DER Applications and Testing - PowerPoint PPT Presentation

1 / 34
About This Presentation
Title:

DER Applications and Testing

Description:

DER Applications and Testing Ben Kroposki, PE Senior Electrical Engineer - National Renewable Energy Laboratory DER Grid Interconnection DER Power Quality Issues DER ... – PowerPoint PPT presentation

Number of Views:123
Avg rating:3.0/5.0
Slides: 35
Provided by: bkro2
Category:

less

Transcript and Presenter's Notes

Title: DER Applications and Testing


1
DER Applications and Testing
  • Ben Kroposki, PE
  • Senior Electrical Engineer - National Renewable
    Energy Laboratory

2
DER Technology Portfolio
Examples
Reciprocating Engines
Fuel Cells
Advanced Turbines
Photovoltaics
Thermally Activated Technologies
Microturbines
Wind
3
(No Transcript)
4
(No Transcript)
5
DER Grid Interconnection
6
Residential Applications
Fuel Cells or Photovoltaic Systems
The CRN Residential Fuel Cell Demonstration
Handbook serves as a comprehensive guide to
residential fuel cell technology and related
issues.
http//www.nrel.gov/docs/fy02osti/32455.pdf.
7
Residential Applications
Grid Parallel
Power Flow Power flows from the DER to the
customers dwelling and to/from the grid, both of
which are connected in parallel. Often this
arrangement is net metered.
Interconnect The DER interconnects with the grid
through a fused disconnect, which is accessible
to distribution service personnel, and an
internal disconnect under control of the power
plant. In the event of a short-term grid upset,
the inverter typically interrupts or stops
commuting. In the event of a longer upset, the
inverter opens an internal disconnect and likely
goes to idle while monitoring the grid and
waiting to reconnect after a preset time delay
after the grid returns to normal.
8
Residential Applications
Grid-Independent
Power FlowPower flows only from the DER to the
customers dwelling. Thus, the DER must meet all
dwelling loads. This requires application
preplanning and perhaps load monitoring before
installation. The DER will likely have a
substantial battery storage system charged by the
cell stack at night to supplement the cell stack
during peak daytime loads.
Interconnect The DER connects to the dwelling
through a fused disconnect and perhaps an
internal disconnect for certain fault-clearing
events.
9
Residential Applications
Dual Mode (Combination Grid Parallel and Grid
Independent)
Power Flow Power flows from the DER to the
customers dwelling and to/from the grid in
normal operation. In the event of a grid upset,
the power plant interrupts. In the event of a
serious grid event, it disconnects itself and the
dwelling from the grid and runs independently.
After a suitable delay after the grid returns to
normal, the inverter interrupts, and
grid-parallel operation is restored.
Interconnect The DER interconnects with the
grid through a fused disconnect. An internal DER
disconnect is provided for certain grid-parallel
upsets and may be provided for certain dwelling
grid-independent fault-clearing events.
10
Commercial Applications Transfer Switch
Area Electric Power System (Area EPS)
Point of Common Coupling (PCC)
PCC
PCC
Transfer Switch
Point of DR Connection
Distributed Resource (DR) Unit
Load
Load
Distributed Resource (DR) Unit
Local EPS 1
Local EPS 2
Local EPS 3
Note Dashed lines are EPS boundaries. There can
be any number of Local EPSs
11
Commercial Applications Parallel Switch
Area Electric Power System (Area EPS)
Point of Common Coupling (PCC)
PCC
PCC
Parallel Switch
Point of DR Connection
Distributed Resource (DR) Unit
Load
Load
Distributed Resource (DR) Unit
Local EPS 1
Local EPS 2
Local EPS 3
Note Dashed lines are EPS boundaries. There can
be any number of Local EPSs
12
Commercial Applications Facility Microgrid
Area Electric Power System (Area EPS)
Point of Common Coupling (PCC)
PCC
PCC
Point of DR Connection
Point of DR Connection
Distributed Resource (DR) Unit
Load
Load
Distributed Resource (DR) Unit
Local EPS 1
Local EPS 2
Local EPS 3
Note Dashed lines are EPS boundaries. There can
be any number of Local EPSs
13
Utility Applications Area EPS Microgrid
Area Electric Power System (Area EPS)
Point of Common Coupling (PCC)
PCC
PCC
Point of DR Connection
Point of DR Connection
Distributed Resource (DR) Unit
Load
Load
Distributed Resource (DR) Unit
Local EPS 1
Local EPS 2
Local EPS 3
Note Dashed lines are EPS boundaries. There can
be any number of Local EPSs
14
Utility Applications Substation DER
EPS Source
Area Electric Power System (Area EPS)
Local EPS 2
PCC
Local EPS 4
Point of DR Connection
Load
Distributed Resource (DR) Unit
Load
DR
Load(s)
Local EPS 3
15
DER Power Quality Issues
  • Sustained Interruptions DG can provide backup
    power if designed to do so. This may improve
    reliability if designed and operated properly.
  • Voltage Regulation DG can provide voltage
    regulation if allowed. This can also be a
    limiting factor as to penetration on a feeder.
  • Harmonics There are harmonic concerns with both
    rotating and inverter based DG.
  • Voltage Sag DG may be able to help keep voltage
    up, but only if allowed to do so.

16
DER Microgrids for improved reliability
17
DER-Grid Interconnection Operational Issues
  • Short circuit contribution
  • Protection coordination
  • Voltage regulation
  • Unintentional islanding
  • Grounding and overvoltages
  • --------- ------------------ -------------------
  • Interconnection issues are real and resolvable
  • e.g., specific to equipment, design, location,
    application, etc.

18
IEEE 1547 Series Standards
1547-2003 Standard for Interconnecting
Distributed Resources with Electric Power Systems
1547.1-2005 Conformance Test Procedures for
Equipment Interconnecting DR with EPS
Current Projects
Future Projects
P1547.2 Application Guide for IEEE 1547 Standard
for Interconnecting DR with EPS

DG Specifications and Performance
Interconnection System Certification Guide
P1547.3 Guide for Monitoring, Information
Exchange and Control of DR
Guide for Grid/DG Impacts Determination
P1547.4 Guide for Design, Operation, and
Integration of DR Island Systems with EPS
P1547.5 Guidelines for Interconnection of
Electric Power Sources Greater Than 10 MVA to the
Power Transmission Grid
P1547.6 Recommended Practice for Interconnecting
DR With EPS Distribution Secondary Networks
19
IEEE 1547Technical Requirements
  • General Requirements
  • Voltage Regulation
  • Integration with Area EPS Grounding
  • Synchronization
  • Secondary and Spot Networks
  • Response to Area EPS Abnormal Conditions
  • Voltage Disturbances
  • Frequency Disturbances
  • Disconnection for Faults
  • Power Quality
  • Limitation of DC Injection
  • Limitation of Voltage Flicker
  • Induced by the DR
  • Islanding
  • Inadvertent Energizing of the Area EPS
  • Monitoring
  • Isolation Device
  • Loss of Synchronism
  • Feeder Reclosing Coordination
  • Immunity Protection
  • Harmonics
  • Surge Capability

20
IEEE 1547.1 Interconnection Tests have been
incorporated into UL 1741 for product
certification
DER Interconnection Equipment Certification
Approach
  • IEEE 1547
  • Interconnection System Requirements
  • Voltage Regulation
  • Grounding
  • Disconnects
  • Monitoring
  • Islanding
  • UL 1741
  • Interconnection Equipment
  • Construction
  • Protection against risks of injury to persons
  • Rating, Marking
  • Specific DR Tests for various technologies
  • IEEE 1547.1
  • Interconnection System Testing
  • O/U Voltage
  • and Frequency
  • Synchronization
  • EMI
  • Surge Withstand
  • DC injection
  • Harmonics
  • Islanding
  • Reconnection

21
NREL DER Test Facility
22
Testing Interconnection Equipment
GE Universal Interconnection Technology (UIT)
ASCO Soft-Load Transfer Switch
  • Validation of IEEE P1547 Interconnection Standard
    Tests
  • Over/Under Voltage and Frequency Response
  • Unintentional islanding test

23
Test Results System Configuration
Unit under Test
Onan 125kW Generator
200kW Grid Simulator
Programmable Load Banks
24
Test Results IEEE 1547 Response Times
  Response to Abnormal Voltage
Response to Abnormal Frequency
25
Test Results
  • Testing Results from ASCO SLTS Overvoltage
    Magnitude Test

26
Test Results
  • Testing Results from ASCO SLTS Overvoltage Time
    Test

27
Test Results
  • Testing Results from NPS DER Switch
    Synchronization Test

Testing synchronization around a specific voltage
and frequency window Using secondary injection
testing X shows where equipment does not meet
spec This equipment was recalibrated to meet spec.
28
IEEE 1547 - Islanding
  • Unintentional Islanding - For an unintentional
    island in which the DR energizes a portion of the
    Area EPS through the PCC, the DR interconnection
    system shall detect the island and cease to
    energize the Area EPS within two seconds of the
    formation of an island.
  • Intentional Islanding - This topic is under
    consideration for future revisions of this
    standard. (IEEE 1547.4 covers this topic)

29
Test Results
  • Testing Results from ASCO SLTS Unintentional
    Islanding
  • IEEE 1547 requirement is to disconnect within 2
    seconds of island formation

30
Test Results
  • Testing Results from ASCO SLTS Unintentional
    Islanding

31
IEEE 1547 - Islanding
  • Limited DR capacity as share of customer load
    If the aggregate DR capacity is less than
    one-third of the minimum load of the Local EPS,
    it is generally agreed that, should an
    unintentional island be formed, the DR will be
    unable to continue to energize the load connected
    within the Local EPS and still maintain
    acceptable voltage and frequency. In this case,
    it is expected that that the DR itself will
    respond by various means to cease to energize the
    island. These may include excitation system
    behavior for synchronous generators, overload or
    over/underspeed sensing, or the over/undervoltage
    relays or over/Underfrequency relays which are
    required elsewhere in IEEE 1547.
  • Non-Islanding Inverter Many inverters are
    designed specifically such that they are unable
    to supply a load without the presence of the
    electrical system. The inverter, in many cases,
    will lock to the Area EPS frequency. The
    inverter controls may also be equipped with one
    of several anti-islanding means, which usually
    continually attempt to force the inverter off the
    power system frequency, such that, if the power
    system is unavailable, the inverter voltage and
    frequency will quickly deviate from nominal
    ranges to cause under/over voltage or frequency
    trips.
  • Reverse Power Protection If the DR is intended
    to supply power only to its own Local EPS, and
    not to provide power to the Area EPS across the
    PCC, reverse power relays may be installed at the
    PCC to operate isolating devices. These
    isolating devices may be the generator isolation
    device itself, or, if the DR wishes to continue
    to support the Local EPS as an intentional
    island, may be at the PCC.
  • Passive Protection Passive protection may use
    voltage and frequency relays as a means of
    anti-island protection, as detailed above. This
    passive scheme measures electrical variables at
    the PCC and detects conditions that indicate an
    island has been formed. This protection scheme
    is based on the DRs inability to satisfy a
    sudden change in load without a corresponding
    change in its voltage and/or frequency. In this
    instance, the voltage or frequency relays will
    take the unit off line. Besides under/over
    voltage and frequency relays, several means
    derived from voltage and frequency changes are
    also commonly used for anti-islanding detection,
    for example, phase or vector jump, rate of change
    of frequency.

32
IEEE 1547 - Islanding
  • Synchronous Generator Excitation System Controls
    Synchronous generators may also be equipped
    with excitation system controls that maintain a
    constant power-factor or constant power, and rely
    on the under/overvoltage or under/overfrequency
    relays to operate if the load on the generator
    does not match the generator output.
  • For example, power factor control can be used as
    an anti-islanding method. The DR is set to
    regulate at a fixed power factor. This power
    factor should be selected to be intentionally
    significantly different from the load that would
    be isolated with the DR. If an island condition
    develops, the DR will either supply too little or
    too much VAR support resulting in a high or low
    voltage condition. For example, if the load
    power factor is 0.9 and the DR is regulating to a
    power factor of 1.0, the DR will not provide
    sufficient VAR support should an island form.
    This will result in an undervoltage condition
    which in turn will cause the generator to trip
    due to low voltage (assuming standard
    undervoltage protection per IEEE 1547).
  • Active Protection Active protection will take a
    more proactive approach, and attempt to detect an
    island directly. Anti-islanding controls in an
    inverter fall into this category. In some
    cases, passive protection can be fooled if the
    generator is able to carry the load of the island
    without a substantial change in voltage or
    frequency. Some inverter manufacturers have
    added an additional active anti-islanding
    capability .
  • One class of active scheme is to use external
    devices, for example, to actively inject current
    signal with certain frequencies other than
    fundamental frequency, and then measure voltage
    at those frequencies. Islanding will be detected
    by examining the impedance changes. (e.g. ENS
    device commonly used in Germany)
  • Active schemes measure electrical variables at
    the PCC, but the response of the variables is
    checked against a deliberate variation in some
    aspects of the DR output. Active anti-islanding
    is more robust than passive, but even it cannot
    guarantee that an island will not develop in some
    rare cases. Anti-Islanding relays are available
    which continually monitor for minute momentary
    changes in the vector relationships of the
    current of voltage to detect events on the Area
    EPS which would form an unintentional island.
  • Direct Transfer Trip Direct Transfer Trip may
    also be used, and is a very active and positive
    approach to assure that the DR ceases to energize
    an unintentional island. Direct transfer trip
    involves communication equipment both on the Area
    EPS and at the DR. The specific events on the
    Area EPS will be used to send a secure reliable
    communications signal to the DR to cause the DR
    to open isolation devices as needed to satisfy
    this requirement. Implementation of direct
    transfer trip will be addressed comprehensively
    in IEEE P1547.3, a recommended practice that is
    in the early development stages.

33
References
  1. Basso, T.S. and DeBlasio, R. "IEEE P1547 Series
    of Standards for Interconnection Preprint for
    IEEE Power Engineering Society Transmission and
    Distribution 2003 Conference and Exhibition"
    NREL/CP-560-34003. Golden, CO NREL, May 2003.
  2. Basso T.S. and DeBlasio, R. IEEE 1547 Series of
    Standards Interconnection Issues. NREL Report
    No. 34882. September 2003.
  3. Kroposki, B., Basso, T. and DeBlasio, R.
    Interconnection Testing of Distributed
    Resources Preprint for 2004 PES General Meeting,
    June 2004, NREL/CP-560-35569. Golden, CO NREL.
  4. Distributed Energy Resources Interconnection
    Systems Technology Review and Research
    NREL/SR-560-32459
  5. Universal Interconnection Technology Workshop
    Proceedings NREL/BK-560-32865
  6. CRN Residential Fuel Cell Demonstration Handbook,
    http//www.nrel.gov/docs/fy02osti/32455.pdf.
  7. Ye, Z. Dame, M. Kroposki, B. (2005).
    Grid-Connected Inverter Anti-Islanding Test
    Results for General Electric Inverter-Based
    Interconnection Technology. 24 pp. NREL Report
    No. TP-560-37200. http//www.nrel.gov/docs/fy05ost
    i/37200.pdf

34
References
  1. Kroposki, B. Englebretson, S. Pink, C. Daley,
    J. Siciliano, R. Hinton, D. (2003). Validation
    of IEEE P1547.1 Interconnection Test Procedures
    ASCO 7000 Soft Load Transfer System. 52 pp. NREL
    Report No. TP-560-34870. http//www.nrel.gov/docs/
    fy04osti/34870.pdf
  2. Distributed Generation Opportunities and
    Challenges for the TD System, Michael Doyle and
    Reigh Walling, 2003 IEEE/PES Transmission and
    Distribution Conference
  3. Interconnection and Integration Studies for Wind
    Farms, Jeff Smith, 2003 IEEE/PES Transmission and
    Distribution Conference
  4. Electrical Power Systems Quality- 2nd Edition,
    Roger Dugan, Mark McGranaghan, Surya Santoso,
    Wayne Beaty, 2002, Chapter 9
  5. IEEE 1547-2003 Standard for Interconnecting
    Distributed Resources with Electric Power Systems
  6. IEEE 1547.1-2005 Standard Conformance Test
    Procedures for Equipment Interconnecting
    Distributed Resources with Electric Power Systems
  7. Lynch, J. John, V. Danial, S. M. Benedict, E.
    Vihinen, I. Kroposki, B. Pink, C. (2006).
    Flexible DER Utility Interface System Final
    Report, September 2004--May 2006. 222 pp. NREL
    Report No. TP-560-39876. http//www.nrel.gov/docs/
    fy06osti/39876.pdf
Write a Comment
User Comments (0)
About PowerShow.com