MLC Connectivity to SLC 500 via DeviceNet - PowerPoint PPT Presentation

About This Presentation
Title:

MLC Connectivity to SLC 500 via DeviceNet

Description:

Intended for devices transmitting small blocks of information ... Insert one Normally Closed Contact and Two Copy Instructions into Rung 1 ... – PowerPoint PPT presentation

Number of Views:157
Avg rating:3.0/5.0
Slides: 37
Provided by: jbl59
Category:

less

Transcript and Presenter's Notes

Title: MLC Connectivity to SLC 500 via DeviceNet


1
MLC Connectivity to SLC 500 via DeviceNet
2
Equipment Needed for Connecting
  • MLC 9000 BCM
  • Allen-Bradley SLC 500 CPU 5/02 or higher
  • 5/02 smallest CPU to support M0/M1 File Transfer
  • Allen-Bradley 1747-SDN DeviceNet Scanner
  • Allen-Bradley RSNetworx or DeviceNet Manager
    Software
  • RSLogix PLC Programming Software
  • PC Interface(i.e 1770-KFD for programming)
  • DeviceNet Cabling
  • Thick Trunk Cable with Mini-Connectors
  • Thin Drop Cable with Micro or Mini-Connectors
  • T-Connectors
  • Terminating connectors(110 Ohms)

3
How SLC500 Communicates with 1747-SDN
  • Two methods used
  • I/O Transfer
  • 1747 occupies 32 Input Words and 32 Output Words
  • 1 word of input, 1 word of output used for module
    status and command
  • 62 words available for devices
  • Intended for devices transmitting small blocks of
    information
  • Proximity and Photoelectric Switches
  • Slice I/O
  • Valves

4
How SLC 500 Communicates with 1747-SDN
  • Block Transfer via M0/M1 Files
  • M1 File
  • 150 Words Available for Input from Network
    Devices (M11.0-M11.149)
  • 74 Diagnostic Words (M11.150-M11.223)
  • 32 Words for Inbound Explicit Message Control
    (M11.224-M11.255)

5
How SLC 500 Communicates to 1747-SDN
  • Block Transfer via M0/M1 Files
  • M0 File
  • 150 Words of data used for output to network
    devices (M01.0-M01.149)
  • 74 Words Reserved/Unused (M01.150-M01.223)
  • 32 Words used for outgoing explicit message
    control (M01.224-M01.255)

6
How MLC 9000 Communicates with 1747-SDN
  • MLC 9000 Gateway
  • Converts DeviceNet Messages from Scanner into
    Modbus Messages to Bus Control Module
  • Uses Polled Messaging for Implicit I/O Connection
  • One Loop Control Module takes up 16 Bytes of
    Input and 6 Bytes of Output
  • Uses Explicit Messaging to gain access to
    parameters not supported through implicit
    connection

7
Implicit I/O Connection Data
8
Setting Up PC to Communicate via DeviceNet
In RSLinx, Select Communications and Configure
driver
9
Setting Up PC to Communicate via DeviceNet
Under Available Driver Types, select DeviceNet
Drivers and select Add new
10
Setting Up PC to Communicate via DeviceNet
Select 1747-SDNPT
11
Setting Up PC to Communicate via DeviceNet
Select Processor to Connect to and slot where
1747-SDN resides
12
Setting Up PC to Communicate via DeviceNet
1747-SDNPT-1 should be seen running
13
Setting Up SLC500 to Pull Information from
1747-SDN
Start RSLogix and Select File-New
14
Setting Up SLC500 to Pull Information from
1747-SDN
Select processor from list
15
Setting Up SLC500 to Pull Information from
1747-SDN
From Menu Tree, Select IO Configuration then add
1747-SDN into Slot 1 of Rack
16
Setting Up SLC500 to Pull Information from
1747-SDN
Highlight on Rung in Ladder Window
17
Setting Up SLC500 to Pull Information from
1747-SDN
  • Insert one Normally Closed Contact and Two Copy
    Instructions into Rung 1
  • Copy Instructions move data from M0/M1 Files to
    usable data areas

18
Setting Up SLC500 to Pull Information from
1747-SDN
  • Last Rung Energizes Output Run coil and disables
    in event of error in module
  • Download to PLC and place in Run Mode

19
Configuring the DeviceNet Network
  • To Configure Network, Gateway EDS file must be
    installed
  • EDS (Electronic Data Sheet) carries configuration
    properties for DeviceNet products
  • Start RSNetworx then select Tools-EDS Wizard

20
Configuring the DeviceNet Network
Select Register EDS File then select Choose File
21
Configuring the DeviceNet Network
  • Select A Drive then select West0456
  • Click Open

22
Configuring the DeviceNet Network
Wizard will run test on EDS
23
Configuring the DeviceNet Network
Wizard will prompt you to associate a graphic
icon with EDS
24
Configuring the DeviceNet Network
This will finish the EDS Installation
25
Configuring the DeviceNet Network
Select 1747-SDN from Device List
26
Configuring the DeviceNet Network
Insert MLC 9000 Gateway form Device List
27
Configuring the DeviceNet Network
Double Click on 1747-SDN and select Scanlist
28
Configuring the DeviceNet Network
  • Click on arrow to add Gateway to 1747-SDNs
    scanlist
  • Select edit I/O parameters

29
Configuring the DeviceNet Network
  • Adjust the Polled Rx and Tx parameters to match
    the number of I/O taken up by LCMs
  • 16 bytes of Rx and 6 bytes Tx for every LCM (up
    to 8 LCMs)

30
Configuring the DeviceNet Network
  • Select Input
  • Select Memory Type M file
  • Select AutoMap

31
Configuring the DeviceNet Network
  • Select Output
  • Select Memory Type M file
  • Select AutoMap

32
Configuring the DeviceNet Network
  • From Main Screen, select Tools then Node
    Commissioning
  • Nodes must be commissioned with proper baud rate
    and node address before the configuration can be
    downloaded to network
  • Select Browse

33
Configuring the DeviceNet Network
  • Select 1747-SDNPT from list of drivers
  • RSNetworx will detect connected devices
  • Select Node to adjust

34
Configuring the DeviceNet Network
Change Node Address and click Apply if changes
are needed
35
Configuring the DeviceNet Network
  • To prepare for download, network connection must
    be established online first
  • Click Network, then Online

36
Configuring the DeviceNet Network
After Online connection established, select
network-download to network to send configuration
Write a Comment
User Comments (0)
About PowerShow.com