Title: Variable Speed Drive Centrifugal Chillers


1
Variable Speed Drive Centrifugal Chillers
Chiller System Optimization and Energy
Efficiency Workshop September 16,17,18, 2003
York International Corporation 320 Norwood Park
South Norwood, MA 02062
David Klee, Senior Sales Engineer
2
Todays Topics
  • Theory of Operation
  • Harmonics
  • Secondary Benefits
  • Questions

3
Car Analogy
4
Prerotation vanes
Electric motor
5
Constant Speed
  • Accelerator pegged to the floor
  • Brake to slow down

6
Variable Speed
  • Full control of accelerator
  • Brake only if necessary

7
How it Works
Chilled Water Temp. Temp. Setpoint Evap / Cond
Pressure PRV Position Actual Motor Speed
Optimum Motor Speed
Optimum PRV Position
8
Weather Data
98.3
9
Head Pressure
Lowering condenser water temperature Lowers
head pressure Reduces compressor work Reduce
s energy consumption
Pressure
Condenser
Head Pressure
Compressor
Evaporator
Enthalpy
10
Variable Speed Centrifugal Chillers
30 Energy Savings
11
Harmonics
  • What do they do?
  • Cause distortion of the voltage and current sine
    wave
  • Increase the current used by a product
  • Increase the heating of utility wires and
    transformers
  • Disrupt the operation of other equipment

12
(No Transcript)
13
(No Transcript)
14
(No Transcript)
15
Harmonics
  • Many utilities are pushing for lower harmonics
  • The current standard is IEEE 519-1992
  • It developed acceptable levels of voltage and
    current distortion produced by a product
  • This is a guideline not a required law

16
Harmonics Filtration
  • Specially designed filter to keep a building in
    compliance with IEEE-519
  • Filter is unit mounted in the same cabinet as the
    VSD
  • Still has the UL label
  • Filter parameters displayed on the chiller panel

17
(No Transcript)
18
Current Generation VSDs
  • Unit Mounted
  • UL Approved
  • Cooling Circuit
  • Any Refrigerant
  • 3rd party or 1st party

19
Standard Features
  • Circuit breaker with 65kA withstand
  • UL listed ground fault protection
  • All drive displays on chiller panel
  • Single point wiring
  • No additional floor space required
  • Harmonics Attenuation Packages

20
Operating Benefits
  • Slower minimum speed of 30 hz
  • 0.95 or better total power factor at all loads
  • 0.98 or better total power factor with filter
  • Takes the place of the starter
  • Reduces inrush to less than 100 FLA
  • Anti-recycle timer - 0 min
  • Reduced driveline wear

21
Sound
  • Generated by refrigerant discharge at high
    velocities
  • Slowing compressor reduces sound

22
Inrush Current
500
400
300
Motor FLA ()
Star Delta Starter
200
100
Millennium VSD
0
5
10
20
40
Time (sec)
23
Soft Start
  • Never exceed 100 FLA
  • Increase motor life
  • Excellent for limited inrush capabilities
    (generator starts)

24
Local Installations
  • Mass General Hospital
  • Harvard University
  • Boston City Hall
  • Northeastern University
  • BAE Systems
  • Prudential Center
  • 111 Huntington
  • Gillette Company
  • Raytheon Company
  • Museum of Science
  • Royal Sonesta Hotel

25
Questions?
26
YORK OptiSpeedTM Variable Speed Drive
Designed for Optimum Real-World Energy
Performance