Title: AirSense Technology Limited
1AirSense Technology Limited
HOW?
PRESENTATION
AirSense Technology Limited January 2007
2Agenda
Product Selection Installation Commissioning
Questions Answers Contacts
AirSense Technology Limited January 2007
3Products
PRODUCT
RANGE
4Stratos Series Features
- Key Features
- High sensitivity provided by laser based forward
light scatter mass detection and particle
evaluation for reliable early warning detection. - Particle sensitivity range 0.003µ to 10µ
- Industries widest sensitivity range 0.003 to 25
obs/m - Four programmable alarm thresholds (Aux,
Pre-Alarm, Fire 1 and Fire 2) - ClassiFire Perceptive Artificial Intelligence
system - Dual Technology LDD 3D3 Laser Dust Discrimination
and elimination system. - RS485 communications built in as standard for
networking and remote communications. Up to 127
detectors per loop, 1.2 km between repeaters. - RS232 built in for direct PC interface
- Powered by 24-Volt DC regulated supply.
Product Selection
5Stratos Aspirating Smoke Detectors
Wide product range for practically any application
Product Selection
6Stratos-Micra 25
Product Selection
- Key Features
- Ultra small low cost aspirating smoke detector
for easy and discreet installation. - Single sampling pipe up to 50m.
- 10 sample points
- Built-in status LEDs
- Rugged Steel Enclosure
- Docking station equipped to facilitate simple
installation and removal.
7Stratos
- Key Features
- Lightweight design for easy one-man installation.
- External air filter for ease of maintenance... no
need to declassify area for routine maintenance. - RS485 communications built in as standard for
networking and remote communications. - Single sampling pipe up to 164ft (50m).
- Up to 10 sample ports maximum
- ATEX rated EEx d IIB H2 T3. Equipment group 2
(zones 1, 2 and 3). Group gases A and B
Hydrogen.
Product Selection
8Stratos-Micra 100
- Key Features
- Ultra small and affordable aspirating smoke
detector for easy and discreet installation. - Dual sampling pipe (2 x 50m).
- 10 Sample points per pipe.
- Built-in Status LEDs
- Rugged Steel Enclosure
- Docking station equipped to facilitate simple
installation and removal.
Product Selection
9StratosHSSD
- Key Features
- Large capacity Aspirating Smoke Detector.
- Four sampling pipes up to 200m maximum total
length. - 4 x 50m or 3 x 70m or 2 x 100m
- Capacity of up to 100 Sample points, 25 per inlet
maximum. - On-board graphical display and LCD programmer
- IP-50 rated enclosure
- Available in rugged steel enclosure and as
Minimum Display model with status LEDs, no
programmer.
Product Selection
10Stratos Network Command Module
- Stratos Command Module provides a single location
display, control and interfacing option for
systems of up to 127 detectors. - The integral bargraph automatically displays the
status of the detector with the highest alarm
level to identify potential problem areas. - RS485 Communications.
- Built-in Short Isolators for optimum reliability.
- Integral Serial Interface programmable for TAP
text messages/paging or BACnet BMS
communications. - RS232 serial interface for SenseNET PC Graphical
Management System. - Optional steel enclosure for durability
- IP-50 rated enclosure
Product Selection
- Key Features
- Stratos-HSSD detector fitted with a Command
Module Network Controller. Available as stand
alone controller without detector. - Command Module allows global programming of all
detector functions simultaneously.
11Remote Display Units
Product Selection
- Mimics the displays of Stratos-HSSD and
Stratos-Micra Detectors - 26 bargraph segments with 4 separate alarm
indicators - Available in single wall mounted enclosure or in
a 19 rack enclosure accommodating up to 8 RDUs - Compatible with SenseNET bus (RS 485 data
highway) - Remote relay board option available with 4 alarms
and common fault
12Product Selection
13- Key Features
- Manages all devices centrally
- Manages 16 x loops of 127 detectors via Command
Modules - Real-time indication of alarms /definable sound
files - User definable sound files for alarm and fault
conditions - Displays maps with specific instructions
- SiteAudit logs all events in real time
- SiteScan detects all attached devices for rapid
configuration - SiteMail and SitePage for automatic email/text
alarm alerts - 4 levels of password protected access
- Full system diagnostics
- Connectivity to other manufacturers systems
- Global configuration changes
- Display full system status or historical
information at any time
Product Selection
14View ClassiFire 3D in real time
Product Selection
History List
Set site maps and warnings
Paging
Device Settings
Email
15Installation Commissioning
AirSense Technology Limited January 2007
16Commissioning Equipment Required
- Appropriate installers handbook (Supplied
on CD).
Installation Commissioning
- A laptop installed with latest version of remote
software (Supplied on CD)
- Copy of commissioning checklist.
17Commissioning List
- Correct use of a checklist will ensure a standard
commissioning procedure is carried out in every
instance and no aspects are overlooked.
Installation Commissioning
18Commissioning Equipment Required
- Appropriate installers handbook (Supplied
on CD).
Installation Commissioning
- A laptop installed with latest version of remote
software (Supplied on CD)
- Copy of commissioning checklist.
- Correctly configured serial lead
19Serial Lead
Installation Commissioning
- The serial lead used to connect the detector a PC
is referred to as a Null Modem cable, due to
its configuration
It is now common for laptops to be supplied
without a serial port, several third-party
devices are available to convert a USB port to a
serial port, we recommend the CN-116 from
Sitecom.
20Commissioning Equipment Required
- Appropriate installers handbook (Supplied
on CD).
Installation Commissioning
- A laptop installed with latest version of remote
software (Supplied on CD)
- Copy of commissioning checklist.
- Correctly configured serial lead
21Commissioning Equipment Required
Installation Commissioning
- AirSense promote the use of real smoke in order
to test detectors, Canned Smoke should not be
used to test any of our product range.
22 Stratos-HSSD 2 Mechanical Installation
The Stratos-HSSD 2 is supplied with a back plate
for ease of installation
The plate mounts to the wall using the
pre-drilled holes
Installation Commissioning
23Stratos-HSSD 2 Mechanical Installation
Inlets
The plate has pilot holes for rear pipe access,
these highlight the pitch of the pipes.
3
Exhaust
1
2
4
Installation Commissioning
24Inside the Stratos-HSSD 2 detector
Installation Commissioning
25Stratos-Micra Mechanical Installation
Exhaust
Inlet
Installation Commissioning
26Inside the Stratos-Micra 25 detector
Installation Commissioning
27Interfacing
- Various interfacing options are available. A
simple installation may only utilise the volt
free contacts supplied as standard. - Alternatively an A.P.I.C. (Addressable
programmable interface card) might be used, which
emulates a device on the main fire panel loop.
Installation Commissioning
28Interfacing
- The Alarm relays are N/O, closing on alarm
- The Fault relay is N/C, opening on fault
- The onboard relays are volt free and rated at
10VA - this equates to 400mA _at_ 24Vdc.
- It is worth noting that the current rating
stated on most beacons / sounders is the
quiescent, these devices can have in-rush
currents in excess of 3A! - It is a wise precaution to use a 47ohm resistor
in series to limit current draw.
Installation Commissioning
29Pre Power-Up checks
- Site, company and system type details details
should be noted on the checklist.
Installation Commissioning
- Isolate the detector at the main fire panel prior
to carrying out any work.
- Ensure there is sufficient access to the detector
for future maintenance.
30Sufficient Access
Installation Commissioning
- Allow an 80mm margin around the outside of the
detector, this will allow future access to the
air filter..
..the serial port.
and the detector housing.
31Pre Power-Up checks
- Site, company and system type details details
should be noted on the checklist. - Isolate the detector at the main fire panel prior
to carrying out any work. - Ensure there is sufficient access to the detector
for future maintenance. - Ensure the pipe work is correctly installed, the
exhaust bung has been removed and that all
necessary inlet bungs have been removed.
Installation Commissioning
32Pre Power-Up checks
Installation Commissioning
33Basic Configuration
- The following brief checklist outlines a basic
generic configuration of any detector in the
Stratos range. - This procedure will be adequate for most standard
installations, for more detailed programming
information refer to the relevant installers
handbook and/or technical manual.
Installation Commissioning
34Basic Configuration
Installation Commissioning
The detector can now be programmed via the front
panel
.or using a laptop via RS232
.or using a Command Module via RS485
35Basic Configuration
Installation Commissioning
Access - After clicking the detector icon the
you will be prompted to enter the access code,
the default code is 0102
36Basic Configuration
Installation Commissioning
Date Time - it is important to ensure a
correct date and time stamp on any events that
occur for future reference.
37Basic Configuration
Installation Commissioning
Alarm factor - This is the sensitivity setting
for the detector, 0 being the most sensitive
and 8 being the least sensitive.
38Fixed Scaling
It is important to understand how the sensitivity
is set, the main obstacle for reliable operation
of such a high sensitivity detection system is
the interpretation of any background pollution
either genuine smoke and /or fine particles that
would be seen as smoke
.our competitors use Fixed Scaling, this means
they determine the highest point to which the
background smoke will riseand then fix the
alarm threshold above this level
Installation Commissioning
39Fixed Sensitivity
Relative Scaling
Because Stratos-HSSD is a RELATIVELY scaled
(sensitivity) detector, the sensitivity to a FIRE
remains constant, regardless of changing ambient
conditions
Installation Commissioning
Variable Ambient Smoke Level
40Fixed Sensitivity
Relative Scaling
Our smoke density display will only show a
fluctuation above ambient or normal levels.
Installation Commissioning
Variable Ambient Smoke Level
41Installation Commissioning
42Basic Configuration
Installation Commissioning
The Alarm factor is the sensitivity setting for
the detector, 0 being the most sensitive and
8 being the least sensitive.
If you are tracking the background level very
closely (alarm factor 0) then you are providing
very high sensitivity, however nuisance alarms
may be more frequent as a result.
Conversely by setting the alarm factor to 8 the
background level is being tracked at a greater
distance, nuisance alarms will be extremely rare,
however the detector will be operating at a lower
sensitivity.
43Basic Configuration
Installation Commissioning
Auxiliary Level - The factory default value is
10, so this relay will activate after Fire unless
altered.
44Basic Configuration
Installation Commissioning
45Basic Configuration
Installation Commissioning
Battery Mains Check If the power monitoring
functions are not being used then they should be
disabled to stop faults from being generated.
46Basic Configuration
Installation Commissioning
47Basic Configuration
Installation Commissioning
..or switched manually when someone leaves the
office or activates a security alarm..
48Basic Configuration
Installation Commissioning
Reset, Test Isolate - The front panel
buttons can be enabled or disabled depending on
the environment, the reset button is disabled by
default.
.so should be enabled if you intend to have
latching alarms or faults.
49Basic Configuration
Installation Commissioning
..where a particular port is unused the sensor
should be disabled by un-ticking the box
..the ports are numbered 1 4 from left to
right.
The Stratos-HSSD 2 features individual flow
monitoring on each inlet port..
50 Basic Configuration
Installation Commissioning
if the reading is less than 30 or greater than
80 then the pipe layout may require attention
For each Inlet the actual flow is displayed,
this cannot be altered and should be approx 60 (
or - 10)
51 Basic Configuration
Installation Commissioning
The low high flow limits are set automatically
during a flow setup
The limits may also be set manually in order to
allow for larger fluctuations in flow.
52 Basic Configuration
Installation Commissioning
.or increased to reduce transport times,
altering the aspirator speed will affect current
consumption.
The aspirator speed on the Stratos-HSSD 2 may be
altered, decreased to reduce noise levels.
53FastLearn
Installation Commissioning
The detector will carry out a FastLearn for 15
minutes after being powered-up, when a filter
has been replaced or when the Alarm Factor has
been changed.. . this is indicated by scrolling
LEDs on the smoke density display or a flashing
OK LED.
54FastLearn
Installation Commissioning
During this 15 minute period the detector will
gather information.. a snap-shot of its
surrounding environment that will determine the
position of the alarm thresholds. The detector
may be tested once this period has elapsed,
however it will not reach full sensitivity for 24
hours unless Demo Mode has been initiated.
55FastLearn
Installation Commissioning
Initiating Demo Mode causes the detector to
treat the 15 minutes worth of information it has
just gathered as a full 24 hour learn. The
detector can then approximate the alarm
thresholds to a more sensitive level for the
purposes of providing a realistic demonstration
of future performance
56Basic Configuration
Installation Commissioning
Whilst a FastLearn is in progress Demo Mode
may be initiated by ticking the box and clicking
OK.
57Basic Configuration
Installation Commissioning
15 minutes, just enough time for a coffee.!
58FastLearn
Installation Commissioning
After 15 minutes the LEDs will stop scrolling
or flashing, the detector can now be
tested Once the detector has been tested the a
new FastLearn should be initiated to gather data
over a true 24 hour period.
59Questions Answers