Specview 32 Release 2.5 Enhancements
February 2008
2
Enhancements for HC900 Interface
Specview Version 2.5 Build 834 and beyond
  • HC Designer Tag Import Support (for automatic
  • database build)
  • HC900 Redundant Network Support (for C70R and
    C70 controllers)

Specview database
import
AllModbusRegisters.csv file
3
HC900 Tag Import Support
  • Supports Fixed Modbus map and Custom Modbus map
    .csv file import
  • Builds categorized Variables list for function
    blocks, tags and variables using HC Designer tag
    names
  • Interactive Instrument Views for
  • All control loops
  • The first 8 SP Programmer blocks
  • Other Function blocks (parameter list only)
  • Example Sequencer, Device Control
  • Supports Incremental Updates to Database
  • Specview checks and lists differences on file
    import

4
HC900 Tag Import Support
  • References
  • Specview User Manual Version 2.5 Build 833
  • Section 4.13 HC900 HC Designer Modbus Map
    Import
  • Specview On-Line Help
  • Under Starting SpecView and Instrument
    Definition/Detection

5
Tag Import Configuration Steps
  • Export the Fixed or Custom Modbus Map report .csv
    file from the HC Designer configuration
  • For Fixed Modbus map applications
  • In HC Designer, go to FilegtExport, click on
    FBDs, choose All Modbus Registers, rename the
    file as desired, then store in known folder.
  • For Custom map applications
  • In HC Designer, go to FilegtExport, click on
    FBDs, choose All Modbus Partitions, rename the
    file as desired, then store in known folder.

6
Tag Import Configuration Steps Fixed Map
  • Connect HC900 to the Specview application via
    Ethernet, then start Specview
  • In Specviews Configurations Found dialog,
    click on Test Comms for NEW Config and enter
    new project file name
  • In Specviews Ports and Protocols dialog, enter
    Begin and End IP address for HC900, then click on
    Start Scan button

7
Tag Import Configuration Steps Fixed Map
  • To import the Modbus map file, click on Yes for
    the following dialog
  • Browse for the AllMobusRegisters tag export
    .csv file from HC Designer, then click on Open

8
Tag Import Configuration Steps Fixed Map
  • The following will now occur
  • All Control loop, SP programmer, other function
    blocks, signal tags, and variables will be
    imported, categorized, and placed into the
    Variables list.
  • A screen (in Configuration mode) will be
    displayed with all of the tagged Instrument Views
    related to the HC900 configuration import
    (example below). Click OK to continue. This
    display can be saved if desired and viewed
    on-line as a test.

9
Tag Import Configuration Steps Fixed Map
  • The Variables list is populated as follows

All function blocks are listed by HC
Designer-assigned tag name for access to
associated parameters
Check Include Name to provide name text for
Variable selected
The Signal Tags and Variables lists show all
listed by number (for reference) and tag
name, data type pre-assigned as Analog or Boolean
(digital), read only or read/write
Uncheck Include Name to not include text
10
Tag Import Configuration Steps Custom Map
  • Steps prior to tag import
  • Add SP programmer blocks while in Fixed Modbus
    map mode (SP programmer blocks 1 8 supported)
  • After conversion to Custom Modbus map, add
    addresses for each additional control loop (or
    other function block) to a defined Modbus map
    partition with sufficient supporting parameters
    for Specview interface
  • For control loops, use Select All to add all
    control loop parameters to the map or use the
    Vista_PID.ptf template (on HC Designer CD) and
    add the LSP1 parameter (needed for writing to
    local SP)
  • Add similar blocks in contiguous addresses
    within named partition
  • Modify floating point data types as necessary
    (to unsigned 16) for digital status (does not
    apply to Signal Tags and Variables since digital
    types will be converted by Specview automatically
    as necessary)

11
Tag Import Configuration Steps Custom Map
  • Adding control loop to Custom Modbus Map in HC
    Designer (all control loop parameters)
  • Adding a control to Custom map (all paremeters)

12
Tag Import Configuration Steps Custom Map
  • Adding control loop to Custom map in HC Designer
    (using Vista_PID. ptf template plus adding LSP1)

Add
Browse and select
13
Tag Import Configuration Steps Custom Map
  • Prepare Custom Modbus map (as described in
    previous slides)
  • Follow import configuration steps shown for fixed
    map except
  • Use the All Modbus Partitions report file for a
    new Specview configuration
  • Select a specific custom map partition report
    file for import to Specview if a fixed map import
    was previously executed.

14
Tag Import Configuration Steps Custom Map
Sample Custom Map All Modbus Partitions file
import
15
Tag Import Configuration Steps
  • Adding an HC900 Controller or Updating Variables
    List
  • Select the HC900 menu, then click on Import
    HCDesigner File
  • Click on Add as new HC900, enter IP address,
    then browse for
  • All Modbus Registers or Partitions file to add
    controller to database
  • - Click on Update existing HC900, enter IP
    address, then browse for HC Designer export file
    to update the database for controller

Click choice for naming
Adds HC900 controller name to Variables
Omits controller name
16
HC900 Redundant Ethernet Network Support
  • Overview
  • Supports primary and secondary TCP/IP network IP
    addresses
  • When primary communications TCP/IP network
    fails, the communications will flip to the
    secondary network, then flip back to the primary
    network only if the secondary network fails
  • Typical failover time is within 1-2 scan updates
  • Driver commands are available for
  • Returning to the primary network once that
    network is detected to be available
  • Adjusting retries and timeouts (retry default 2
    retries)

Primary network
Secondary network
17
HC900 Redundant Ethernet Network Support
  • Technical Note Reference document
  • A Tech Note is available in the Tech Notes
    section of Specviews FTP site.
  • Go to www.specview.com, choose Tech Notes from
    the Support menu, then download
    SVD1950ModbusRedunant.pdf from the Modbus TCP
    folder.

18
HC900 Redundant Ethernet Network Support
  • To setup in Specview
  • In Configuration mode, access Variables List and
    click on Show New
  • Select IP Address Fail To instrument. In
    dialog, enter primary and secondary IP addresses
    for HC900 specified as
  • ltPrimary IP AddressgtBltSecondary IP Addressgt

19
HC900 Redundant Ethernet Network Support
  • To view active network in use
  • Place Active IP address variable on a display

20
HC900 Redundant Ethernet Network Support
  • Driver Commands (Specview Configuration mode)
  • The following driver commands can be entered into
    the commands listing for TCP/IP Com Port Setup.
    See supporting Tech Note for more detail on these
    and other commands.

For full fault tolerance
For automatic fail-back to primary network
21
HC900 Redundant Ethernet Network Support
  • Failover Options
  • Default Fail to secondary network when primary
    fails, only fail back to primary if secondary
    fails
  • Driver Command Entry None, this is the default
    case
  • Fail Back to Primary After failover to
    secondary network, monitor access to primary
    network and fail back to primary network when
    available
  • Driver Command Entry TCPFAIL2PRI 1