Title: Series F4P 14 DIN Process and Temperature Controllers
1Series F4P 1/4 DIN Process and Temperature
Controllers
2(No Transcript)
3Watlows Next Generation Styling
Series V4T 1/4 DIN Temperature Controller
Series F4P Temperature and Process Controller
Series 97 Matching 1/16 DIN Limit Controller
4F4P Focus Markets
5Furnaceand Oven
- Applications
- Heat Treating
- Kilns
- Autoclaves
- Foundry Metal Processing
6Electronic Components and Assembly
- Semiconductor processing equipment
- Electronic assembly equipment
- Test Equipment
7Packaging and Sealing
- Box Sealing
- Shrink Wrapping
- Blister Packing
8Other FocusIndustries
- Applications
- Analytical Instruments
- Pulp and paper processing
- Petrochemical processing
9Ease of Use
The most important selection factor following
quality and reliability when selecting a
temperature controller is ease of use.
Source1997 VDC Worldwide Market Report for
Industrial Electronic Temperature Controllers
10Enhanced Display and Keypad
- Control programming made easy through advanced
technology - Icons for international applications
- Read-at-a-glance process display
- Full message prompting of operation and setup
11F4 Operator Interface
- Primary process display
- Large 5-digit, 7-segment display
- 0.562 (14.3mm) display digit height
- F or C, degree, and decimal point indication
- Operations display
- 4 line X 20 characters per line
- High definition back lit LCD
- Wide viewing angle
12F4 Operator Interface
- 6 Operator interface keys
- Rubber key switch with tactile feel
- Four navigational keys
- Parameter and value selection
- i information key
- Toggle for help
- Dedicated Auto/Manual operation key
13F4 Operator Interface
- Discrete LED Indicators
- Control output indication
- Alarm active indication
- Communications activity
- Auto/Manual operation indication
-
14Advanced Hardware Features
- 20 MHz operation, 16-bit processor
- NEMA 4X, IP 65 sealed front panel
- Shallow 4 (101mm) overall case depth
- FLASH memory for field software update
15F4 Industrial Design Features
- High strength injection molded case
- 3.85 (97.8mm) behind panel depth
- Ergonomic design styling
- Compatible with Series 96 97 limit
- NEMA 4X, IP 65 front panel seal
- Convenient 4 screw installation brackets
16F4 Industrial Design Features
- Touch safe wiring termination
- Removable for wiring convenience
- Accepts 12 to 22 gauge wires
- Positive latching feature
- Connection integrity
- Withstands equipment vibration
17Loaded With Standard Hardware Features
- 3 universal analog inputs (2 3 optional)
- TC, RTD, process (no DIP switches)
- 4 digital inputs (standard)
- Control functions
- Contact closure or DC voltage
18Modular Hardware Inputs and Outputs
- Field replaceable input and output modules
- Dual control outputs
- Reverse/Direct or Off
- Linear or time proportioned
- Switched dc/open collector, SSR, process
- Alarms (2 standard)
- Process, deviation, rate
- 2 A mechanical relays
19Leading the Way in Communications
- Serial communications standard
- EIA 232 EIA 485 hardware interfaces
- MODBUS protocol
- 9600 and 19,200 baud
- Allows in field software updates
20Hardware Features
- Retransmit outputs
- 2 optional
- Current or voltage
- Process, set points, power
- Universal power supply
- 85 to 265 vac/vdc, 50 to 60 hz
- Optional 24 to 28 vac/vdc
21Performance Specifications
- Operating range
- 0 to 65C
- Calibration accuracy
- 0.1 of span, /- LSD (whole digit)
- Sensor update rate
- 20 Hz, 50 ms, Input 1
- 10 Hz, 100 ms, Input 2 and Input 3
22F4 Hardware Architecture
Input to Output Isolation Minimum 500
Vac/Vdc between blocks
23Agency Approvals
- UL, c-UL 916 listed
- User replaceable input and output modules
- European CE conformity
- EN 50082-2, immunity standard
- EN 50081-2, emission standard
- EN 61010-1 low-voltage directive, safety
- NEMA 4X, IP 65 front panel seal
24Software Architecture
Main Page
Operations Page
Setup Page
Factory Page
25Software Architecture
- Guided setup programming
- Guided configuration
- Presents a sequence of parameter choices needed
to complete a functional configuration - Full unabbreviated text
- Uses full text messages, not cryptic parameter
and configuration names
26Software Operation
Toggle the Information key
27Process Value Bargraph Displays
- View both
- Output 1A and 1B in graphical format
28Programming A User-Named Alarm
- Select first line to change
29Programming A User-Named Alarm
30Programming A User-Named Alarm
31Programming A User-Named Alarm
32Programming A User-Named Alarm
33Programming A User-Named Alarm
34Programming A User-Named Alarm
- Enter VENT OPEN to name output
35Programming A User-Named Alarm
- Save change, output naming complete
36Programming A User-Named Alarm
- Return to normal operations display with Vent
Open status displayed
37F4 Software Architecture
- Function naming
- Optional, up to 10 characters
- Better operator recognition
Enter Alarm Name Alarm 1 Adjusts
Character Selects Character
38F4 Software Architecture
- Pop up verification displays
- Lets the user know when the F4 software is
storing changes in Non Volatile Memory
Save Setup Changes or restore Values?
Restore Save
39F4 Software Architecture
Main Page____ Go to Operations Go to Setup Go to
Factory
Main Page
- Display key control parameters
- Up to 16 customer programmable control parameters
- Set points, alarms, errors, power
- Inner loop set point (cascade control)
- Bar graphs/set point and process
- Gateway to controller configuration
40F4 Software Architecture
Operations Page
Main Page____ gtGo to Operations Go to Setup Go to
Factory
- Auto tune PID control parameter values
- Edit PID crossover points
- Digital set points
- Alarm set points
41F4 Software Architecture
Setup Page
Main Page____ Go to Operations gtGo to Setup Go to
Factory
- Controller functional configuration
- System settings
- PID units, F or C, auto tune SP,
- sensor failure, open loop, transfer power levels
- Inputs analog and digital
- Outputs control, alarm, communications,
retransmit - Custom main page selections
42F4 Software Architecture
Factory Page
Main Page____ Go to Operations Go to Setup gtGo to
Factory
- Set lockout
- Change password
- Diagnostics
- Date code, software revisions, etc.
- Calibration data
43F4 Temperature/Process Standard Operation
- Open or closed loop operation
- Automatic, closed loop control
- Control action responds to differences in set
point value - and process value
- Manual, open loop operation
- Control actions responds to manual changes to the
controller output power levels.
44F4 Temperature/Process Standard Operation
- Five heat cool PID sets
- Four crossover points programmable in the
operations menu - Crossover based on set point or process value
45F4 Temperature/Process Standard Operation
- Auto/manual control operation
- Manual to auto transition
- Based on the last set point
- Based on set point tracking (reverse bumpless)
- Auto to manual operation
- System menu choices for heat/cool transfer power
levels
46F4 Temperature/Process Standard Operation
- Single or multi-point offset feature
- Single-point
- Linear across entire operating span
- Multi-point (10 points and offset values)
- Points can be positioned anywhere over the entire
operating span -19999 to 30000 - Offset values are /- 1000 units/degrees
- Offset values are linearly interpolated between
points
47F4 Temperature/Process Standard Operation
- Digital set point feature
- Four namable set points
- Activated via the four digital inputs
- Set point values are entered in the operations
menu - Set point name and value appear on the main page
- Values can not be adjusted from the main page
- Digital set points have priority over local set
point
48F4 Temperature/Process Standard Operation
- Additional features
- Process outputs
- Duplex
- 4 to 20 mA, 20 to 4 mA
- Ramp to set point
- Ramp on start up/ramp on set point
- Square root input linearization
49F4 Temperature/Process Standard Operation
- Additional features
- Custom messages
- 4 user definable up to 50 characters
- Activated by digital inputs
- Displayed in main page
- Tuning feature
- Auto tune for heat only, cool only or heat and
cool
50F4 Temperature/Process Standard Operation
Main Page
- Displayable options
- Local or digital (namable) set point
- Bar graphs
- Set point, process value, output power value
- Tune status, active PID set
- Digital input status
51Creating a Part Number
Temperature/Process Controller
F4P X - X X X A - X X X X
RG Displays Custom Options
Power Supply
Output 1A
Language Option
Output 1B
English, German Spanish, French
Control Operation (Standard or Enhanced)
Auxiliary Retransmit
52F4P Feature Summary
- F4P single channel
- Single channel PID controller
- 1 universal analog input
- 4 digital event inputs
- EIA232/485 comms
- 2 alarm outputs
53Reasons to Buy
- Usability
- High definition display
- Information key
- Guided set Up and programming
54Reasons to Buy
- Reliability
- ISO 9001 manufacturing
- Three year warranty
55Reasons to Buy
- Performance
- Control accuracy
- Extensive feature set
- Exhaustive life qualification testing
- Availability
- 4 day lead-time
56Reasons to Buy
- Support
- Local sales specialists
- Applications engineering support
- Rapid field returns department
57Series F4P 1/4 DIN Process and Temperature
Controllers