Title: SERVICE PROCEDURE
1SERVICE PROCEDURE
- Airflow measurement
- System charging
- Performance measurement
2Airflow measurement
- An accurate airflow measurement must be
performed before the system can be properly
charged with refrigerant or before any attempt is
made to measure performance.
3Airflow measurement
- BTUH (OUTPUT)
- CFM TEMP DIFFERENCE X 1.08
4Measurement Methods
- power measurement - watt-hour meter
- electric resistance heat and heat pumps
- power measurement - volt-ampere
- electric resistance heat
- clocking a gas meter
- natural gas furnaces
- calculating input by orifice capicity
- propane gas furnaces
- total static pressure
5(No Transcript)
6WATT-HOUR METER
- Power input measurements, by the watt-hour meter
require power interruption to all appliances in
the structure except the indoor fan motor and
electric heaters. - Do not turn off power to
- Life support devises
- Appliances subject to damage from power
interruption
7WATT-HOUR METER
- Set the thermostat to heat or emergency heat and
adjust the setpoint to 90 degrees. - Locate the watt-hour meter serving the structure.
- Clock the black mark on the meter disc for 20
revolutions using a stop watch or the second hand
on your wrist watch.
8Power Input Formula
- Revolutions x KH factor x 3.6
- KW (KILOWATT) INPUT
- Seconds
- 20 revolutions
- kh 7.2
- 65 seconds
9Power Input Formula
-
- 20 rev x 7.2 kh x 3.6 518.4
- KW 7.97 kw
- 65 65
101 KW 3413 BTU PER HOUR
- 7.97 kw x 3413 27,202 btuh (input)
- electric resistance heat is 100 effecient
- input output
11Take Return Air Temperature Measurement as Close
to Equipment as Possible
12 Do NOT Take Temperature Measurement in the Line
of Sight of Heat Source.
13Take an Average of ALL Supply Duct Temperatures
14Use a Calibrated Thermometer to Measure
Temperature.
15Use the Same Thermometer for ALL Temperature
Measurements
16Airflow measurement
- BTUH (OUTPUT)
- CFM TEMP DIFFERENCE X 1.08
- EXAMPLE
- 27,202 BTUH (output)
- 27 degrees delta T
17Airflow measurement
- 27,202 BTUH 27,202 BTUH
- CFM 933 CFM 27 X 1.08
29.16
18Measurement Methods
- power measurement - volt-ampere
- electric resistance heat
19POWER MEASUREMENT VOLT-AMPERE
- set the thermostat to the heat or emergency heat
mode, in the case of a heat pump, so that only
the resistance heaters and the fan motor are
activiated. - measure the applied voltage to the resistance
heaters while they are operating. - measure the current draw for each circuit if more
than one and add them together. - measure the temperature difference entering and
leaving the air handler.
20POWER MEASUREMENT VOLT-AMPERE
- multiply the applied volts times the total
current draw (amperes) - VOLTS X AMPERES WATTS
- BTUH (OUTPUT) WATTS X 3.413
21Measurement Methods
- Clocking a gas meter
- Natural gas furnaces
222 cubic feet per revolution
23GAS FURNACE INPUT
- make sure no other appliances are on during the
test. - set the thermostat to heat mode and 90 degrees.
- record the seconds required for one revolution of
the 2 cubic foot dial on the gas meter. - determine the gas flow rate in cubic feet per
hour from the following equation or use a gas
flow table.
24GAS FURNACE INPUT
- 2 cu. feet per
revolution x 3600 - cu. ft per hour
-
25GAS FURNACE INPUT
- 2 cu. feet per
revolution x 3600 - cu. ft per hour
- time (in seconds)
per revolution
26GAS FURNACE INPUT
- 2 cu. feet per
revolution x 3600 - cu. ft per hour
- time (in seconds)
per revolution - example 1 rev. (2cu.ft. dial) 60 seconds
27GAS FURNACE INPUT
- 2 cu. ft. per
revolution x 3600 - cu. feet per hour
-
60 - 2 x 3600
7200 - cu. feet per hour
120 CFH - 60
60
2860 SECONDS
120 CFH
29GAS FURNACE INPUT
- BTUH HEAT CONTENT X CUBIC FOOT/HOUR
- BTUH 1000 BTU X 120 CFH 120,000 BTUH (INPUT)
- BTUH (OUTPUT) BTUH (INPUT) X EFFECIENCY
- USE A MIN. OF 80 EFFICIENCY FOR NAT. GAS
- USE FURNACE AFUE EFFECIENCY IF HIGHER THAN 80
30GAS FURNACE INPUT
- 120,000 BTUH X 92
- CFM
- 55 X 1.08
- 110,400 BTUH (OUTPUT)
- CFM
1858 CFM - 59.4
-
31Measurement Methods
- calculating input by orifice capacity
- propane gas furnaces
32CALCULATING CFM AND INPUT BY ORIFICE CAPACITY
- determine the burners orifice size.
- count the number of orifices in the furnace.
- set the gas valves outlet manifold pressure to 11
inches of water column. - set the thermostat to heat mode and 90 degrees.
- measure the temperature difference entering and
leaving the furnace.
33CALCULATING CFM AND INPUT BY ORIFICE CAPACITY
- determine the btu per hour input for the selected
orifice size using table f-2 in apendix f of the
national fuel gas code. - multiply the btu per hour input times the number
of orifices counted in the furnace. - multiply the btu per hour input times the furnace
effeciency (minimum 80).
34table F-2
35Measurement Methods
- total external static pressure
36STATIC PRESSURE
- Definition
- The pressure measured above or below
atmospheric pressure created by the blower
independant of air velocity. It is exerted in all
direction to the inside walls of the ductwork and
is measured at a 90 degree angle to the airflow.
37(No Transcript)
38Measure return static pressure close to air
handler or furnace cabinet.
messure return static pressure as close to air
handler or furnace cabinet as possible
39Measure supply static pressure downstream of all
pressure drops. Average readings where turbulant
airrflow is present
40PRODUCT DATATWEO48C140B - BAY96X1415PUB
22-1298-03 PAGE 8
- EXAMPLE
- Measured external static pressure .5 In. W.C.
- Blower set on high speed tap
41Product DataTWE048C140B - BAY96X1415
- EXAMPLE
- Measured external static pressure .5 In. W.C.
- Pressure drop accross heater .13 In. W.C.
- Final static pressure .63
- Airflow approx. 1550 CFM
42TUD100C948H - TXC049C4HPB
- EXAMPLE
- Measured external static pressure .30 In. W.C.
- Blower set on black - high speed tap
43Product Data TUD100C948H - TXC049C4HPB
- EXAMPLE
- Measured external static pressure .30 In. W.C.
- Pressure drop accross coil .30 In. W.C.
- Final total external static pressure .60 In.
W.C. - Blower set on black - high speed tap
- Airflow 1595 CFM
44Product Data TUD100C948H
- EXAMPLE
- Temperature rise 47 degrees
- Airflow 1550 CFM