Title: Danish Institute of Fire and Security Technology Sprinkler Research


1
Danish Institute of Fire and Security Technology
Sprinkler Research Glass ConstructionAnders
Drustrup
  • 7th International Fire Sprinkler Conference
    Exhibition
  • 2008 Copenhagen, Denmark

2
Purpose with test
Replace a standard passive fire protective
system with a combined active and passive system.
Passive system Glazed partition (3200 mm x
2035mm) Aluminium frame with Intermediate
mullion Tempered glass Active system Window
sprinkler k-factor 80 LPM/bar½ (5.6
GPM/psi½) Quick response bulb 68 Required
Classification EI 60, Integrity 60
minutes Insulation 60 minutes According to EN
1364-1 (ISO 834, temperature curve)
DEKO Glazed partition
EN 1364-1 Fire resistance tests for
non-loadbearing elements Part 1 Walls
3
Motivation
Reduced building costs for 60 minutes
partition Partition with fire resistant
glass 1300 1600 Partition with tempered
glass including sprinkling 450 - 530 Reduction
approx. 65 Reduced self-weight 25 mm fire
resistant glass 65 kg/m2 6 mm 8 mm tempered
glass 35 kg/m2 Reduction approx. 45
4
Test Setup

Furnace specifications 22 Gas burners 215 kW per
burner Total capacity approx. 4700 kW
5
Test results
6
Test results after 62 minutes
  • Measured temperature rise on unexposed side
  • All temperatures on glass and frame below 140 C
  • All temperature curves showed a tendency to level
    out
  • Radiation from test specimen
  • Radiation was approx. 1.1 kW/m2 at test stop
  • Deflection of test specimen
  • Measured deflection of between 2 mm

DEKO Glazed partition
7
Test Summary
  • Integrity and Insulation criteria fulfilled
  • Insignificant radiation from test specimen
  • Insignificant deflection of test specimen,
    indicating low temperature gradient in test
    specimen
  • Dry spots around centre post observed
  • Fracture of glass after test stop
  • (during the cooling phase).

DEKO Glazed partition
8
Critical parametersinfluencing the stress in the
glazing
  • Passive system
  • Type of glass,
  • Edge handling
  • Size of glass
  • Blocking up of the glass
  • Fixation of glass in frame
  • Active system
  • Response time
  • Spray pattern
  • Water flow
  • The formation of dry spots during the test
  • Position of mullions

9
Needs for the future
  • Standardised methods for combined systems
  • A standard to evaluate the critical parameters of
    the active and passive system
  • with rules for field of application of test
    results, to be used in the
  • following FSE calculations.
  • Possible technical committees in CEN to the
    undertake the work
  • CEN/TC 127 Fire safety in building
  • CEN/TC 191 Fixed fire fighting systems
  • Suggestions
  • Prescribed fire exposure scenarios for the period
    up to activation of the active system (passive
    system only).
  • Verification of the passive systems ability to
    withstand the fire exposure until the active
    system responds.
  • Verification of the passive systems ability to
    withstand the thermal shock originating from the
    water cooling the passive system immediately
    after the active system respond.
  • Verification of that the combined systems ability
    to withstand the long term fire exposure after
    the active system respond.