1
AirSense Technology Limited
HOW?
PRESENTATION
AirSense Technology Limited January 2007
2
Agenda
Product Selection Installation Commissioning
Questions Answers Contacts
AirSense Technology Limited January 2007
3
Products
PRODUCT
RANGE
4
Stratos Series Features
  • Key Features
  • High sensitivity provided by laser based forward
    light scatter mass detection and particle
    evaluation for reliable early warning detection.
  • Particle sensitivity range 0.003µ to 10µ
  • Industries widest sensitivity range 0.003 to 25
    obs/m
  • Four programmable alarm thresholds (Aux,
    Pre-Alarm, Fire 1 and Fire 2)
  • ClassiFire Perceptive Artificial Intelligence
    system
  • Dual Technology LDD 3D3 Laser Dust Discrimination
    and elimination system.
  • RS485 communications built in as standard for
    networking and remote communications. Up to 127
    detectors per loop, 1.2 km between repeaters.
  • RS232 built in for direct PC interface
  • Powered by 24-Volt DC regulated supply.

Product Selection
5
Stratos Aspirating Smoke Detectors
Wide product range for practically any application
Product Selection
6
Stratos-Micra 25
Product Selection
  • Key Features
  • Ultra small low cost aspirating smoke detector
    for easy and discreet installation.
  • Single sampling pipe up to 50m.
  • 10 sample points
  • Built-in status LEDs
  • Rugged Steel Enclosure
  • Docking station equipped to facilitate simple
    installation and removal.

7
Stratos
  • Key Features
  • Lightweight design for easy one-man installation.
  • External air filter for ease of maintenance... no
    need to declassify area for routine maintenance.
  • RS485 communications built in as standard for
    networking and remote communications.
  • Single sampling pipe up to 164ft (50m).
  • Up to 10 sample ports maximum
  • ATEX rated EEx d IIB H2 T3. Equipment group 2
    (zones 1, 2 and 3). Group gases A and B
    Hydrogen.

Product Selection
8
Stratos-Micra 100
  • Key Features
  • Ultra small and affordable aspirating smoke
    detector for easy and discreet installation.
  • Dual sampling pipe (2 x 50m).
  • 10 Sample points per pipe.
  • Built-in Status LEDs
  • Rugged Steel Enclosure
  • Docking station equipped to facilitate simple
    installation and removal.

Product Selection
9
StratosHSSD
  • Key Features
  • Large capacity Aspirating Smoke Detector.
  • Four sampling pipes up to 200m maximum total
    length.
  • 4 x 50m or 3 x 70m or 2 x 100m
  • Capacity of up to 100 Sample points, 25 per inlet
    maximum.
  • On-board graphical display and LCD programmer
  • IP-50 rated enclosure
  • Available in rugged steel enclosure and as
    Minimum Display model with status LEDs, no
    programmer.

Product Selection
10
Stratos Network Command Module
  • Stratos Command Module provides a single location
    display, control and interfacing option for
    systems of up to 127 detectors.
  • The integral bargraph automatically displays the
    status of the detector with the highest alarm
    level to identify potential problem areas.
  • RS485 Communications.
  • Built-in Short Isolators for optimum reliability.
  • Integral Serial Interface programmable for TAP
    text messages/paging or BACnet BMS
    communications.
  • RS232 serial interface for SenseNET PC Graphical
    Management System.
  • Optional steel enclosure for durability
  • IP-50 rated enclosure

Product Selection
  • Key Features
  • Stratos-HSSD detector fitted with a Command
    Module Network Controller. Available as stand
    alone controller without detector.
  • Command Module allows global programming of all
    detector functions simultaneously.

11
Remote Display Units
Product Selection
  • Mimics the displays of Stratos-HSSD and
    Stratos-Micra Detectors
  • 26 bargraph segments with 4 separate alarm
    indicators
  • Available in single wall mounted enclosure or in
    a 19 rack enclosure accommodating up to 8 RDUs
  • Compatible with SenseNET bus (RS 485 data
    highway)
  • Remote relay board option available with 4 alarms
    and common fault

12
Product Selection
13
  • Key Features
  • Manages all devices centrally
  • Manages 16 x loops of 127 detectors via Command
    Modules
  • Real-time indication of alarms /definable sound
    files
  • User definable sound files for alarm and fault
    conditions
  • Displays maps with specific instructions
  • SiteAudit logs all events in real time
  • SiteScan detects all attached devices for rapid
    configuration
  • SiteMail and SitePage for automatic email/text
    alarm alerts
  • 4 levels of password protected access
  • Full system diagnostics
  • Connectivity to other manufacturers systems
  • Global configuration changes
  • Display full system status or historical
    information at any time

Product Selection
14
View ClassiFire 3D in real time
Product Selection
History List
Set site maps and warnings
Paging
Device Settings
Email
15
Installation Commissioning
AirSense Technology Limited January 2007
16
Commissioning Equipment Required
  • Appropriate installers handbook (Supplied
    on CD).

Installation Commissioning
  • A laptop installed with latest version of remote
    software (Supplied on CD)
  • Copy of commissioning checklist.

17
Commissioning List
  • Correct use of a checklist will ensure a standard
    commissioning procedure is carried out in every
    instance and no aspects are overlooked.

Installation Commissioning
18
Commissioning Equipment Required
  • Appropriate installers handbook (Supplied
    on CD).

Installation Commissioning
  • A laptop installed with latest version of remote
    software (Supplied on CD)
  • Copy of commissioning checklist.
  • Correctly configured serial lead

19
Serial Lead
Installation Commissioning
  • The serial lead used to connect the detector a PC
    is referred to as a Null Modem cable, due to
    its configuration

It is now common for laptops to be supplied
without a serial port, several third-party
devices are available to convert a USB port to a
serial port, we recommend the CN-116 from
Sitecom.
20
Commissioning Equipment Required
  • Appropriate installers handbook (Supplied
    on CD).

Installation Commissioning
  • A laptop installed with latest version of remote
    software (Supplied on CD)
  • Copy of commissioning checklist.
  • Correctly configured serial lead
  • Test apparatus

21
Commissioning Equipment Required
Installation Commissioning
  • AirSense promote the use of real smoke in order
    to test detectors, Canned Smoke should not be
    used to test any of our product range.

22

Stratos-HSSD 2 Mechanical Installation
The Stratos-HSSD 2 is supplied with a back plate
for ease of installation
The plate mounts to the wall using the
pre-drilled holes
Installation Commissioning
23
Stratos-HSSD 2 Mechanical Installation
Inlets
The plate has pilot holes for rear pipe access,
these highlight the pitch of the pipes.
3
Exhaust
1
2
4
Installation Commissioning
24
Inside the Stratos-HSSD 2 detector
Installation Commissioning
25
Stratos-Micra Mechanical Installation
Exhaust
Inlet
Installation Commissioning
26
Inside the Stratos-Micra 25 detector
Installation Commissioning
27
Interfacing
  • Various interfacing options are available. A
    simple installation may only utilise the volt
    free contacts supplied as standard.
  • Alternatively an A.P.I.C. (Addressable
    programmable interface card) might be used, which
    emulates a device on the main fire panel loop.

Installation Commissioning
  • APIC Card
  • Detector On-Board Relays

28
Interfacing
  • The Alarm relays are N/O, closing on alarm
  • The Fault relay is N/C, opening on fault
  • The onboard relays are volt free and rated at
    10VA
  • this equates to 400mA _at_ 24Vdc.
  • It is worth noting that the current rating
    stated on most beacons / sounders is the
    quiescent, these devices can have in-rush
    currents in excess of 3A!
  • It is a wise precaution to use a 47ohm resistor
    in series to limit current draw.

Installation Commissioning
29
Pre Power-Up checks
  • Site, company and system type details details
    should be noted on the checklist.

Installation Commissioning
  • Isolate the detector at the main fire panel prior
    to carrying out any work.
  • Ensure there is sufficient access to the detector
    for future maintenance.

30
Sufficient Access
Installation Commissioning
  • Allow an 80mm margin around the outside of the
    detector, this will allow future access to the
    air filter..

..the serial port.
and the detector housing.
31
Pre Power-Up checks
  • Site, company and system type details details
    should be noted on the checklist.
  • Isolate the detector at the main fire panel prior
    to carrying out any work.
  • Ensure there is sufficient access to the detector
    for future maintenance.
  • Ensure the pipe work is correctly installed, the
    exhaust bung has been removed and that all
    necessary inlet bungs have been removed.

Installation Commissioning
32
Pre Power-Up checks
Installation Commissioning
33
Basic Configuration
  • The following brief checklist outlines a basic
    generic configuration of any detector in the
    Stratos range.
  • This procedure will be adequate for most standard
    installations, for more detailed programming
    information refer to the relevant installers
    handbook and/or technical manual.

Installation Commissioning
34
Basic Configuration
Installation Commissioning
The detector can now be programmed via the front
panel
.or using a laptop via RS232
.or using a Command Module via RS485
35
Basic Configuration
Installation Commissioning
Access - After clicking the detector icon the
you will be prompted to enter the access code,
the default code is 0102
36
Basic Configuration
Installation Commissioning
Date Time - it is important to ensure a
correct date and time stamp on any events that
occur for future reference.
37
Basic Configuration
Installation Commissioning
Alarm factor - This is the sensitivity setting
for the detector, 0 being the most sensitive
and 8 being the least sensitive.
38
Fixed Scaling
It is important to understand how the sensitivity
is set, the main obstacle for reliable operation
of such a high sensitivity detection system is
the interpretation of any background pollution
either genuine smoke and /or fine particles that
would be seen as smoke
.our competitors use Fixed Scaling, this means
they determine the highest point to which the
background smoke will riseand then fix the
alarm threshold above this level
Installation Commissioning
39
Fixed Sensitivity
Relative Scaling
Because Stratos-HSSD is a RELATIVELY scaled
(sensitivity) detector, the sensitivity to a FIRE
remains constant, regardless of changing ambient
conditions
Installation Commissioning
Variable Ambient Smoke Level
40
Fixed Sensitivity
Relative Scaling
Our smoke density display will only show a
fluctuation above ambient or normal levels.
Installation Commissioning
Variable Ambient Smoke Level
41
Installation Commissioning
42
Basic Configuration
Installation Commissioning
The Alarm factor is the sensitivity setting for
the detector, 0 being the most sensitive and
8 being the least sensitive.
If you are tracking the background level very
closely (alarm factor 0) then you are providing
very high sensitivity, however nuisance alarms
may be more frequent as a result.
Conversely by setting the alarm factor to 8 the
background level is being tracked at a greater
distance, nuisance alarms will be extremely rare,
however the detector will be operating at a lower
sensitivity.
43
Basic Configuration
Installation Commissioning
Auxiliary Level - The factory default value is
10, so this relay will activate after Fire unless
altered.
44
Basic Configuration
Installation Commissioning
45
Basic Configuration
Installation Commissioning
Battery Mains Check If the power monitoring
functions are not being used then they should be
disabled to stop faults from being generated.
46
Basic Configuration
Installation Commissioning
47
Basic Configuration
Installation Commissioning
..or switched manually when someone leaves the
office or activates a security alarm..
48
Basic Configuration
Installation Commissioning
Reset, Test Isolate - The front panel
buttons can be enabled or disabled depending on
the environment, the reset button is disabled by
default.
.so should be enabled if you intend to have
latching alarms or faults.
49
Basic Configuration
Installation Commissioning
..where a particular port is unused the sensor
should be disabled by un-ticking the box
..the ports are numbered 1 4 from left to
right.
The Stratos-HSSD 2 features individual flow
monitoring on each inlet port..
50

Basic Configuration
Installation Commissioning
if the reading is less than 30 or greater than
80 then the pipe layout may require attention
For each Inlet the actual flow is displayed,
this cannot be altered and should be approx 60 (
or - 10)
51

Basic Configuration
Installation Commissioning
The low high flow limits are set automatically
during a flow setup
The limits may also be set manually in order to
allow for larger fluctuations in flow.
52

Basic Configuration
Installation Commissioning
.or increased to reduce transport times,
altering the aspirator speed will affect current
consumption.
The aspirator speed on the Stratos-HSSD 2 may be
altered, decreased to reduce noise levels.
53
FastLearn
Installation Commissioning
The detector will carry out a FastLearn for 15
minutes after being powered-up, when a filter
has been replaced or when the Alarm Factor has
been changed.. . this is indicated by scrolling
LEDs on the smoke density display or a flashing
OK LED.
54
FastLearn
Installation Commissioning
During this 15 minute period the detector will
gather information.. a snap-shot of its
surrounding environment that will determine the
position of the alarm thresholds. The detector
may be tested once this period has elapsed,
however it will not reach full sensitivity for 24
hours unless Demo Mode has been initiated.
55
FastLearn
Installation Commissioning
Initiating Demo Mode causes the detector to
treat the 15 minutes worth of information it has
just gathered as a full 24 hour learn. The
detector can then approximate the alarm
thresholds to a more sensitive level for the
purposes of providing a realistic demonstration
of future performance
56
Basic Configuration
Installation Commissioning
Whilst a FastLearn is in progress Demo Mode
may be initiated by ticking the box and clicking
OK.
57
Basic Configuration
Installation Commissioning
15 minutes, just enough time for a coffee.!
58
FastLearn
Installation Commissioning
After 15 minutes the LEDs will stop scrolling
or flashing, the detector can now be
tested Once the detector has been tested the a
new FastLearn should be initiated to gather data
over a true 24 hour period.
59
Questions Answers
THANK
YOU
60