Title: Arc Flash Hazard Can HRG Technology play a role in prevention
1Arc Flash HazardCan HRG Technology play a role
in prevention
2Overview
- Understand
- What is Arc Flash
- Bolted Fault and Arcing Fault
- Flash Hazard Analysis
- Ungrounded Systems
- Solidly Grounded Systems
- HRG Systems
3Poll Question 1
- Have you considered using HRG technology as part
of an arc flash reduction strategy?
4What is Arc Flash?
NFPA 70E says an arc flash hazard is A dangerous
condition associated with the release of energy
caused by an electric arc
A hazard beyond shock and electrocution.
5Two major electrical Faults Bolted and Arcing
Faults
- Bolted faults (low impedance and high current)
- Commonly caused by
- Improper connections after maintenance
- Installation errors
- Arcing faults (high impedance, lower current)
- Commonly caused by
- Careless cover or device removal
- Foreign object (tool) dropped into equipment
- Misalignment of moving contacts (parts failure)
- Dirt contamination or dielectric breakdown
- Entry of foreign body (rodent, snake, squirrel)
6Bolted and Arcing Fault Characteristics
- Arcing fault incident energy produced is
- Greater at higher bolted fault current levels
- Reduced by dynamic impedance (air)
- And increased by the time duration of the arc
- The most controllable factor in reducing the
incident energy is time - Fuses or circuit breakers are the first line of
defense in reducing arcing fault incident energy - Calculating arc fault incident energy is a very
complex engineering task
7Electrical Arc Facts
- Arc is electric current passing through air
- Shock potential from contact with arc
- Temperature of arc plasma center is greater than
5000F (some say much higher) - Radiated heat burns
- Pressure wave generated from arc
- Impact to hearing, etc
- Gaseous copper is 44,000 times solid
- Molten metal expelled from equipment at high
speed - Arc fault results from something wrong or out of
place
8Some arc flash injury statistics
Five to ten arc flash explosions occur in
electrical equipment every day in the United
States, according to statistics compiled by
Cap-Schell, Inc., a Chicago-based research and
consulting firm that specializes in preventing
workplace injuries and deaths. Injuries from arc
flash events range from minor injuries to third
degree burns and potential death due to the
energy released. Other injuries include
blindness, hearing loss, nerve damage, and
cardiac arrest. The average cost of medical
treatment for survivors of arc flash incidents is
1,500,000
9Flash Hazard Analysis
Flash hazard analysis shall be done before a
person approaches any exposed electrical
conductor or circuit part that has not been
placed in an electrically safe work condition.
(NFPA 70E, Part II, 2-1.3.3)
- Desired output for each equipment
- Flash protection boundary distance
- Incident energy
- Hazard / risk category for PPE selection
10Limits of approach
Flash protection boundary An approach limit at a
distance from exposed live parts within which a
person could receive a second degree burn if an
electric arc flash were to occur. (NFPA 70E
proposed)
It is generally accepted that a second degree
burn results from exposure of incident energy of
1.2 cal/cm2
NFPA 70E, Fig. A-1-2.4
11Flash Protection Boundary
a distance from exposed live parts within which a
person could receive a second degree burn
D
Dfb
12Incident Energy
The amount of energy impressed on a surface, a
certain distance from the source, generated
during an arc event. Incident energy is
measured in calories/cm2 or Joules/cm2.
(Ref NFPA 70E 2003 ROC, IEEE 1584)
13Incident Energy
Incident energy is energy impressed on this
surface a working distance, D, from the arc
source.
D
14Analysis process steps
- 1 Collect system and installation data
- 2 Determine system modes of operation
- 3 Determine bolted fault current
- 4 Determine arc fault current
- 5 Find protective device characteristic and arc
duration - 6 Document system voltages and equipment class
- 7 Select working distances
- 8 Calculate incident energy
- 9 Calculate flash protection boundary
Source IEEE 1584
15Step 1,2System data and modes of operation
- Begin with single-line diagrams and people who
know site - Collect information needed for short circuit and
coordination study - Determine each operation mode and perform
calculation for each (maximum fault may not be
worst case) - Modes
- Multiple feeders
- Multiple transformers with tie
- Generators in parallel or standby
16Step 3Determine bolted fault current
- Start with utility information
- Use information from Steps 1 2
- Calculate accurate 3-phase bolted fault
- High or low values may not give proper arc flash
output - Calculation spreadsheet available with IEEE 1584
17Step 4Calculate arc fault current
For V lt 1 kV, Log Ia K 0.662 Log Ibf
0.0966 V 0.000526 Gap 0.5588 (Log Ibf) V
-0.00304 (Log Ibf) Gap
For V gt 1 kV, Log Ia 0.00402 0.983 Log Ibf
Both cases, Ia 10(Log Ia)
480 V Examples 20 kA bolted gt 6 kA arc 50 kA
bolted gt 13 kA arc 80 kA bolted gt 20 kA arc
Calculate Normalized Incident Energy
Convert to Incident Energy
Gap is distance between electrodes. Typical
distances provided.
18Step 5Determine protective device duration
Use calculated arc current instead of bolted
fault current to determine duration. Notice
dramatic change below the instantaneous
level. Include delay plus device operating time
where relay is involved.
Time
Current
?
?
19Determine PPE Hazard Risk Category
Category Cal/cm2 Clothing
0 (1.2) Untreated cotton 1 5 FR shirt FR
pants 2 8 Cotton underwear plus FR shirt FR
pants 3 25 Cotton underwear plus FR shirt FR
pants plus FR coverall 4 40
Cotton underwear plus FR shirt FR pants
plus double layer switching coat and
pants Source NFPA 70E, Table 3-3.9.3
From incident energy value Output category for
Personal Protective Equipment
20Example of PPE
21Analogy
- Automotive Industry
- Passive Safety Control
- Seat Belt
- Shoulder Harness
- Airbags
- Electrical Industry
- Passive Safety Control
- PPE
- Arc Resistant Gear
22Analogy
- Automotive Industry
- Active Safety Control
- Intelligent Speed Adaptation
- Center High Mounted Stop Lamps
- Rear End Collision Warning
- Variable Assist power steering
- Traction Control
- Anti-locking Braking System
- Emergency Brake Assist
- Corner Brake Control,
- Forward Collision Warning
- Lane Departure Warning
- Driver Training
- Electrical Industry
- Active Safety Control
- HRG?
- Training
23Analogy
- Automotive Industry
- Statistics
- 855,258 ACCIDENTS analyzed by light conditions
- In daylight, black cars were 12 more likely than
white cars to involved in an accident. Followed
by grey cars at 11,silver at 10 - At dusk, or Dawn, the risk factor for black cars
jumped to 47 more likely than white cars to
involved in an accident. Follwed by silver cars
at 15.
- Electrical Industry
- Statistics
- 90 of all Faults start as ground faults.
24What are the main Hazards with Ungrounded /
Solidly Grounded?
- Ungrounded Method used to ground first power
systems - Very large transient over-voltage conditions may
exist. - Insulation not rated, therefore, hazard to
personnel and equipment. - Very difficult to locate ground fault.
- Good chance of second ground fault on a different
phase due to prolonged ground fault. - Solidly Grounded Replaced Ungrounded Systems
- Very high ground fault currents.
- Fault must be cleared, shutting down equipment.
- Generators may not be rated for ground fault .
- Tremendous amount of arc flash / blast energy.
- Equipment and people are not rated for energy.
25Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 242-2001 (Buff Book)
- Recommended Practice for Protection and
Coordination of Industrial and Commercial Power
Systems - 8.2.5 If this ground fault is intermittent or
allowed to continue, the system could be
subjected to possible severe over- voltages to
ground, which can be as high as six to eight
times phase voltage. Such over-voltages can
puncture insulation and result in additional
ground faults. These over- voltages are caused
by repetitive charging of the system
capacitance or by resonance between the system
capacitance and the inductance of equipment in
the system.
26Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 141-1993 (Red Book)
- Recommended Practice for Electric Power
Distribution for Industrial Plants - 7.2.1 Accumulated operating experience
indicates that, in general purpose industrial
power distribution systems, the over- voltage
incidents associated with ungrounded operation
reduce the useful life of insulation so that
electric current and machine failures occur
more frequently than they do on grounded power
systems.
27Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 242-2001 (Buff Book)
- Recommended Practice for Protection and
Coordination of Industrial and Commercial Power
Systems - 8.2.5 Ungrounded low-voltage systems employ
ground detectors to indicate a ground fault.
These detectors show the existence of a ground
on the system and identify the faulted phase,
but do not locate the ground, which can be
anywhere on the entire system. - One disadvantage of the solidly grounded 480V
system involves the high magnitude of
destructive, arcing ground-fault currents that
can occur. However, if these currents are
promptly interrupted, the equipment damage is
kept to acceptable levels.
28Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 141-1993 (Red Book)
- Recommended Practice for Electric Power
Distribution for Industrial Plants - 7.2.4 The solidly grounded system has the
highest probability of escalating into a
phase-to-phase or three-phase arcing fault,
particularly for the 480V and 600V systems.
The danger of sustained arcing for
phase-to-ground fault probability is also high
for the 480V and 600V systems, and low for the
208V systems. For this reason ground fault
protection shall be required for system over
1000A. A safety hazard exists for solidly
grounded systems from the severe flash, arc
burning, and blast hazard from any
phase-to-ground fault.
29What causes the Hazards inUngrounded Systems?
- System Capacitance
- Unable to discharge leading to transient
over-voltages - No direct return path for ground fault current
- Prolonged fault conditions due to inability to
quickly locate fault - NEC 250.21(B) Ground Detectors. Ungrounded
alternating current systems as permitted in
250.21(A)(1) through (A)(4) operating at not less
than 120 volts and not exceeding 1000 volts shall
have ground detectors installed on the system.
30Ungrounded Systems
- Ungrounded systems do not have an intentional
connection from the source generator or
transformer to ground - Typically a three wire delta system
- Can be a four wire system where the source
neutral is not connected to ground
31Ungrounded Systems
- Unintentionally grounded through system
capacitance - Such as cables, transformers, motors, surge
suppressors, etc.
277V
Ground 0V
32Ground Faults
- Ground fault current distribution (minimal
current)
480V
Ground AØ
33Ground Faults
- Ground Fault voltage distribution (voltage rise)
34Ground Faults
- Ground Fault current distribution (current rise)
35What causes the Hazards in Solidly Grounded
Systems?
- Very low impedance in ground path
- High fault current
- High fault energy
- Ground Fault Coordination
- Long time delays on upstream devices
- High fault energy
36Solidly Grounded Systems
- Grounded systems have an intentional connection
from the source generator or transformer to
ground - Typically a four wire delta system
- Can be a three wire system where the source
neutral is not connected to loads
37Solidly Grounded Systems
- Intentionally grounded through ground wire
0O
277 O
38Bolted Ground Faults
- Ground fault current distribution on AF
39Arcing Ground Faults
- Ground fault current distribution on AF
40Arcing Ground Faults
- Arcing ground fault Lower fault current, so
OCPDs may not clear fault. Delay will cause
severe equipment and personnel damage due to
tremendous amount of energy released.
No transient over-voltages
High fault current
Arcing ground faults are approximately 38 bolted
faults.
41Locating Ground Faults
- Follow the Smoke!
- Direct return to source provides over-current
conditions that allow for OCPD to operate, hence,
clearing the fault. - OK, IF the following condition is met (and you
like repair work) - Acceptable Damage
- People???
- Equipment???
- Costs???
- Who decides???
- Not OK, IF
- You do not want to accept damaging people
- You pay for equipment repairs
42Coordination Problems
- Discussed Over-Voltage and Over-Current Hazards
... - Now discuss time factor
- Energy is also a function of time
- E volts amps time
- Large radial systems have long time delays for
coordination
43Coordination Problems
IG Fault Current (A) Va 100V (typical) t
time (cycles)
- Typical Transformer
- 2500 kVA, 5 impedance
- Ground condition Ig23kA
- KWC 55,200
- Acceptable???
44Coordination Problems
A) 100 Kilowatt Cycles Fault location
identifiable at close inspection - spit marks on
metal and some smoke marks. B) 2000 Kilowatt
Cycles Equipment can usually be restored by
painting smoke marks and repairing punctures in
insulation. C) 6000 Kilowatt Cycles Minimal
amount of damage, but fault more easily
located. D) 10,000 Kilowatt Cycles Fault
probably contained by the metal enclosure.
E) 20,000 Kilowatt Cycles Fault probably burns
through single thickness enclosure and spreads to
other sections. F) Over 20,000 Kilowatt
Cycles Considerable destruction.
45Hazards w/ Ungrounded S-G
46High Resistance Grounding
- How does HRG solve these hazards?
- Inserts a resistor between neutral and ground
- Eliminates 90 of Arc Flash / Blast Injuries
47High Resistance Grounding
- What if no neutral exists (i.e. delta systems)?
- A grounding transformer is installed (either a
zig-zag or a wye-delta) from all three phases to
create an artificial neutral for grounding
purposes only.
48High Resistance Grounding
- Intentionally grounded through neutral resistor
277V
Vng0V
Ground 0V
49High Resistance Grounding
- Compared to Ungrounded Systems (voltage rise)
480V
VngVan (277V)
Ground AØ
Additional return path, only difference between
Ungrounded and HRG!
50High Resistance Grounding
- Voltages
- Normal Operation
- Vag 277V
- Vbg 277V
- Vcg 277V
- Vng 0V
- Fault conditions
- Vag 0V (Faulted phase is at ground potential)
- Vbg 480V
- Vcg 480V
- Vng 277V
51High Resistance Grounding
- Importance of additional path versus Solidly
Grounded
Resistor (HRG) in lieu of wire adds significant
amount of resistance to lower ground fault to a
predetermined value preventing destructive fault
currents and shut-down!
52High Resistance Grounding
- Compared with Solidly Grounded (current rise)
55.4O 5.00A
277O 1.73A
5.83A
Ground AØ
Resistor in return path, only difference between
Solidly Grounded and HRG!
5.83A ? 3.00A 5.00A
53High Resistance Grounding
- Currents
- Normal Operation
- Fault conditions
54High Resistance Grounding
- Another advantage of return path ground fault
location
Contactor shorts out part of the resistor
changing the resistance, hence, changing the
current. Ground fault current now is a pulse
signal that allows for detection!
55High Resistance Grounding
Meter reading will alternate from 5A to 10A every
2 seconds.
- Method to quickly locate ground faults.
56Ground Faults
- Damage to Power System Components
- Thermal Damage (Irms)2 t
- Mechanical Damage (Ip)2
- Comparison between S-G example and HRG
System Grounding HRG S-G
Ground Fault (A) 5 22,800
Damage to Equipment (1 sec) 1 per unit
(22,800 / 5)2 20.8x106 p.u.
Solidly-Grounded Systems have 20.8 million times
more damage than HRG!!!
57Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 142-1991 (Green Book)Recommended
Practice for Grounding of Industrial and
Commercial Power Systems - 1.4.2 Numerous advantages are attributed to
grounded systems, including greater safety,
freedom from excessive system over-voltages
that can occur on ungrounded systems during
arcing, resonant or near- resonant ground
faults, and easier detection and location of
ground faults when they do occur. - 1.4.3 A system properly grounded by resistance
is not subject to destructive transient
over-voltages.
58Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 142-1991 (Green Book)Recommended
Practice for Grounding of Industrial and
Commercial Power Systems - 1.4.3 The reasons for limiting the current by
resistance grounding may be one or more of
the following. - 1) To reduce burning and melting effects in
faulted electric equipment, such as
switchgear, transformers, cables, and rotating
machines. - 2) To reduce mechanical stresses in circuits
and appartus carrying fault currents. - 3) To reduce electric-shock hazards to
personnel caused by stray ground-fault
currents in the ground return path. -
59Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 142-1991 (Green Book)Recommended
Practice for Grounding of Industrial and
Commercial Power Systems - 1.4.3 The reasons for limiting the current by
resistance grounding may be one or more of
the following. - 4) To reduce the arc blast or flash hazard to
personnel who may have accidentally caused or
who happen to be in close proximity to the
ground fault. - 5) To reduce the momentary line-voltage dip
occasioned by the clearing of a ground fault. - 6) To secure control of transient
over-voltages while at the same time avoiding
the shutdown of a faulty circuit on the
occurrence of the first ground fault (high
resistance grounding).
60Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 141-1993 (Red Book)Recommended Practice
for Electric Power Distribution for Industrial
Plants - 7.2.2 There is no arc flash hazard, as there is
with solidly grounded systems, since the fault
current is limited to approximately 5A. - Another benefit of high-resistance grounded
systems is the limitation of ground fault
current to prevent damage to equipment. High
values of ground faults on solidly grounded
systems can destroy the magnetic core of rotating
machinery.
61Do others agree?
- TO HRG OR NOT TO HRG?
- IEEE Std 242-2001 (Buff Book)Recommended
Practice for Electric Power Distribution for
Industrial Plants - 8.2.5 Once the system is high-resistance
grounded, over- voltages are reduced and
modern, highly sensitive ground-fault
protective equipment can identify the faulted
feeder on the first fault and open one or both
feeders on the second fault before arcing
burndown does serious damage.
62Design Considerations when applying HRG Systems
- HRG is the best Grounding Method available today
- First developed with resistor and pulsing
contactor (Analog) - Least Hazards of all grounding methods, but some
still exist - Elevated Voltages
- Trained Personnel
- Cables, TVSSs, VFDs Insulation
- Line-to-Neutral Loads
- Phase-to-ground-to-phase Faults
- Bypasses neutral grounding resistor
- Single-poling circuit breakers
- HRG Systems Resolve these Hazards
63Design Considerations when applying HRG Systems
- NFPA 70 National Electrical Code (2005)
- 250.36/186 High-impedance grounded neutral
systems in which a grounding impedance, usually
a resistor, limits the ground-fault current to a
low value shall be permitted for 3-phase ac
systems of 480 volts to 1000 volts where all the
following conditions are met - 1) The conditions of maintenance and
supervision ensure that only qualified persons
service the installation. - 2) Ground detectors are installed on the
system. - 3) Line-to-neutral loads are not served
- Continuity of power is required.(Removed 2008).
64Elevated Voltage Hazard
- Properly rated equipment prevents Hazards.
0V
480V
277V
480V
0V
Ground AØ
Maintenance must be aware of elevated voltages
and method to locate fault. IF NOT, DO NOT HAVE
TO MAINTAIN POWER. Allowed to trip (same as S-G)
but without the hazards.
65Elevated Voltage Hazard
- Properly rated equipment prevents Hazards.
0V
480V
277V
480V
0V
Ground AØ
Cables, TVSSs, VFDs, etc. and other equipment
must be rated for elevated voltages (Ungrounded
Systems).
66Resolve Cable Insulation Issue
- 600V Cables
- Insulation thickness based on mechanical
strength, not electrical - Extra thickness exceeds 600V electrical rating
- Therefore, should be used on 600V systems (HRG)
- 1000V Cables
- Only CSA listed, not UL
- 5000V Cables
- Non-shielded Should be used on 2400V systems
(HRG) - Shielded Should be used on 4160V systems (HRG)
- 8000V Cables
- Non-shielded Should be used on 4160V systems
(HRG)
67 Resolve NEC requirement
Add small 11 transformer and solidly ground
secondary for 1F loads (i.e. lighting).
68Resolve NEC Requirement
- Advantages of 11 transformer
- Ability to retrofit HRG Systems
- Only 20 of facility / plant load is 1F
- No neutral required from main source and main
switchgear (cost savings,) - Significantly reduced risk of Arc Blast / Flash
Hazard - Only small portion of power system is solidly
grounded - Lighting Ballasts
69Phase-to-Ground-to-Phase Fault
- Single-poling circuit breaker
2000A/3P/65kAIC
During phase-ground-phase fault, single-pole of
MCB has to clear the 480V fault at 65kA.
However, per UL 489, single-pole interrupting
rating is only at 20kAIC. HAZARDOUS?
70Phase-to-Ground-to-Phase Fault
- For condition to occur, all of the following must
be true - 1) One fault must be on line side of MCB
- Very uncommon
- 2) Low impedance per ground fault
- Very uncommon
- Ground faults are usually arcing faults (high
impedance faults per IEEE Std 241, 9.2.5) - 3) Faults on different phases
- 4) No other over-current protective devices in
fault path - Very uncommon
- If so, they will open eliminating the
single-pole interruption - Although remote, HAZARD may still exists
- Should be considered during coordination study
- Detect ground faults per NEC 250-36
71Resolving Hazard via New Technology
- First fault
- Sound Alarm
- Send signal
- Second fault
- Open feeder with lower priority
- Third fault
- Open feeder with lower priority
-
72Poll Question 2
- Will you consider using HRG technology as part of
an arc flash reduction strategy?
73Additional Advancementsin HRG Systems
- Communications
- RS232 (Serial) / RS485 (Modbus, Profibus) /
TCP/IP (Ethernet) - Control and monitor relay remotely via existing
SCADA system - Data Logging Trending
- Most ground faults are intermittent, so when you
go to locate via pulse, fault may have cleared - Data log can link ground faults with equipment
starting or running
74Additional Advancementsin HRG Systems
- Filters Harmonics / Noise / RF
- Monitors fundamental voltage and current for
ground faults - Avoids nuisance tripping
- Monitors 3rd harmonic voltage and current
- High Harmonics may require de-rating resistor
- Low Harmonics may indicate ground fault near
generator neutral - Zone Selective Interlocking
- Allows coordination between interlocked
protection relays on the same system - Continuously measures system impedance
- Electrical systems are perpetual systems
- System capacitance may increase causing grounding
resistor to be incorrectly sized - Undesirable, higher fault current may flow
- Transient over-voltage may occur
75Summary
- Hazards with Ungrounded Systems
- Severe transient over-voltages
- Cannot efficiently locate ground faults
- Hazards with Solidly-Grounded Systems
- Very high fault currents and time delays
- Causing severe arc blast / flash conditions
- Ground fault coordination problems
76Summary
- High-Resistance Grounded Systems
- Best Grounding Method today
- Resolves Ungrounded hazards
- Resolves Solidly-Grounded hazards
- Technology continues to make HRG Systems safer
than any other grounding method, but need help - Continue to educate and train personnel (engr and
maint.) - NETA
- Update standards and guideline that hinder HRG
- NEC
- NFPA 70E and IEEE 1584