Motor Starting Analysis - PowerPoint PPT Presentation

1 / 16
About This Presentation
Title:

Motor Starting Analysis

Description:

... current and voltage flicker. Using motor analysis in ... will likely hit a voltage flicker constraint before hitting a dropout ... and Voltage Flicker ... – PowerPoint PPT presentation

Number of Views:271
Avg rating:3.0/5.0
Slides: 17
Provided by: mils3
Category:

less

Transcript and Presenter's Notes

Title: Motor Starting Analysis


1
Motor Starting Analysis
Dan HarmsLa Plata Electric Association
2
Overview
  • Starting a motor
  • Why run motor analyses?
  • Available fault current and voltage flicker
  • Using motor analysis in WindMil
  • VFD and soft starting options
  • Communicating results to customer

3
Starting a Motor
  • Motor must overcome its own rotor inertiaplus
    that of the load
  • Locked rotor starting current may be 6 to 9 times
    normal
  • running current

4
System Voltage Drop
Current Flow
Voltage Drop
  • Inrush of current causes additional voltage dip
    from the source to the motor

Source
115 kV 60 mi of 477 ACSR
0.2
9 A
Substation 10 MVA 6.5
0.3
12.47 kV 3 mi of 4/0 ACSR
83 A
1.9
Dist Xfmr 500 kVA, 3.5
2.0
2.1 kA
1.8
480 V 100 ft of 2-500 MCM
300 HP
5
(No Transcript)
6
Why Run Motor Analysis?
  • Customer perspective
  • Will the motor start?
  • Dropout voltage
  • Typically 80 - 85 of (of what we consider)
    nominal
  • Motor heating is proportionate to the square of
    the operating current
  • You will likely hit a voltage flicker constraint
    before hitting a dropout voltage constraint

7
Why Run Motor Analysis?
  • Utility perspective
  • Transformer sizing / impedance
  • Voltage flicker

8
Voltage Flicker
9
Point of Common Coupling
  • Distribution transformer secondary
  • If other customers share distribution transformer
  • Distribution transformer primary
  • If distribution transformer is dedicated to motor
    load
  • Substation transformer secondary
  • If large motor has its own feeder
  • Substation transformer primary
  • If large motor has its own substation

10
System Voltage Drop
Voltage Drop
Current Flow
Cumulative Voltage Drop
Source
115 kV 60 mi of 477 ACSR
9 A
0.2
0.2
Substation 10 MVA 6.5
0.3
0.5
12.47 kV 3 mi of 4/0 ACSR
83 A
1.9
2.4
Dist Xfmr 500 kVA, 3.5
2.0
4.4
2.1 kA
1.8
6.2
480 V 100 ft of 2-500 MCM
300 HP
11
Available Fault Current and Voltage Flicker
  • Maximum allowable inrush current approximately
    equals maximum allowable flicker times available
    fault current

12
Motor Analysis in WindMil
13
WindMil Examples
  • Locked rotor motor start on a distribution system
  • Custom data boxes
  • Soft starting options
  • Add capacitor for motor start assist
  • Large motor analysis on looped transmission
    system
  • Variable frequency drives
  • Color by maximum allowable kVA

14
Communicating Results
  • Customer needs to be capable of interpreting the
    results you provide them
  • Maximum starting kVA
  • Best format to present results
  • Independent of voltage
  • Maximum starting amps
  • Voltage needs to be specified
  • Maximum horsepower
  • May be the only thing the customer comprehends
  • Many other variables could increase the amount of
    starting current above what you projected

15
Follow Up
  • Make a file of your studies
  • Dont be afraid to spot check installations
  • Keep an eye on harmonics

16
QUESTIONS?
  • Dan Harms
  • La Plata Electric Association
  • 970-382-3514
  • dharms_at_lpea.coop
Write a Comment
User Comments (0)
About PowerShow.com