Overload Capacity
  • Battery charger
  • Environmental
  • Battery Run Time
  • Parallel Redundancy
  • Outside the UPS
  • Front Panel
  • Panel Display
  • Load/Battery Status Indicator
  • Rear Panel
  • Inside the UPS
  • PCBs Location
  • Main Structure
  • Selectable Parameter

4
OUTLINES
  • How to Maintain UPS
  • Take Care of Yourselves
  • Before Starting Service
  • Find Out the Problem by Debug Flow Chart
  • LED Display Explanation
  • Recover the Unit - Alignment Check

5
Feature
  • High frequency PWM technology
  • Intelligent ?-computer (CPU) inside
  • Double conversion design
  • Zero transfer time
  • Pure sine wave output
  • High input power factor(gt0.95)
  • Long back-up time with external battery packs (LB
    model )
  • 4/8 Amp Super charger(Long back-up models)

6
SpecificationInput
7
SpecificationOutput
8
Specification for Overload Capacity
  • 13KVA
  • 108 lt Load ? 150
  • Line Mode Switches to bypass after 30 sec and
    overload fault, alarm.
  • Battery Mode 30s then turn off output and alarm
  • Load gt 150
  • Line Mode Switches to bypass after 300ms and
    overload fault, alarm.
  • Battery Mode 300ms then turn off output and
    alarm
  • Short circuit
  • Immediate shutdown, alarm.

9
Specification for Overload Capacity (cont.)
  • 6 / 10 KVA
  • 105 ? Load lt 130
  • Line Mode 10mins, then transfer to Bypass and
    Alarm
  • Battery Mode 10 seconds then turn off output
    and alarm
  • Load ? 130
  • Line Mode 1 second, then transfer to Bypass and
    Turn Off Output after 1mins and Alarm
  • Battery Mode 1 seconds then turn off output and
    alarm

10
Specification forBattery Charger
11
Specification forEnvironmental
12
Battery Runtime-1K 1K(LB)
13
Battery Runtime-2K 2K(LB)
14
Battery Runtime-3K 3K(LB)
15
Battery Runtime-6K(LB)
16
Battery Runtime-10K(LB)
17
Parallel Redundancy
  • What is Parallel Redundancy?
  • For GXT 6/10KMT(LB) only !
  • Maximum Parallel Number 3 Units.
  • Refer to Parallel Installation SOP

18
Outside the UPSOutside Looking
6/10KVA
13KVA
19
Outside the UPSFront Panel
Status LED
Load / Battery Level LED
On / Mute switch
Off switch
20
Panel Display
Line mode
Bypass mode
Battery mode
21
Load/Battery Status Indicator
  • Line mode Load Indicator
  • Battery mode Battery Capacity Indicator

22
Outside the UPSRear Panel-1K 2K
1K 1K(LB)
2K 2K(LB)
23
Outside the UPSRear Panel-3K 6/10K
3K 3K(LB)
6K(LB)
10K(LB)
24
Inside the UPSPCBs Location-6/10K
Control board
PSDR
Input EMI board
25
Inside the UPSPCBs Location-6/10K
BUS capacity
Charger board
Output EMI board
Communication board
26
Inside the UPSDifference between Standard and
LB model13K
Standard Model Built-in 7Ah CSB batteries with 1A
standard charger
LB(Long Backup) Model No built-in battery with
4/8 Amp Super Charger
27
Inside the UPS Main StructureBlock Diagram of
1/2/3KVA
Note bypass mode
line mode battery
mode
28
Inside the UPS Main StructureBlock Diagram of
6/10KVA
29
Block Diagram
30
Block Diagram
31
PCB Assembly
32
(No Transcript)
33
Standard Back UP
34
Long Backup
35
GXT MT 6KVA
36
GXT MT 10KVA
37
GXT MT 10KVA 3Phase I/P
38
PFC Section
39
Inverter Section
40
DC/DC Booster
41
Charger Circuit
42
PCBs
Parallel card
Control Card
PSDR PCB
CHARGER PCB
43
Selectable Parameters
  • Selectable Inherent Manual Bypass Function
  • Selectable UPS Auto Restart When Power Return
  • Setting via the UPS monitoring software.
  • Selectable Output Voltage for 200/210/220/230/240
    Vac
  • Setting by Hyper terminal program in Windows.

44
How to Maintain Your UPS?
  • Guideline for UPS maintain.
  • Take Care of Yourselves
  • Before Starting Service
  • Find Out the Problem by Debug Flow Chart
  • LED Display Explanation
  • Recover the Unit - Alignment Check

45
How to Maintain Your UPS? Take Care of Yourselves
  • Something Keep in Mind
  • High voltage exists everywhere, BE CAREFUL !
  • Battery is extremely dangerous!!!
  • Before re-plug in the INPUT LINE POWER, make sure
    all power components have been checked.

46
How to Maintain Your UPS? Before Starting Service
  • Be careful of some symptoms
  • Environment and User Condition
  • Utility voltage/frequency Generator
  • Wiring
  • Load Type
  • Fault LED Indication
  • The UPS Situation Before Service

47
How to Maintain Your UPS?Before Starting Service
(Cont.)
  • What should we prepare?
  • At Least One Digital Multi Meter (DMM) 2 is
    ideal.
  • A Discharge High Power Resistor
  • Slotted and Phillips Screw Drivers
  • Service Manual
  • Good Spare PCB
  • What should we do?
  • Inspect It Carefully
  • Recording Failure Situation.
  • Disconnect UPS from Utility

48
How to Maintain Your UPS?Guess What Happened ?
49
How to Maintain Your UPS? Find Out the Problem
by Debug Flow Chart flow chart approach
50
Panel LED Display Explanation-1
  • Bypass Due to Over Temperature
  • Cause 1Ambient Temperature is higher than
    allowed operation temperature.
  • Strategy Reduce ambient temperature or O/P load.
  • Cause 2 Thermal detection circuit failed.
  • Strategy Refer to the thermal detection problem
    strategy. (Replace the CNTL)

51
Panel LED Display Explanation-2
  • Bypass Due to Inverter Failure
  • Cause 1 O/P short circuit. (In this situation,
    no power will be transfer to O/P socket.)
  • Strategy Remove short circuit condition, turn
    off the UPS then turn on again.
  • Cause 2 Inverter circuit failed.
  • Strategy Replace the PSDR.

52
Panel LED Display Explanation-3
  • Bypass Due to DC Bus Over-voltage
  • Cause 1 Some non-fatal misbehavior of UPS.
  • Strategy Turn off UPS then Turn it on.
  • Cause 2 PFC circuit fails.
  • Strategy Replace the PSDR.
  • Cause 3 DC/DC circuit fails. (In this situation,
    AC INPUT LED will not light)
  • Strategy Replace the PSDR
  • Cause 3 Bus voltage feedback circuit problem.
  • Strategy Replace the PSDR

53
Panel LED Display Explanation-4
  • Fault Due to Battery Over-Voltage
  • Cause Charger circuit fail
  • Strategy 1 Replace the Charger board.
  • Strategy 2 Replace the PSDR

54
Panel LED Display Explanation-5
  • Bypass Due to Output Overload
  • Cause O/P load is larger than rated load in VA
    or in Wattage.
  • Strategy Removed or reduce load connected to O/P
    socket. In line mode, the UPS will restart
    automatically. In battery mode, UPS must be OFF
    in advance and ON again.

55
How to Maintain Your UPS? Recover the Unit
Alignment Check
  • Check Charger and Power Supply Function
  • Disconnect the battery wires, connect DMM to
    Bat, Bat-.
  • Connect I/P power cord to utility then disconnect
    it ASAP.
  • The fan should start to rotate?
  • DMM reading should be a little less than expected
    voltage.
  • Panel LED should light then distinguish.

56
How to Maintain Your UPS? Recover the Unit
Alignment Check (Cont.)
  • Check DC/DC and CPU function
  • Connect DMM to BUS voltage test points, connect
    I/P to utility.
  • The BUS voltage should rise to 400V slowly
  • I/P relay contact
  • The BUS voltage will drop to about 325V slowly
  • Adjust charger voltage to expected value
  • Connect battery wires

57
How to Maintain Your UPS? Recover the Unit
Alignment Check (Cont.)
  • Check DC/DC and Inverter function
  • Disconnect I/P power cord from utility
  • After the fan stop rotating, press ON button
  • The BUS voltage will rise to 400V slowly
  • Inverter relay switch to INV mode
  • Check O/P voltage as expect.
  • Turn the UPS off

58
How to Maintain Your UPS? Recover the Unit
Alignment Check (Cont.)
  • Check PFC function
  • Connect I/P power cord to utility
  • Turn the UPS on, the BUS voltage will rise to
    380V slowly.
  • O/P relay switch to inverter, inverter LED lights.

59
How to Maintain Your UPS? Recover the Unit
Alignment Check (Cont.)
  • Be sure to check the
  • All VR are adjusted to expected value as service
    manual
  • All cables and screws are firmly locked
  • All air guides and accessories are recover to the
    original position
  • Line, neutral and GND wires are correctly
    connected.
  • Do not forget turning on UPS
  • Check the environment of operation

60
How to Maintain Your UPS? (Cont.)
  • Something Keep in Mind
  • High voltage exists everywhere, BE CAREFUL !
  • Battery is extremely dangerous
  • Before re-plug in the INPUT LINE POWER, make sure
    all power components have been checked.
  • FFC - Frequent Fail Components
  • DC/DC, PFC and INV power devices are most likely
    to fail.
  • PWM IC (power supply, charger, DC/DC, PFC)
  • Others

61
UPS Monitoring
AS400 Card
SNMP Card
62
GXT MT SNMP
63
The EndThank You