Title: NEMA RV 3 Application
1NEMA RV 3Application Installation Guidelines
For Flexible Liquid Tight Flexible Metal
Conduits
2Application Guidelines for FMC
- Construction of FMC
- Grounding and Bonding
- Uses Permitted and Not Permitted
3Construction for FMC
- Constructed in accordance with NEC
- Complies with safety requirements of UL1
- Interlocked corrosion resistant steel or Aluminum
strip
4Picture Example for FMC
5Diagram Example for FMC
Cross-section view illustrating interlocking
construction
6Grounding and Bonding for FMC
- Permitted for bonding
- When installed with listed fittings and
- Flexibility is not required after installation
and - When installed according to NEC Articles 348 and
250 and - Protected by overcurrent device rated 20 Amperes
or less. - Limited to 6 lengths when used for bonding (see
NEC 250.118 (5)) - Grounding conductor required if FMC
- installed for flexible equipment or
- when used in lengths greater than 6.
- Grounding and bonding continued in slide 7
7Product Marking for FMC
- Manufacturers designation
- UL Logo
- Conduit type
- Reduced wall (RW)
- Extra reduced wall (XRW)
- Material type
- Aluminum (AL)
- Steel (No Mark Required)
8FMC Marking Example
9Uses Permitted for FMC
- Exposed and concealed locations NEC 348.10
- Dry locations only
- Branch circuits and feeders
- Ducts or plenums for environmental air
- 300.22(B) limits to 4 length
- 300.22(C) no length limit
- Under raised floors for computer rooms
- Lighting whips and motor leads
- These uses are not all inclusive, but serve as
guidelines
10Uses Not Permitted for FMC
- NEC 348.12
- Wet locations
- 2008 NEC removed exceptions
- Hoistways except as permitted in 620.21(A)(1)
- Storage battery rooms
11Uses Not Permitted cont. for FMC
- Hazardous locations except 501.10(B) and 504.20
- Where conductors are exposed to deteriorating
material - Underground or in concrete
- Where subject to physical damage
12Reference ArticlesReference UL 1 and NEC
- NEMA RV 3 1.4.1 National Electric Code
- NEMA RV 3 1.4.2 Related NEC Articles
- NEMA RV 3 1.4.3 UL Standards
- Guide information page http//database.ul.com/cgi
-bin/XYV/template/LISEXT/1FRAME/index.htm - White book Guide Information for Electrical
Equipment
13Application Guidelines for LFMC
- Construction of LFMC
- Grounding and Bonding
- Marking
- Uses Permitted and Not Permitted
14Construction for LFMC
- In accordance with NEC
- Complies with safety requirements of UL360
- Interlocked zinc-coated corrosion resistant steel
- Trades sizes are 3/8 through 4
- Sizes 3/8 1 ¼ have bonding strip enclosed by
convolution
15Construction cont. for LFMC
- Jacket material is liquid-tight, non metallic
- Jacket specifications governed by UL 360
- Fittings for LFMC are constructed to UL 514B
16Picture example for LFMC
Cut-away view of Liquidtight Flexible Metal
Conduit to illustrate construction
17Diagram Example for LFMC
Cross-section view illustrating interlocking
construction
18Grounding and Bonding for LFMC
- LFMC trade sizes 3/8 1 ¼ permitted for
equipment bonding - When installed with listed fittings and
- Flexibility is not required after installation
and - When installed according to NEC Articles 350 and
250 and - Only in 6 lengths or less
- Sizes 3/8 4 may be installed in unlimited
lengths provided - A separate grounding conductor is installed
- And installed according to NEC Articles 350 and
250
19Surface Print for LFMC
- Manufacturers name or location
- Trade size
- Temperature rating
- Burial rating (when applicable)
- Flame rating (when applicable)
- Current rating (for equipment bonding according
to NEC article 250)
20Uses Permitted for LFMC
- Exposed and concealed locations as follows
- When flexibility or protection from liquids,
vapors or solids are required - As permitted by 501.10(B), 502.10, 503.1 and
504.20 - Other hazardous classified locations per 553.7(B)
- Direct burial where listed marked for that
purpose - If LFMC is marked direct burial it is also
suitable for use in concrete or in poured
concrete - The following are references throughout the NEC
code
21Uses Permitted cont. for LFMC
- Outside branch circuits and feeders
- Under raised floors for computer rooms
- Lighting whips and motor leads
- These uses are not all inclusive, but serve as
guidelines - References throughout the NEC Code
22Uses Not Permitted for LFMC
- Where subject to physical damage
- Where operating conditions cause temperatures to
exceed material ratings - See NEC 350.12 for prohibited uses
23Reference Articles for LFMC
- NEMA RV 3 2.4.1 National Electric Code
- NEMA RV 3 2.4.2 Related NEC Articles
- NEMA RV 3 2.4.3 UL Standards
- Guide information page http//database.ul.com/cgi
-bin/XYV/template/LISEXT/1FRAME/index.htm - White book Guide Information for Electrical
Equipment
24Installation Guidelines
- Installation Considerations
- Securing Supporting FMC LFMC
- Terminating FMC
25Installation Considerations for FMC LFMC
- Minimum centerline bend radius
- Table 2 chapter 9 NEC
- Other bends column
- Maximum of bends between pull points
- Not to exceed (4) - 90 degree bends
- Or a total of 360 degrees (any direction)
26Lateral Offsets
- Use tables for length
- Lateral offset
- Example below
27Vertical Loop
- Vertical loop w/offset
- L(8xTS)(1.57xA) T/2F
- L Overall length
- TS Trade size
- A Horizontal dist between fittings
- T Travel distance
- F Offset
- This accounts for suggested tangent length
28Installation Considerations cont. for FMC LFMC
- Fittings should be tightened properly
- Section 3.3, tables 1 and 2 of NEMA guidelines
for proper torquing values - Closely follow manufacturer's instructions
29Securing Supporting FMC LFMC
- According to NEC 348.30 350.30
- Both must be supported and secured every 4.5 or
less - Must be secured within 12 of each termination
- These support requirements are waived if needed
for flexibility or for luminaries
30Securing Supporting cont. for FMC LFMC
- Both may be unsupported when
- Conduit is fished between access points through
concealed spaces in finished buildings or
structures and supporting is impractical - Flexibility is required
- 3 maximum for LFMC
- 3 maximum for FMC ½ through 1¼
- 4 maximum for FMC 1½ through 2
- 5 maximum for FMC 2½ and larger
- Used on luminaries 6 maximum
- Run through non-vertical framing members with
distances not exceeding 4½
31Terminating FMC
- Fitting Selection requires knowing
- Trade size or metric designator
- Type of FMC, (standard, reduced or extra-reduced
wall) - Type of metal (steel or aluminum)
32Conduit Preparation for FMC LFMC
- Square the cut end of the metal conduit
- Insert conduit flush with fitting end stop
- Ensure seating of clamp on conduit before
torquing - Be careful torquing the securement screw
- Always follow the manufacturer's instructions
- Follow recommendations from NEMA FB 2.20,
Selection and Installation guidelines for
Fittings for use with Flexible Conduit and Cable
33Cutting Conduit for FMC
- Rotary armor cutters
- Hacksaw
- Cut one convolution at a 60 degree angle
- Diagonal wire cutters
- Brake the conduit or twist open
- Then cut with the cutters
34Cutting Conduit for LFMC
- Hacksaw
- Blade should have 32 teeth per inch
- Band saw with ½ X .025 Blade with 24 teeth per
inch at 350 ft/min
35Fitting Attachment for FMC
- Always make sure the conduit is inserted
completely to the smooth end stop - When using a clamp type fitting, be sure the
fitting seats between the convolutions - Hand tighten the fitting screws and slightly
rotate the conduit in the fitting - If there are two screws, tighten alternately to
provide even pressure. - Table 1 in NEMA RV 3 shows standard torque values
for FMC fittings
36Terminating for LFMC
- Fitting Selection requires knowing
- Trade size or metric designator
- The environment of installation
- Conduit preparation
- Square the end of the conduit
- Fully insert conduit to end stop
- Ensure jacketing is not cut or ripped
- Always follow the manufacturers instructions
- Follow recommendations from NEMA FB 2.20,
Selection and Installation guidelines for
Fittings for use with Flexible Conduit and Cable
37Fitting Attachment for LFMC
- Squared end must be fully inserted into ferrule
- Assembly methods vary for LFMC fittings, follow
manufacturer's instructions - Table 2 in NEMA RV 3 show standard torque values
for LFMC fittings
38Unthreaded Entries
- Hand tighten the threaded portion of fitting to
secured box using a locknut - Assemble nut, gland and ferrule onto conduit
- After securely tightening the gland nut to the
threaded body, finish tightening the locknut ¼
turn
39Fitting Example
40Verification of Installation
- Conduit shall be properly terminated at boxes
- Conduit shall be properly secured and supported
- Conduit shall not show evidence of damage or
physical abuse