Module 05: Industrial Valve - PowerPoint PPT Presentation

1 / 46
About This Presentation
Title:

Module 05: Industrial Valve

Description:

Control valves, both manual and automatic, used to regulate flow. Selecting a Valve Type ... This requires troubleshooting skills on the part of the operator. ... – PowerPoint PPT presentation

Number of Views:1476
Avg rating:3.0/5.0
Slides: 47
Provided by: notesU
Category:

less

Transcript and Presenter's Notes

Title: Module 05: Industrial Valve


1
Module 05 Industrial Valve
2
1.0 Introduction
  • Fluid Any substance that flow from one area to
    another area when it subjected to a normal and
    shear stress. Gases and liquids are both
    considered fluids
  • Valve A mechanical device that is used in
    industrial piping to control the flow of fluids
  • On-Off Service Valve that only operate in the
    fully open or fully closed positions are said to
    provide on-off service

3
1.0 Introduction.
  • Throttling Service Valves that control flow by
    partially restricting the passage of the fluids
    provide in what is called throttling service.
  • Pressure Drop The loss of energy that occurs
    when a fluid encounters resistance passing
    through a valve. The greater resistance, the
    higher the pressure drop for a given flow rate. A
    higher pressure drop means that more energy in
    the form of pumping or compressing, must be used
    to move the fluid through the piping.

4
2.0 Valve Functions And Applications
  • Shut-off valves (block valves), whose purpose is
    to close off the flow
  • Control valves, both manual and automatic, used
    to regulate flow

5
Selecting a Valve Type
  • When speaking of valves, it's easy to get lost in
    the terminology.  Valve types are used to
    describe the mechanical characteristics and
    geometry (Ex/ gate, ball, globe valves).  We'll
    use valve control to refer to how the valve
    travel or stroke (openness) relates to the flow
  • Equal Percentage  equal increments of valve
    travel produce an equal percentage in flow
    change
  • Linear  valve travel is directly proportional to
    the valve stroke
  • Quick opening  large increase in flow with a
    small change in valve stroke

6
Equal Percentage (most commonly used valve
control)
  • Used in processes where large changes in pressure
    drop are expected
  • Used in processes where a small percentage of the
    total pressure drop is permitted by the valve
  • Used in temperature and pressure control loops

7
Linear
  • Used in liquid level or flow loops
  • Used in systems where the pressure drop across
    the valve is expected to remain fairly constant
    (ie. steady state systems)

8
Quick Opening
  • Used for frequent on-off service
  • Used for processes where "instantly" large flow
    is needed (ie. safety systems or cooling water
    systems)

9
Typical Industrial Valve
10
Gate Valve
11
Gate Valve
  • Best Suited Control  Quick Opening
  • Recommended Uses1.  Fully open/closed,
    non-throttling2.  Infrequent operation3. 
    Minimal fluid trapping in line
  • Applications  Oil, gas, air, slurries, heavy
    liquids, steam, noncondensing gases, and
    corrosive liquids

12
Gate Valve
  • Advantages
  • High capacity
  • Tight shutoff
  • Low cost
  • Little resistance to flow
  • Disadvantages
  • Poor control
  • Cavitate at low pressure drops
  • Cannot be used for throttling

13
Globe Valve
14
Globe Valve
  • Best Suited Control  Linear and Equal percentage
  • Recommended Uses1.  Throttling service/flow
    regulation2.  Frequent operation
  • Applications  Liquids, vapors, gases, corrosive
    substances, slurries

15
Globe Valve
  • Advantages
  • Efficient throttling
  • Accurate flow control
  • Available in multiple ports
  • Disadvantages
  • High pressure drop
  • More expensive than other valves

16
Ball Valve
17
Ball Valve
  • Best Suited Control Quick opening, linear
  • Recommended Uses1.  Fully open/closed,
    limited-throttling2.  Higher temperature fluids
  • Applications Most liquids, high temperatures,
    slurries

18
Ball Valve
  • Advantages
  • Low cost
  • High capacity
  • Low leakage and maintenance
  • Tight sealing with low torque 
  • Disadvantages
  • Poor throttling characteristics
  • Prone to cavitation

19
Butterfly Valve
20
Butterfly Valve
  • Best Suited Control  Linear, Equal percentage
  • Recommended Uses  1.  Fully open/closed or
    throttling services2.  Frequent operation3. 
    Minimal fluid trapping in line
  • Applications  Liquids, gases, slurries, liquids
    with suspended solids

21
Butterfly Valve
  • Advantages
  • Low cost and maintenance
  • High capacity
  • Good flow control
  • Low pressure drop
  • Disadvantages
  • High torque required for control
  • Prone to cavitation at lower flows

22
Plug Valve
23
Plug Valve
  • Best Suited Control  Quick Opening
  • The valve is positioned by turning a lever
  • A quarter turn of the handle will completely open
    or close a plug valve
  • Advantages When line of flow through a plug
    valve is straight, so when it is open there is
    very little turbulence and pressure drop

24
Diaphragm Valve
25
Diaphragm Valve
  • The stem of the valve is used to push down a
    flexible diaphragm, which in turn blocks the path
    of the fluid. There are two different
    classifications of diaphragm valve based on the
    geometry of the valve body
  • Weir type - A weir is cast into the body, and
    when closed, the diaphragm rests on the weir,
    restricting the flow
  • Straight-through type - The bore runs laterally
    through the body and a wedge shaped diaphragm is
    used to make the closure

26
Diaphragm Valve
  • Application
  • Suitable for handling aggressive fluids and for
    those containing suspended solids

27
Check Valve
28
Check Valve
  • Non-return valve
  • Application To avoid backflow

29
Valve Actuator, Operation And Troubleshooting
30
Valve Actuator, Operation And Troubleshooting
  • Control Valve A valve used in automatic control
    situations that is positioned by a controller.
    Any manual valve can be adapted into a control
    valve by attaching an actuator to the valve body.
  • Actuator A device that mechanically moves the
    stem of a control valve in response to a signal
    from a controller.
  • Controller An instrument that automatically
    positions a control valve. A controller uses the
    energy of compressed air, hydraulic fluid
    pressure, or electricity to send signals to an
    actuator.
  • Positioner A device that helps the actuator
    move the valve stem into the correct position.

31
Control Valve
32
Body Styles
  • Control valves can be designed to have one or two
    openings for fluid to pass through.
  • A valve that has one flow opening is called a
    single- ported valve.
  • Single-ported valves are often used because they
    are inexpensive, require little maintenance, and
    are resistance to leakage once closed.
  • The disadvantage of a single valve is that fluid
    pressure working against one side of the valve
    plug makes the valve difficult to position.

33
Body Styles
  • While in double-ported valve, there are two paths
    for fluid to flow through.
  • Because of its design, a double-ported valve can
    handle higher flow rates than a single-ported
    valve of the same size.
  • Since pressure is exerted somewhat evenly across
    the plugs, a double-ported valve is easier to
    position than a single-ported valve.
  • The characteristics of double-ported valves makes
    them especially good for throttling service

34
(No Transcript)
35
Pneumatic Actuator
  • The actuator contains a diaphragm and a spring.
    It receives compressed air or pneumatic signals
    from the controller.
  • A pneumatic actuator uses compressed air, or air
    pressure to move the stem of a control valve.
  • The compressed air is introduced above the
    diaphragm. The air pressure tries to push the
    diaphragm down. The spring tries to keep the
    diaphragm up.
  • When the air pressure against the top of the
    diaphragm exceeds the force of the spring, the
    valve stem is pushed downward and the valve
    closes.

36
Pneumatic Actuator
  • This type of valve is called an air-to-close
    valve. Increasing the air pressure above the
    diaphragm in an air-to-close valve causes the
    valve to close.
  • Some valves are air-to-open which is increasing
    the air pressure to this actuator causes the
    valve to open. Air pressure in this actuator
    builds up below the diaphragm.
  • The design of this valve makes it and air-to-open
    valve.
  • Hence, what is important for an operator to know
    is whether increasing air pressure opens or
    closes a valve. An operator also needs to know
    whether a valve fails in the open or closed
    position.

37
Electrical Actuator
  • Some actuators use the energy of electricity to
    position a control valve. A solenoid is an
    example of this type of actuator.
  • The solenoid consists of an iron core that slides
    in and out of wire coil.
  • When electrical current is sent through the coil,
    a strong magnetic field is set up inside it. This
    magnetic field pulls the iron core up into the
    coil. When the current stops, the magnetic field
    collapses. And, the core is pushed out of the
    coil by a spring.

38
Electrical Actuator
  • The iron core of the solenoid is attached to a
    valve stem. An electrical signal from the
    controller magnetizes the coil. This pulls the
    core up, and the valve is closed.
  • When the flow of current stops, the core is
    pushed out of the coil by the spring, and the
    valve opens.
  • Because of the way a solenoid actuator positions
    a valve, it can only be used for on-off service.

39
Solenoid Valve
40
Introduction to Control Valve
Control Valves Device that manipulates a
flowing fluids, such as gas, steam, water, or
chemical compound, to compensate for the load
disturbance and keep the regulate
process variables as close as possible to the
desired set point
41
Control Valve Actuator Nomenclature
  • Fail Open, FO or Air To Close, ATC
  • A condition wherein the valve port remains open
    in the event of
  • loss of actuator loading pressure to the
    diaphragm
  • - No air/pneumatic, Valve in Open condition
  • - 4 mA Fully Open, 20 mA Fully Closed
  • Fail Closed, FC or Air To Open, ATO
  • The condition wherein the valve port remains
    closed in the event
  • of loss of actuator loading pressure to the
    diaphragm
  • - No air/pneumatic, Valve in Closed condition
  • - 4 mA Fully Closed, 20 mA Fully Open

42
Control Valve Actuator Nomenclature
1.0 Valve Positioner / Pneumatic Positioner
- The primary function is to ensure that the
control valve stem position is directly
proportional to the respective value of
instrument o/p pressure, regardless of stuffing
box friction, spring hysteresis or off balance
forces on the valve plug - Positioners also
provide a convenient means of changing the
effective o/p pressure range of the controller
and also of changing the valve action 2.0
Actuator Spring - A spring, enclosed in the
yoke, to move the actuator stem in a direction
opposite to that created by diaphragm
pressure 3.0 Actuator Stem - A rod-like
extension of the diaphragm plate to permit
convenient connection to valve plug stem 4.0
Diaphragm - A flexible pressure responsive
element which transmits force to the diaphragm
plate and actuator stem 5.0 Direct Acting
Actuator (ATC) - An actuator in which the
actuators stems extends with increasing diaphragm
force 6.0 Dynamic Force - a force produced
by the fluid pressure on control valve components
while valve is throttling
43
Control Valve Actuator Nomenclature
7.0 Fail Closed - A condition
wherein the valve port remains closed in the
event of loss of actuator loading pressure to
the diaphragm 8.0 Fail Open - A
condition wherein the valve port remains open in
the event of loss of actuator loading pressure to
the diaphragm 9.0 PDTC - Push Down
To Close, referring to the motion required to
seat the closure member of a control valve 10.0
PDTO - Push Down To Open, referring to the
motion required to fully open the closure member
of a control valve 11.0 Reverse Acting Actuator
(ATO) - An actuator construction in which
the actuator stem retracts with increasing
diaphragm pressure 12.0 Seat Load - The
total amount of system force, in pounds, that is
exerted against a fully closed control valve plug
or closure member 13.0 Spring Rate
(K) - The measurement of a spring to
determine its stiffness. Defined as the amount of
force in LBs. required to compress the
spring one inch 14.0 Stiffness - The
ability of the actuator to freeze the valve plug
in a desired position. A function of spring rate
44
Troubleshooting
  • Although an operator is not usually responsible
    for repairing valves, he should be able to
    identify problems so that the appropriate
    maintenance or instrument personnel can be called
    in.
  • This requires troubleshooting skills on the part
    of the operator. The problems that occur in
    manually-operated valves are often easy to
    detect, such as a broken hand wheel or stripped
    screw threads.
  • If the operating mechanism is working properly,
    but the valve still wont open or close, you can
    assume the problem is inside the valve.

45
Troubleshooting
  • Check valves do not have an external operating
    mechanism. So, when a check valve is not
    preventing a reversal of flow, you know the
    problem is inside the valve body.
  • Control valves are usually more difficult to
    troubleshoot because more things can go wrong
    with them. If a control valve fails, your first
    action should be check the controllers signal to
    the actuator or valve.
  • If the signal is incorrect, you know the failure
    is being caused by the controller.

46
Troubleshooting
  • Sometimes the signals from the controller to the
    actuator are disrupted by a leak, blockage, or
    short in the line that connects these two
    components. So, a control valve failure can also
    be caused by a problem in the signal transmission
    system. Most control valves are equipped with
    some type of valve position indicator.
  • Another possibility is that the actuator is not
    working properly. If the diaphragm in a pneumatic
    actuator is torn or ruptured, it will not respond
    to changes in air pressure.
  • A burned out coil or motor will cause an
    electrical actuator to malfunction.
Write a Comment
User Comments (0)
About PowerShow.com