Title: Industrial Control Panel
1Industrial Control Panel Short-Circuit Current
Rating
2Industrial Control Panel Definition
- 2008 NEC 409.2
- An assembly of two or more components consisting
of one of the following - Power circuit components only
- Control circuit components only
- Combination of power and control circuits
- These components, with associated wiring and
terminals, are mounted on or contained within an
enclosure or mounted on a subpanel. - The industrial control panel does not include the
controlled equipment.
3Short-Circuit Current Rating Definition
- 2008 NEC Article 100 UL 508A Definition
- The prospective symmetrical fault current at a
nominal voltage to which an apparatus or system
is able to be connected without sustaining damage
exceeding defined acceptance criteria.
4SCCR Marking Requirements
- 2005 NEC or Later
- 430.8 Marked on motor controllers.
- 440.4(B) Marked on HVAC equipment.
- 409.110 Marked on industrial control panels
- SCCR not required for panels that contain only
control circuit components. - 670.3 Marked on industrial machinery control
panel. - UL 508A, Supplement SB is an approved method to
determine SCCR for industrial control panels.
5SCCR Marking Requirements
- UL 508A Shops
- Comply with UL 508A the standard for industrial
control panels - Requires all industrial control panels listed and
marked to UL 508A to be marked with the
short-circuit current rating. - Includes requirements for specific use panels
such as industrial machinery, service equipment,
elevator control, HVAC, etc.
6How to Determine SCCR
- Short-Circuit Current Rating
- Can be established by testing during the listing
and labeling process - OR
- Can be determined using an approved (calculation)
method - UL 508A Supplement SB is an approved method
- UL field evaluation can also be used.
7How to Determine SCCR
- For a detailed presentation on SCCR and how to
determine SCCR based on UL 508A Supplement SB,
request quote for four hour training from your
Cooper Bussmann representative (Part
CBTR-SCCR-4HP). - The following slides only highlight the UL 508A
Supplement SB method.
8UL 508A Supplement SB
- What Needs to be Analyzed?
- All power circuit components (SB 4.1)
- Feeder and branch circuit components that supply
power to loads (motors, lighting, heating and
appliances) - Includes disconnect switches, fuses, circuit
breakers, load controllers, overload relays,
power distribution/terminal blocks, bus bars,
etc. - Control circuit components are not required to be
analyzed - Pushbuttons, pilot lights, selector switches,
timers, control relays, etc.
9UL 508A Supplement SB
- How to Determine Component SCCR (SB4.2.2)?
- The SCCR marked on the component or on
instructions. - The SCCR determined by the voltage rating of the
component and the assumed short circuit current
from Table SB4.1. - or
- The SCCR for a load controller, motor overload
relay, or combination motor controller that has
been investigated in accordance with the
performance requirements, including short circuit
test requirements for standard fault currents or
high fault currents specified in the Standard for
Industrial Control Equipment, UL 508, and
described in the manufacturers procedure.
10UL 508A Supplement SB
- What are the Rules?
- Lowest component SCCR limits assembly SCCR
unless - Combination ratings can be used to increase
branch circuit component ratings (SB 4.2.2) - Component with marked/specified OCPD
- Check with component manufacturer for combination
ratings - Feeder components are used that limit the
short-circuit current reducing the need for
higher branch circuit component SCCR (SB 4.3) - Current limiting overcurrent protective devices
- Transformers rated 10kVA or less
11Component Combination Ratings
Component SCCR
OCPD I.R.
- Branch component limiting assembly rating
12Component Combination Ratings
Component SCCR
OCPD I.R.
- Use combination ratings with specified/marked
OCPD to fix low rated branch components
Combination ratings of overcurrent protective
devices and components can be used
13Component Combination Ratings
Component SCCR
OCPD I.R.
- Feeder Component Limiting Assembly Rating
14Component Combination Ratings
Component SCCR
OCPD I.R.
- Use UL Listed power distribution block with high
SCCR when used with marked or specified current
limiting fuses
Combination ratings of PDBs is cost effective fix
15Current Limitation - OCPD
Component SCCR
OCPD I.R.
- Branch components limiting assembly rating
16Current Limitation - OCPD
Component SCCR
OCPD I.R.
- Current limiting feeder OCPD can be used that
limits the short-circuit current below 10kA
Current limitation is cost effective fix
Note To learn how to use feeder let-through -
request Lunch Learn
17Current Limitation - Transformer
Component SCCR
OCPD I.R.
10 kVA
- Transformers can be used to limit the
short-circuit current available
Current limitation is cost effective fix
18Current Limitation Transformer
Component SCCR
OCPD I.R.
10 kVA
- Transformers can be used to
- limit the short-circuit current available
- If 10kVA sec comp 5kA
- If 5kVA/120V sec comp 2kA
- Then assign entire circuit I.R. of primary
overcurrent device
Current limitation is cost effective fix
19UL 508A Supplement SB
- What are the Rules?
- Lowest overcurrent protective device interrupting
rating (or SCCR for some devices) always limits
assembly SCCR - See SB 4.3.2 and 4.3.3
- Tested series combination ratings or series
ratings (fuse-circuit breaker or circuit
breaker-circuit breaker) are also NOT allowed.
See NEC also 240.86(B).
20Interrupting Rating
Component SCCR
OCPD I.R.
- Limited by interrupting rating of OCPD in the
branch
Interrupting rating directly affects assembly
rating
21Interrupting Rating
Component SCCR
OCPD I.R.
- Only fix is to increase interrupting rating
Series ratings of OCPDs are NOT allowed
22Interrupting Rating
Component SCCR
OCPD I.R.
- Limited by interrupting rating of OCPD in the
feeder
Interrupting rating directly affects assembly
rating in all locations
23Two Sweep Method
24Two Sweep Method
- Sweep 1 Verify Component Short-Circuit Current
Ratings - Determine lowest branch and feeder power circuit
component SCCR - Check with component manufacturer for combination
ratings - Use current limiting overcurrent protective
devices or transformers in feeder circuit to
increase downstream branch circuit components
with low SCCR. - Determine assembly SCCR.
- Sweep 2 Modify Assembly SCCR Based on Lowest
Interrupting Rating of Overcurrent Protective
Devices
25SCCR Design Considerations
- Proper Component Use and Limitations
- SCCR and IR
- Combination Ratings
- Voltage limitations (slash ratings)
- Functionality
- Fundamentals of Assembly Calculations (UL 508A
Supplement SB)
26SCCR Design Considerations
- Other Considerations
- Customer requirements
- Fault Current Levels
- Flexibility of application
- Multiple installations
- Fault current unknown
- Insufficient SCCR can delay installation
27SCCR Compliance
- Ensure equipment Is
- Labeled with SCCR per NEC requirements
- SCCR is sufficient for installation
- Fault current calculations/documentation
- Higher rated panels less concern
- System or location changes
- Adequate for system voltage and grounding type
28SCCR Compliance
Isca 12,000A
Motor Controller SCCR 15kA
X
Available Short-Circuit Current (Isca)
54,000A
Isca 28,000A
Industrial Control Panel SCCR 30kA
X
X
Isca 31,000A
X
Industrial Machinery Panel SCCR 35kA
HVAC SCCR 40kA
Isca 38,000A
X
29Solutions fromCooper Bussmann
30Code Change Document
- Code Change Update
- Provides background information on NEC changes
including SCCR
Available at www.cooperbussmann.com
31Simplified Guide to SCCR
- Provides Overview
- SCCR.
- Typical supply, feeder and branch components and
default ratings (in easy to use interactive
chart). - Find-It, Fix-It, Forget-It.
Available at www.cooperbussmann.com
32Selecting Protective Devices (SPD)
- Industrial Control Panels SCCR
- Overview of SCCR.
- Detailed example of Two Sweep analysis method
per UL 508A. - FixIt solutions.
Available at www.cooperbussmann.com
33Software Programs
- Short-circuit Calculator Program
- Single- or three-phase.
- Transformer calculation.
- Conductor/bus calculation.
- FREE.
- OSCAR SCCR Calculator
- Assembly SCCR calculator.
- Database of 55,000 parts.
- Select devices and calculate.
- Version 2.0 available now.
34Cooper Bussmann OSCAR 2.0
New layout
35Cooper Bussmann OSCAR 2.0
Easier part search
36Cooper Bussmann OSCAR 2.0
Identify weak link
37Cooper Bussmann OSCAR 2.0
New report
38Cooper Bussmann OSCAR 2.0
- Available from Cooper Bussmann Website for
Purchase - 299.99 per year.
- Free 7-day trial available.
Contact your local Cooper Bussmann sales
representative for further details
39Find It - Common Weak Links
- Supplemental Protectors
- If unmarked 200A, often 5-10kA with slash
ratings (480/277V). - Standard Circuit Breakers and Class H Fuses
- If standard CB 10-14kA.
- Class H fuses 10kA.
- Motor Controllers
- If no combination ratings available 5kA SCCR.
- Power Distribution Blocks
- If unmarked/untested 10kA SCCR.
40Fix It - Solutions
- High I.R. Protective Devices
41Fix It - Solutions
42Fix It - Solutions
- Compact Circuit Protector (CCP)
- 200kA SCCR.
- 600V.
- 30A with Class CC fuses.
- 30A or 60A with CUBEFuse.
- Smallest fusible disconnect available.
- Finger-safe design.
- UL 98 branch circuit disconnect.
43Fix It - Solutions
- CCP
- Relative size comparison with similar devices
UL 489 600V
Circuit Breaker
UL 489 480/277V Circuit Breaker
UL 98 600V Cooper Bussmann CCP
UL 489 240V Circuit Breaker
UL1077 480/277V Supplementary Protector
Small value for the OEM customer
3 pole rating
44Fix It - Solutions
- Type 2 Ratings (SPD)
- Combination Ratings (UL Website)
- Procedure Described
Cooper Bussmann LPJ-60SP IR 300kA
A30 contactor SCCR 5kA
TA25DU32 overload SCCR 5kA
Type 2 ratings or http//www.ul.com/controlequipme
nt/shortcircuit.html
45Fix It - Solutions
- Power Distribution Blocks
- High SCCR.
- Larger spacings.
- UL Listed.
46Forget It - Solution
Benefits of Cooper Bussmann Solutions Example
Industrial Machinery Control Panel Label
47Questions?Comments?