Title: Texas Department of State Health Services
1Texas Department of State Health Services
133.163(x)
2Objectives
? 797 Rule Spatial Requirements for Pharmacy
? Chapter 22 of Texas Administrative Code,
291.26 (relating to Pharmacies
Compounding Sterile Pharmaceuticals).
? The United States Pharmacopoeia, Chapter 797,
Pharmaceutical Compounding-Sterile
Preparations. (January 1, 2004)
? Questions ???
3Review of the New Hospital Spatial Req. - Pharmacy
- Pharmacy suite - 133.163(x) (New)
- Intravenous (IV) solutions area. When IV
solutions are prepared in a pharmacy, a sterile
work area shall be provided and be in compliance
with 22 Texas Administrative Code, 291.26
(relating to Pharmacies Compounding Sterile
Pharmaceuticals) and the United States
Pharmacopoeia, Chapter 797, Pharmaceutical
Compounding-Sterile Preparations. - The IV work area shall consist of a preparation
room, hood room and, if provided, a separate
chemo-hood room. Access to the preparation room
shall be through the pharmacy only, access to the
hood room or chemo-hood room shall be through the
preparation room only.
4Review of the New Hospital Spatial Req. - Pharmacy
- Pharmacy suite (Cont)
- The preparation room shall contain a work
counter, gowning area and shelving. - A hand washing fixture with hands-free operable
controls shall be in the preparation room and
within five feet of each entrance to the hood
room or chemo-hood room. Hand washing fixtures
and floor drains are not allowed inside the hood
room or chemo-hood room. - Laminar-flow hoods/work stations shall be located
inside the hood room.
5Review of the New Hospital Spatial Req. - Pharmacy
- Pharmacy suite (cont.)
- Compounding aseptic isolator (CAI). When a CAI
is used for compounding, in lieu of the IV
solutions area, it may be done within the
pharmacy provided it complies with the following.
- The CAI shall provide isolation from the room and
maintain the International Organization for
Standardization (ISO) Class 5 (100 particles
greater than or equal to 0.5 microns per cubic
foot) levels during dynamic operating conditions
including transferring ingredients, components,
and devices into and out of the isolator and
during preparation of compounded sterile
preparations.
6Review of the New Hospital Spatial Req. - Pharmacy
- Pharmacy suite (cont.)
- The particle counts sampled shall be 6 to 12
inches upstream of the critical exposure site
within the CAI and maintain ISO Class 5 levels
during compounding operations. - The facility shall obtain documentation from the
manufacturer that the CAI will meet this standard
when located in worse than ISO Class 7 (10,000
particles greater than or equal to 0.5 microns
per cubic foot environments. - The door from hood room shall swing into the
preparation room. The door from preparation room
shall swing into the chemo room. The door from
preparation room shall swing into the pharmacy.
7Review of the New Hospital Spatial Req. - Pharmacy
- Pharmacy suite (cont.)
- When fume hoods are used for Chemo, the air/fumes
shall be exhausted directly to the exterior. The
hood exhaust shall not use the building exhaust
system. When more than one fume hood is in the
same hood room and the work stations face each
other, at least six feet must separate work area
openings. - In the IV solutions area the air pressure in the
preparation room shall be positive to the
pharmacy, the hood room shall be positive to the
preparation room and the chemo-hood room shall be
negative to the preparation room.
8Review of the New Hospital Spatial Req. - Pharmacy
- Pharmacy suite (cont.)
- Flooring in the IV solutions area for the
preparation room, hood room and chemo-hood room
shall be seamless and coved to the wall. - IV solutions area ceiling and wall finishes for
the preparation room, hood room and chemo-hood
room shall be interlocking monolithic panels and
sealed together or monolithic epoxy-painted
gypsum board. The ceiling shall be coved to the
wall. - All penetrations in the walls and ceilings shall
be sealed.
9Hospital Licensing RulesTitle 25 TAC - Chapter
133
Pharmacy