Texas Department of State Health Services
  • Pharmacy

133.163(x)
2
Objectives
? 797 Rule Spatial Requirements for Pharmacy
? Chapter 22 of Texas Administrative Code,
291.26 (relating to Pharmacies
Compounding Sterile Pharmaceuticals).
? The United States Pharmacopoeia, Chapter 797,
Pharmaceutical Compounding-Sterile
Preparations. (January 1, 2004)
? Questions ???
3
Review of the New Hospital Spatial Req. - Pharmacy
  • Pharmacy suite - 133.163(x) (New)
  • Intravenous (IV) solutions area. When IV
    solutions are prepared in a pharmacy, a sterile
    work area shall be provided and be in compliance
    with 22 Texas Administrative Code, 291.26
    (relating to Pharmacies Compounding Sterile
    Pharmaceuticals) and the United States
    Pharmacopoeia, Chapter 797, Pharmaceutical
    Compounding-Sterile Preparations.
  • The IV work area shall consist of a preparation
    room, hood room and, if provided, a separate
    chemo-hood room. Access to the preparation room
    shall be through the pharmacy only, access to the
    hood room or chemo-hood room shall be through the
    preparation room only.

4
Review of the New Hospital Spatial Req. - Pharmacy
  • Pharmacy suite (Cont)
  • The preparation room shall contain a work
    counter, gowning area and shelving.
  • A hand washing fixture with hands-free operable
    controls shall be in the preparation room and
    within five feet of each entrance to the hood
    room or chemo-hood room. Hand washing fixtures
    and floor drains are not allowed inside the hood
    room or chemo-hood room.
  • Laminar-flow hoods/work stations shall be located
    inside the hood room.

5
Review of the New Hospital Spatial Req. - Pharmacy
  • Pharmacy suite (cont.)
  • Compounding aseptic isolator (CAI). When a CAI
    is used for compounding, in lieu of the IV
    solutions area, it may be done within the
    pharmacy provided it complies with the following.
  • The CAI shall provide isolation from the room and
    maintain the International Organization for
    Standardization (ISO) Class 5 (100 particles
    greater than or equal to 0.5 microns per cubic
    foot) levels during dynamic operating conditions
    including transferring ingredients, components,
    and devices into and out of the isolator and
    during preparation of compounded sterile
    preparations.

6
Review of the New Hospital Spatial Req. - Pharmacy
  • Pharmacy suite (cont.)
  • The particle counts sampled shall be 6 to 12
    inches upstream of the critical exposure site
    within the CAI and maintain ISO Class 5 levels
    during compounding operations.
  • The facility shall obtain documentation from the
    manufacturer that the CAI will meet this standard
    when located in worse than ISO Class 7 (10,000
    particles greater than or equal to 0.5 microns
    per cubic foot environments.
  • The door from hood room shall swing into the
    preparation room. The door from preparation room
    shall swing into the chemo room. The door from
    preparation room shall swing into the pharmacy.

7
Review of the New Hospital Spatial Req. - Pharmacy
  • Pharmacy suite (cont.)
  • When fume hoods are used for Chemo, the air/fumes
    shall be exhausted directly to the exterior. The
    hood exhaust shall not use the building exhaust
    system. When more than one fume hood is in the
    same hood room and the work stations face each
    other, at least six feet must separate work area
    openings.
  • In the IV solutions area the air pressure in the
    preparation room shall be positive to the
    pharmacy, the hood room shall be positive to the
    preparation room and the chemo-hood room shall be
    negative to the preparation room.

8
Review of the New Hospital Spatial Req. - Pharmacy
  • Pharmacy suite (cont.)
  • Flooring in the IV solutions area for the
    preparation room, hood room and chemo-hood room
    shall be seamless and coved to the wall.
  • IV solutions area ceiling and wall finishes for
    the preparation room, hood room and chemo-hood
    room shall be interlocking monolithic panels and
    sealed together or monolithic epoxy-painted
    gypsum board. The ceiling shall be coved to the
    wall.
  • All penetrations in the walls and ceilings shall
    be sealed.