Title: Transient Stability, Harmonics
1ECE 476POWER SYSTEM ANALYSIS
- Lecture 25
- Transient Stability, Harmonics
- Professor Tom Overbye
- Department of Electrical andComputer Engineering
2Announcements
- Be reading Chapter 13.
- HW 11 is not turned in but should be done before
final. HW 11 is 13.1, 13.7, 13.8, 13.18, and the
special problem (see website for complete
assignment) - Final is Tuesday Dec 16 from 7 to 10pm in EL 165
(web it now correct). Final is comprehensive.
One new note sheet, and your two old note sheets
are allowed. - Special Office Hours Dec 15 from 1 to 3pm
3Generator Electrical Model
- The simplest generator model, known as the
classical model, treats the generator as a
voltage source behind the direct-axis transient
reactance the voltage magnitude is fixed, but
its angle changes according to the mechanical
dynamics
4Generator Mechanical Model
Generator Mechanical Block Diagram
5Generator Swing Equation
6Single Machine Infinite Bus (SMIB)
- To understand the transient stability problem
well first consider the case of a single machine
(generator) connected to a power system bus with
a fixed voltage magnitude and angle (known as an
infinite bus) through a transmission line with
impedance jXL
7SMIB, contd
8SMIB Equilibrium Points
9Transient Stability Analysis
- For transient stability analysis we need to
consider three systems - Prefault - before the fault occurs the system is
assumed to be at an equilibrium point - Faulted - the fault changes the system equations,
moving the system away from its equilibrium point - Postfault - after fault is cleared the system
hopefully returns to a new operating point
10SMIB Example
- Assume a generator is supplying power to an
infinite bus through two parallel transmission
lines. Then a balanced three phase fault occurs
at the terminal of one of the lines. The fault
is cleared by the opening of this lines circuit
breakers.
11SMIB Example, contd
Simplified prefault system
12SMIB Example, Faulted System
During the fault the system changes
The equivalent system during the fault is then
During this fault no power can be
transferred from the generator to the system
13SMIB Example, Post Fault System
After the fault the system again changes
The equivalent system after the fault is then
14SMIB Example, Dynamics
15Transient Stability Solution Methods
- There are two methods for solving the transient
stability problem - Numerical integration
- this is by far the most common technique,
particularly for large systems during the fault
and after the fault the power system differential
equations are solved using numerical methods - Direct or energy methods for a two bus system
this method is known as the equal area criteria - mostly used to provide an intuitive insight into
the transient stability problem
16Examples
17Transient Stability Example
- A 60 Hz generator is supplying 550 MW to an
infinite bus (with 1.0 per unit voltage) through
two parallel transmission lines. Determine
initial angle change for a fault midway down one
of the lines.H 20 seconds, D 0.1. Use
Dt0.01 second.
Ea
18Transient Stability Example, cont'd
19Transient Stability Example, cont'd
20Transient Stability Example, cont'd
21Transient Stability Example, cont'd
22Equal Area Criteria
- The goal of the equal area criteria is to try to
determine whether a system is stable or not
without having to completely integrate the system
response.
System will be stable after the fault if the
DecelArea is greater than the Accel. Area
23Example 13.4 Undamped
24Example 13.4 Damped (d12)
25Example 13.4 Damped, tclear 0.1
26Example 13.9 Angles
27Example 13.9 Frequency
28Eastern Interconnect Actual Freq
29Power System Harmonics
- So far class has talked about fundamental
frequency analysis. Many traditional loads only
consume power at the fundamental frequency.
However, some loads, mostly electronic-based,
tend to draw current in non-linear pulses, which
gives rise to harmonics. - If current has half-wave-symmetry (values are
equal and opposite when separated by T/2) then
there are no even harmonics
30Switched-Mode Power Supply Current
Source www.utterpower.com/commercial_grid.htm
31Quick Review of Fourier Analysis
.
32Harmonic Current Specturm
- The below figure shows the harmonic current
components for an 18-W, electronic-ballast
compact fluorescent lamp.
Source Fig 2.34 of Renewable and Efficient
Electric Power Systems by Masters
33Key Problems with Harmonics
- A key problem with the third harmonic is neutral
current since the fundamental 120 degree phase
shift becomes 360 degrees for the third harmonic
so the third harmonic values do not cancel (also
true for other triplen harmonics) - Delta-grounded wye transformers prevent triplen
harmonic currents from flowing into the power
grid - Harmonics cause transformer overheating since
core losses are proportional to frequency - Harmonic resonance, particularly with shunt
capacitors (can be around 5th or 7th harmonic
values)