Title: MLC Connectivity to SLC 500 via DeviceNet
1MLC Connectivity to SLC 500 via DeviceNet
2Equipment Needed for Connecting
- MLC 9000 BCM
- Allen-Bradley SLC 500 CPU 5/02 or higher
- 5/02 smallest CPU to support M0/M1 File Transfer
- Allen-Bradley 1747-SDN DeviceNet Scanner
- Allen-Bradley RSNetworx or DeviceNet Manager
Software - RSLogix PLC Programming Software
- PC Interface(i.e 1770-KFD for programming)
- DeviceNet Cabling
- Thick Trunk Cable with Mini-Connectors
- Thin Drop Cable with Micro or Mini-Connectors
- T-Connectors
- Terminating connectors(110 Ohms)
3How SLC500 Communicates with 1747-SDN
- Two methods used
- I/O Transfer
- 1747 occupies 32 Input Words and 32 Output Words
- 1 word of input, 1 word of output used for module
status and command - 62 words available for devices
- Intended for devices transmitting small blocks of
information - Proximity and Photoelectric Switches
- Slice I/O
- Valves
4How SLC 500 Communicates with 1747-SDN
- Block Transfer via M0/M1 Files
- M1 File
- 150 Words Available for Input from Network
Devices (M11.0-M11.149) - 74 Diagnostic Words (M11.150-M11.223)
- 32 Words for Inbound Explicit Message Control
(M11.224-M11.255)
5How SLC 500 Communicates to 1747-SDN
- Block Transfer via M0/M1 Files
- M0 File
- 150 Words of data used for output to network
devices (M01.0-M01.149) - 74 Words Reserved/Unused (M01.150-M01.223)
- 32 Words used for outgoing explicit message
control (M01.224-M01.255)
6How MLC 9000 Communicates with 1747-SDN
- MLC 9000 Gateway
- Converts DeviceNet Messages from Scanner into
Modbus Messages to Bus Control Module - Uses Polled Messaging for Implicit I/O Connection
- One Loop Control Module takes up 16 Bytes of
Input and 6 Bytes of Output - Uses Explicit Messaging to gain access to
parameters not supported through implicit
connection
7Implicit I/O Connection Data
8Setting Up PC to Communicate via DeviceNet
In RSLinx, Select Communications and Configure
driver
9Setting Up PC to Communicate via DeviceNet
Under Available Driver Types, select DeviceNet
Drivers and select Add new
10Setting Up PC to Communicate via DeviceNet
Select 1747-SDNPT
11Setting Up PC to Communicate via DeviceNet
Select Processor to Connect to and slot where
1747-SDN resides
12Setting Up PC to Communicate via DeviceNet
1747-SDNPT-1 should be seen running
13Setting Up SLC500 to Pull Information from
1747-SDN
Start RSLogix and Select File-New
14Setting Up SLC500 to Pull Information from
1747-SDN
Select processor from list
15Setting Up SLC500 to Pull Information from
1747-SDN
From Menu Tree, Select IO Configuration then add
1747-SDN into Slot 1 of Rack
16Setting Up SLC500 to Pull Information from
1747-SDN
Highlight on Rung in Ladder Window
17Setting Up SLC500 to Pull Information from
1747-SDN
- Insert one Normally Closed Contact and Two Copy
Instructions into Rung 1 - Copy Instructions move data from M0/M1 Files to
usable data areas
18Setting Up SLC500 to Pull Information from
1747-SDN
- Last Rung Energizes Output Run coil and disables
in event of error in module - Download to PLC and place in Run Mode
19Configuring the DeviceNet Network
- To Configure Network, Gateway EDS file must be
installed - EDS (Electronic Data Sheet) carries configuration
properties for DeviceNet products - Start RSNetworx then select Tools-EDS Wizard
20Configuring the DeviceNet Network
Select Register EDS File then select Choose File
21Configuring the DeviceNet Network
- Select A Drive then select West0456
- Click Open
22Configuring the DeviceNet Network
Wizard will run test on EDS
23Configuring the DeviceNet Network
Wizard will prompt you to associate a graphic
icon with EDS
24Configuring the DeviceNet Network
This will finish the EDS Installation
25Configuring the DeviceNet Network
Select 1747-SDN from Device List
26Configuring the DeviceNet Network
Insert MLC 9000 Gateway form Device List
27Configuring the DeviceNet Network
Double Click on 1747-SDN and select Scanlist
28Configuring the DeviceNet Network
- Click on arrow to add Gateway to 1747-SDNs
scanlist - Select edit I/O parameters
29Configuring the DeviceNet Network
- Adjust the Polled Rx and Tx parameters to match
the number of I/O taken up by LCMs - 16 bytes of Rx and 6 bytes Tx for every LCM (up
to 8 LCMs)
30Configuring the DeviceNet Network
- Select Input
- Select Memory Type M file
- Select AutoMap
31Configuring the DeviceNet Network
- Select Output
- Select Memory Type M file
- Select AutoMap
32Configuring the DeviceNet Network
- From Main Screen, select Tools then Node
Commissioning - Nodes must be commissioned with proper baud rate
and node address before the configuration can be
downloaded to network - Select Browse
33Configuring the DeviceNet Network
- Select 1747-SDNPT from list of drivers
- RSNetworx will detect connected devices
- Select Node to adjust
34Configuring the DeviceNet Network
Change Node Address and click Apply if changes
are needed
35Configuring the DeviceNet Network
- To prepare for download, network connection must
be established online first - Click Network, then Online
36Configuring the DeviceNet Network
After Online connection established, select
network-download to network to send configuration