MEBS6010 -Indoor Air Quality - PowerPoint PPT Presentation

1 / 107
About This Presentation
Title:

MEBS6010 -Indoor Air Quality

Description:

MEBS6010 -Indoor Air Quality Chapter 7 Indoor Air Quality and HVAC Yuguo Li * * The effect of smoking and cooking on the daily average I/O ratios at an outdoor ... – PowerPoint PPT presentation

Number of Views:295
Avg rating:3.0/5.0
Slides: 108
Provided by: Med132
Category:

less

Transcript and Presenter's Notes

Title: MEBS6010 -Indoor Air Quality


1
MEBS6010 -Indoor Air Quality
Chapter 7 Indoor Air Quality and HVAC
  • Yuguo Li

2
Two basic air distribution systems - mixing
3
Two basic air distribution systems - Displacement
4
Basic idea
5
Air flow from these diffusers is not a jet, but a
gravity current
6
Rule of thumb
7
(No Transcript)
8
Overview of Indoor Air Quality
9
The purpose of this lecture
  • To provide practical guide for the evaluation of
    ventilation systems, control of pollutant flows
    in buildings and sources of air contaminants
    related to HVAC systems with respect to providing
    and maintaining good indoor air quality.
  • To consider the impact of outdoor air quality

10
Before
Before
After
Before
After
After
www.a-1quickservice.com/docs/duct_cleaning.php
11
clean
dirty
www.atempheating.com/ductcleaning.html
12
Topics
  • 1 Evaluation of the ventilation system
  • 2 Air movement pathways and pressure
    relationships
  • 3 Sources of air Contaminants related to HVAC
  • 4 A simple macroscopic model considering the
    effect of recirculation and outdoor air quality
  • 5 I/O ratios

13
1 Evaluation of the Ventilation System
  • A review of the occupants complaints or concerns
  • A review of the design documentation
  • The measurement of the outdoor air quantity
    entering the HVAC system
  • The measurement of delivered quantities of
    outdoor
  • A determination of air pathways through the
    building
  • Inspection for sources of air contaminants

14
Prof. Fangers approach
15
Prof. Fanger
16
Prof. Fanger
17
Prof. Fanger
18
Review of the Occupants Complaints or Concerns
  • The occupants are important sources of
    information.
  • Determine if the pattern of complaints
    corresponds to any particular pattern of HVAC
    system.
  • Distribution of the complaints by location.
  • Try to interpret the significance of the
    complaints.
  • While peoples ability to detect odors exceeds
    that of most analytical equipment, their ability
    to explain and describe these odors is typically
    not as refined.

19
Review of the Design Documentation
  • The design documentation provides the basis for
    determining the original intent of the
    specification of the HVAC system.
  • A very useful source of information is the
    Equipment Schedule.
  • Two useful calculations relate to the density of
    people in the building and the predicted supply
    air flow per square metre of occupied area of the
    building, or litre per person.

20
The Measurement of the Outdoor Air Quantity
  • An important starting point in a
    ventilation-based IAQ evaluation.
  • Two issues, the first is about the OA quantity
    entering the HVAC system, and the second is about
    the OA quantity delivered to the occupants.
  • The techniques for determining the OA quantity
    entering an HVAC system include
  • either a direct measurement of the volume of this
    air stream,
  • or measurement of the total air volume in
    combination with a determination of the portion
    of this total supply air volume that is outdoor
    air.

21
RELATIONSHIP BETWEEN OUTDOOR AIR QUANTITY AND THE
HVAC SYSTEM
  • (1) its design,
  • (2) its installation,
  • (3) its operation and
  • (4) its maintenance.

22
Design Factors Affecting Outdoor Air Quantity
Figure 1. HVAC system with fixed minimum outdoor
air, without return air fan
23
Figure 2. HVAC system with economizer control of
outdoor air quantity.
24
Table 1 Estimate of OA as a function of outdoor
air temperatures
25
Installation Factors Affecting Outdoor Air
Quantity
  • For example, in one building, the HVAC system was
    based on a packaged system located on the roof.
    In this package system, all of the wiring had
    been done at the factory except for the wiring
    for the building relief fan, which was performed
    in the field. This on-site portion of the
    installation, however, was performed incorrectly
    and the building relief fans failed to operate.
  • Other installation errors include the placement
    of VAV (variable air volume) mixing boxes upside
    down from their intended arrangement. Since the
    damper position was intended to work with gravity
    to keep it open, its being upside down led to the
    damper remaining closed when it wasn't supposed
    to be.

26
Operational Factors Affecting Outdoor Air
Quantity
  • In one building, the OA dampers were observed to
    be open only to their minimum position. It turned
    out that, unknown to his bosses, the individual
    responsible for that particular building had
    overridden the design intent of the controls of
    the HVAC system.
  • Another building, the determining factor for the
    position of the OA dampers was not the outdoor
    air temperature, but in fact was the need to keep
    a certain minimum load on the chillers.
    Therefore, numerous opportunities to utilize
    "free cooling" and increase the ventilation rate
    in the building were not taken advantage of
    because the OA dampers were being manually kept
    at their minimum position to maintain the load on
    the chiller.
  • In another building, complaints of inadequate
    ventilation were high on Mondays and Tuesdays,
    but dropped off dramatically for the rest of the
    week. - the time clock used to provide reduced
    ventilation during the weekend days was not set
    up correctly, so that Monday and Tuesday received
    the reduced condition intended for Saturdays and
    Sundays

27
Maintenance Factors Affecting Outdoor Air
Quantity
  • The maintenance issues that have the potential
    for affecting the OA quantity entering the
    dampers are more limited than those categorized
    as due to design, installation, or operation.
  • Maintenance activities are more likely to affect
    the air contaminants side of the equation rather
    than the ventilation quantity.
  • There is, however, one maintenance activity -
    that of keeping the OA intake unclogged - which
    can directly affect the OA quantity entering the
    HVAC system. Therefore, the presence of
    obstructions in grilles or screens of air intakes
    should be visually assessed. Dirty coils will
    also reduce the overall quantity of supply air
    and with it, potentially the OA quantity as well.

28
Determination of the quantity of outdoor air
entering via the outdoor air dampers
  • The actual determination of the OA quantity
    entering an AHU can be achieved by
  • either a direct measurement of the air flow,
  • or indirectly using the measurement of either the
    return air or mixed air volume plus the
    measurement of some attribute of the three air
    streams involved, the OA, RA (return air), and MA
    (mixed air).

29
Temperature-Based Determination of Percentage
Outdoor Air
30
Figure 4. Calculation of outdoor air from
temperature measurements
31
Carbon Dioxide-Based Determination of Percentage
Outdoor Air
32
Figure 7 Carbon dioxide re-circulation of
outdoor air
33
Figure 8 Carbon dioxide determination of
reentrainment.
34
Sulfur Hexafluoride-Based Determination of
Percentage Outdoor Air
35
Other pathways of outdoor air into the HVAC
equipment
  • Mechanical rooms are typically under negative
    pressure with respect to the outdoors because the
    ductwork on the suction side of the fan is not
    air-tight.

36
Infiltration and Natural Ventilation
  • Infiltration and natural ventilation are really
    one and the same phenomenon
  • The driving forces
  • Mostly neither thermally conditioned nor filtered
    (airborne pollutant treated)

37
2 Air Movement Pathways and Pressure Relationships
  • It is pressure differences that provide the
    driving forces to transport air from one location
    to another.

38
How air moves through buildings
  • Natural forces
  • Mechanical fans
  • A network of flows

39
Airflow through leakages and openings
40
A simplified model of the air flows between the
stairwell and the outside.
41
Figure 3.2 Air and smoke movement in a high-rise
building due to stack effect (a) airflow due to
stack effect, (b) where is the fire?, (c) where
is the fire?, and (d) Same as (c), but what
happened?
42
Figure 3.2 Air and smoke movement in a high-rise
building due to stack effect (a) airflow due to
stack effect, (b) fire below the neutral plane,
(c) fire above the neutral plane, and (d) fire
above the neutral plane with smoke entering a
shaft due to buoyancy.
43
Discussion air flow direction in the Metropole
Hotel
44
Discussion air flow direction in the Metropole
Hotel
45
939
938
937
936
935
934
933
932
924
Lifts
922
926
928
904
906
908
910
902
Lifts
903
907
909
911
927
929
901
905
915
917
919
931
921
923
925
46
939
938
937
936
935
934
933
932
924
Lifts
922
926
928
904
906
908
910
902
Lifts
903
907
909
911
927
929
901
905
915
917
919
931
921
923
925
47
Reentrainment of exhausts from stacks
48
Figure 11. 3-Dimensional recirculation pattern
around building
49
Solutions
  • Reducing the source strength by process
    modification
  • 2. Increasing the stack height
  • 3. Increasing the stack discharge velocity
  • 4. Relocating the stack
  • 5. Relocating the air intake
  • 6. or diluting the source with outdoor air prior
    to its release into the atmosphere

50
HVAC equipment-related pressure relationships
  • In a building with a properly functioning HVAC
    system, the maintenance of the occupied areas of
    the building at a positive pressure prevents or
    minimizes the infiltration of unconditioned air
    into the occupied areas of the building.
  • The pressurization of the occupied spaces with
    respect to the outdoors is typically achieved by
    operating the supply fan such that it attempts to
    introduce a larger volume of air into the
    building than the return air (RA) fans and
    exhaust fans are attempting to remove from the
    building.

51
Figure 12. Outdoor air intake functioning as
building exhaust.
52
Assessment techniques for identifying air
movement pathways
  • Visual assessment of the evidence
  • Test with your finger on a visible gap
  • Use of air current tubes (or any small smoke
    generators)
  • Tracer gas techniques

53
Existence of bi-directional flows
54
Any air leakage from this SARS ward?
55
Example
56
Odors from Loading Dock at Health Care Facility
Figure 14. Tracer measurement from releases at
loading dock.
57
Figure 15. Building section showing pathways from
loading dock.
58
3. Sources of air contaminants
  • The HVAC system may be a source of air
    contaminants.
  • The HVAC system may be functioning as a transfer
    mechanism to transport air contaminants from
    their source to where the people are.
  • The HVAC system may be failing to adequately
    dilute and remove the air contaminants that are
    arising from a source that is located in the
    occupied space.

59
Sources of air contaminants by location of origin
  • Air contaminants from outdoors via outdoor air
    intake
  • Air contaminants from outdoors via unintentional
    intakes
  • Air contaminants arising from within the HVAC
    system
  • Air contaminants arising from the building itself

60
Air Contaminants Arising from Outdoors
  • Air contaminants can be transported via the HVAC
    system by being captured by the outdoor air
    intake at the air handling units (AHUs).
  • Air contaminants can be transported via the HVAC
    system by being captured via less obvious
    pathways into the HVAC system, such as via the
    mechanical room or somehow into the return flow
    to an AHU.
  • Air contaminants can be transported directly to
    an occupied area by infiltration through the
    building shell.

61
Air Contaminants Entering at the Outdoor Air
Intake
  • If the air intakes are situated near the top of
    the building, the sources to be concerned about
    include cooling towers, plumbing vents, stagnant
    roof puddles?? , and building exhausts, such as
    from kitchens or laboratory fume hoods.
  • For lower-level air intakes, this list of
    potential sources includes vehicle emissions from
    roadways, parking lots, garages, loading docks,
    dumpsters??? , trash compactors, etc.
  • For below-grade air intakes, those located in
    areaways, there is also the potential for
    microbial contamination from decaying leaf litter
    or even pigeon droppings.

62
Others
  • Air Contaminants Entering via Unintentional Air
    Intakes
  • Air Contaminants Entering via Infiltration

63
Air Contaminants Arising from within the HVAC
System
  • Outdoor Air Intake Chamber
  • Air Filters
  • Condensate Drain Pan
  • Heat Exchangers
  • Supply Air Fan
  • Internal Duct Liners

64
Air Contaminants Arising from Activities in the
Building
  • Air contaminants from construction or renovation
  • Air contaminants from building support activities
  • Air contaminants arising from maintenance of the
    HVAC system
  • Air contaminants arising from maintenance of the
    building

65
4. A Simple Macrosopic Model
66
Solution
  • Questions
  • What happens if the infiltration rate is very
    high?
  • Which parameter is important a, K, n or nr

67
Table 1. Occupant and MVAC details for the three
measured offices
68
Table 2. Operation modes of air-conditioning
systems in Office A
69
Measured concentration profile of carbon dioxide
during three consecutive working days in the two
tested offices in Hong Kong.
70
Measured concentration profile of respirable
suspended particles during three consecutive
working days in the two tested offices in Hong
Kong.
71
Measured concentration profile of carbon dioxide
during three consecutive working days in Office A
with different operation modes of the
air-conditioning system.
72
Measured concentration profile of respirable
suspended particles during three consecutive
working days in Office A with different operation
modes of the air-conditioning system.
73
Table 4. Parameters used in the office model
study
74
Three cases
  • Case 1 high recirculation flow rate (4 ACH),
    high infiltration flow rate (0.4 ACH).
  • Case 2 low recirculation flow rate (2 ACH),
    high infiltration flow rate (0.4 ACH).
  • Case 3 high recirculation flow rate (4 ACH),
    low air infiltration flow rate (0.1 ACH).

75
Hourly averaged indoor particulate concentrations
in an office building with mixed-mode
air-conditioning at a constant outdoor PM10
particle concentration of 100 mg/m3.
76
5. I/O Ratios
77
  • For pollutants predominantly generated outdoors,
    I/O is determined by the filtration(1-penetration
    ) efficiency, which can be anything less than 1.
  • For pollutants predominantly generated indoors,
    I/O is determined by the source strength and the
    ventilation rate.
  • For pollutants generated both indoors and
    outdoors, I/O is determined by the combined
    effects of filtration efficiency, indoor source
    strength and the ventilation rate.

78
Particulate Matters
79
(No Transcript)
80
Sulphur dioxide
81
Carbon monoxide
82
Carbon dioxide
83
Nitrogen dioxide
84
Formaldehyde
85
I/O ratios - summary
  • Particles 0.5-2.5
  • SO2 0.5-0.9
  • CO 1.0-2.0
  • CO2 1.5-3.0
  • NO2 0.7-1.4
  • Formaldehyde 5-30

86
3. Effect of Natural Ventilation on Indoor
Particle Concentrations
  • When to open windows???

Exfiltration removal
Penetration
Other sinks
Deposition
Indoor source
Resuspension
87
Macroscopic equation for a building
88
Balance-point outdoor concentration
89
(No Transcript)
90
(No Transcript)
91
Parameters used in the model study for I/O and
I/O concentration relationship
92
Buildings with no activity and without indoor
sources
93
Buildings with normal activity and without major
indoor sources
94
I/Os for buildings (B) with normal human activity
and without major indoor sources.
95
Buildings with normal activity and major indoor
sources
96
The effect of smoking and cooking on the daily
average I/O ratios at an outdoor PM10
concentration of (a) 15 µg/m3 (b) 25 µg/m3 (c)
50 µg/m3 and (d) 100 µg/m3.
97
The effect of smoking and cooking on the daily
average I/O ratios at an outdoor PM10
concentration of (a) 15 µg/m3 (b) 25 µg/m3 (c)
50 µg/m3 and (d) 100 µg/m3.
98
The effect of smoking and cooking on the daily
average I/O ratios at an outdoor PM10
concentration of (a) 15 µg/m3 (b) 25 µg/m3 (c)
50 µg/m3 and (d) 100 µg/m3.
99
The effect of smoking and cooking on the daily
average I/O ratios at an outdoor PM10
concentration of (a) 15 µg/m3 (b) 25 µg/m3 (c)
50 µg/m3 and (d) 100 µg/m3.
100
(No Transcript)
101
(No Transcript)
102
(No Transcript)
103
(No Transcript)
104
(No Transcript)
105
(No Transcript)
106
(No Transcript)
107
Topics IAQ and HVAC
1 Evaluation of the Ventilation System 2 Air
Movement Pathways and Pressure Relationships 3
Sources of Air Contaminants related to HVAC 4 A
Simple Macroscopic Model considering the effect
of recirculation
Write a Comment
User Comments (0)
About PowerShow.com