Transient Stability, Harmonics - PowerPoint PPT Presentation

1 / 33
About This Presentation
Title:

Transient Stability, Harmonics

Description:

One new note sheet, and your two old note sheets are allowed. ... Then a balanced three phase fault occurs at the terminal of one of the lines. ... – PowerPoint PPT presentation

Number of Views:111
Avg rating:3.0/5.0
Slides: 34
Provided by: ecepubli
Category:

less

Transcript and Presenter's Notes

Title: Transient Stability, Harmonics


1
ECE 476POWER SYSTEM ANALYSIS
  • Lecture 25
  • Transient Stability, Harmonics
  • Professor Tom Overbye
  • Department of Electrical andComputer Engineering

2
Announcements
  • Be reading Chapter 13.
  • HW 11 is not turned in but should be done before
    final. HW 11 is 13.1, 13.7, 13.8, 13.18, and the
    special problem (see website for complete
    assignment)
  • Final is Tuesday Dec 16 from 7 to 10pm in EL 165
    (web it now correct). Final is comprehensive.
    One new note sheet, and your two old note sheets
    are allowed.
  • Special Office Hours Dec 15 from 1 to 3pm

3
Generator Electrical Model
  • The simplest generator model, known as the
    classical model, treats the generator as a
    voltage source behind the direct-axis transient
    reactance the voltage magnitude is fixed, but
    its angle changes according to the mechanical
    dynamics

4
Generator Mechanical Model
Generator Mechanical Block Diagram
5
Generator Swing Equation
6
Single Machine Infinite Bus (SMIB)
  • To understand the transient stability problem
    well first consider the case of a single machine
    (generator) connected to a power system bus with
    a fixed voltage magnitude and angle (known as an
    infinite bus) through a transmission line with
    impedance jXL

7
SMIB, contd
8
SMIB Equilibrium Points
9
Transient Stability Analysis
  • For transient stability analysis we need to
    consider three systems
  • Prefault - before the fault occurs the system is
    assumed to be at an equilibrium point
  • Faulted - the fault changes the system equations,
    moving the system away from its equilibrium point
  • Postfault - after fault is cleared the system
    hopefully returns to a new operating point

10
SMIB Example
  • Assume a generator is supplying power to an
    infinite bus through two parallel transmission
    lines. Then a balanced three phase fault occurs
    at the terminal of one of the lines. The fault
    is cleared by the opening of this lines circuit
    breakers.

11
SMIB Example, contd
Simplified prefault system
12
SMIB Example, Faulted System
During the fault the system changes
The equivalent system during the fault is then
During this fault no power can be
transferred from the generator to the system
13
SMIB Example, Post Fault System
After the fault the system again changes
The equivalent system after the fault is then
14
SMIB Example, Dynamics
15
Transient Stability Solution Methods
  • There are two methods for solving the transient
    stability problem
  • Numerical integration
  • this is by far the most common technique,
    particularly for large systems during the fault
    and after the fault the power system differential
    equations are solved using numerical methods
  • Direct or energy methods for a two bus system
    this method is known as the equal area criteria
  • mostly used to provide an intuitive insight into
    the transient stability problem

16
Examples
17
Transient Stability Example
  • A 60 Hz generator is supplying 550 MW to an
    infinite bus (with 1.0 per unit voltage) through
    two parallel transmission lines. Determine
    initial angle change for a fault midway down one
    of the lines.H 20 seconds, D 0.1. Use
    Dt0.01 second.

Ea
18
Transient Stability Example, cont'd
19
Transient Stability Example, cont'd
20
Transient Stability Example, cont'd
21
Transient Stability Example, cont'd
22
Equal Area Criteria
  • The goal of the equal area criteria is to try to
    determine whether a system is stable or not
    without having to completely integrate the system
    response.

System will be stable after the fault if the
DecelArea is greater than the Accel. Area
23
Example 13.4 Undamped
24
Example 13.4 Damped (d12)
25
Example 13.4 Damped, tclear 0.1
26
Example 13.9 Angles
27
Example 13.9 Frequency
28
Eastern Interconnect Actual Freq
29
Power System Harmonics
  • So far class has talked about fundamental
    frequency analysis. Many traditional loads only
    consume power at the fundamental frequency.
    However, some loads, mostly electronic-based,
    tend to draw current in non-linear pulses, which
    gives rise to harmonics.
  • If current has half-wave-symmetry (values are
    equal and opposite when separated by T/2) then
    there are no even harmonics

30
Switched-Mode Power Supply Current
Source www.utterpower.com/commercial_grid.htm
31
Quick Review of Fourier Analysis
.
32
Harmonic Current Specturm
  • The below figure shows the harmonic current
    components for an 18-W, electronic-ballast
    compact fluorescent lamp.

Source Fig 2.34 of Renewable and Efficient
Electric Power Systems by Masters
33
Key Problems with Harmonics
  • A key problem with the third harmonic is neutral
    current since the fundamental 120 degree phase
    shift becomes 360 degrees for the third harmonic
    so the third harmonic values do not cancel (also
    true for other triplen harmonics)
  • Delta-grounded wye transformers prevent triplen
    harmonic currents from flowing into the power
    grid
  • Harmonics cause transformer overheating since
    core losses are proportional to frequency
  • Harmonic resonance, particularly with shunt
    capacitors (can be around 5th or 7th harmonic
    values)
Write a Comment
User Comments (0)
About PowerShow.com