SERVICE PROCEDURE - PowerPoint PPT Presentation

About This Presentation
Title:

SERVICE PROCEDURE

Description:

... volt-ampere electric resistance heat clocking a gas meter natural gas furnaces calculating input by orifice capicity propane gas furnaces total static ... – PowerPoint PPT presentation

Number of Views:69
Avg rating:3.0/5.0
Slides: 45
Provided by: RhamyMo
Category:

less

Transcript and Presenter's Notes

Title: SERVICE PROCEDURE


1
SERVICE PROCEDURE
  • Airflow measurement
  • System charging
  • Performance measurement

2
Airflow measurement
  • An accurate airflow measurement must be
    performed before the system can be properly
    charged with refrigerant or before any attempt is
    made to measure performance.

3
Airflow measurement
  • BTUH (OUTPUT)
  • CFM TEMP DIFFERENCE X 1.08

4
Measurement Methods
  • power measurement - watt-hour meter
  • electric resistance heat and heat pumps
  • power measurement - volt-ampere
  • electric resistance heat
  • clocking a gas meter
  • natural gas furnaces
  • calculating input by orifice capicity
  • propane gas furnaces
  • total static pressure

5
(No Transcript)
6
WATT-HOUR METER
  • Power input measurements, by the watt-hour meter
    require power interruption to all appliances in
    the structure except the indoor fan motor and
    electric heaters.
  • Do not turn off power to
  • Life support devises
  • Appliances subject to damage from power
    interruption

7
WATT-HOUR METER
  • Set the thermostat to heat or emergency heat and
    adjust the setpoint to 90 degrees.
  • Locate the watt-hour meter serving the structure.
  • Clock the black mark on the meter disc for 20
    revolutions using a stop watch or the second hand
    on your wrist watch.

8
Power Input Formula
  • Revolutions x KH factor x 3.6
  • KW (KILOWATT) INPUT
  • Seconds
  • 20 revolutions
  • kh 7.2
  • 65 seconds

9
Power Input Formula
  • 20 rev x 7.2 kh x 3.6 518.4
  • KW 7.97 kw
  • 65 65

10
1 KW 3413 BTU PER HOUR
  • 7.97 kw x 3413 27,202 btuh (input)
  • electric resistance heat is 100 effecient
  • input output

11
Take Return Air Temperature Measurement as Close
to Equipment as Possible
12
Do NOT Take Temperature Measurement in the Line
of Sight of Heat Source.
13
Take an Average of ALL Supply Duct Temperatures
14
Use a Calibrated Thermometer to Measure
Temperature.
15
Use the Same Thermometer for ALL Temperature
Measurements
16
Airflow measurement
  • BTUH (OUTPUT)
  • CFM TEMP DIFFERENCE X 1.08
  • EXAMPLE
  • 27,202 BTUH (output)
  • 27 degrees delta T

17
Airflow measurement
  • 27,202 BTUH 27,202 BTUH
  • CFM 933 CFM 27 X 1.08
    29.16

18
Measurement Methods
  • power measurement - volt-ampere
  • electric resistance heat

19
POWER MEASUREMENT VOLT-AMPERE
  • set the thermostat to the heat or emergency heat
    mode, in the case of a heat pump, so that only
    the resistance heaters and the fan motor are
    activiated.
  • measure the applied voltage to the resistance
    heaters while they are operating.
  • measure the current draw for each circuit if more
    than one and add them together.
  • measure the temperature difference entering and
    leaving the air handler.

20
POWER MEASUREMENT VOLT-AMPERE
  • multiply the applied volts times the total
    current draw (amperes)
  • VOLTS X AMPERES WATTS
  • BTUH (OUTPUT) WATTS X 3.413

21
Measurement Methods
  • Clocking a gas meter
  • Natural gas furnaces

22
2 cubic feet per revolution
23
GAS FURNACE INPUT
  • make sure no other appliances are on during the
    test.
  • set the thermostat to heat mode and 90 degrees.
  • record the seconds required for one revolution of
    the 2 cubic foot dial on the gas meter.
  • determine the gas flow rate in cubic feet per
    hour from the following equation or use a gas
    flow table.

24
GAS FURNACE INPUT
  • 2 cu. feet per
    revolution x 3600
  • cu. ft per hour

25
GAS FURNACE INPUT
  • 2 cu. feet per
    revolution x 3600
  • cu. ft per hour
  • time (in seconds)
    per revolution

26
GAS FURNACE INPUT
  • 2 cu. feet per
    revolution x 3600
  • cu. ft per hour
  • time (in seconds)
    per revolution
  • example 1 rev. (2cu.ft. dial) 60 seconds

27
GAS FURNACE INPUT
  • 2 cu. ft. per
    revolution x 3600
  • cu. feet per hour

  • 60
  • 2 x 3600
    7200
  • cu. feet per hour
    120 CFH
  • 60
    60

28
60 SECONDS
120 CFH
29
GAS FURNACE INPUT
  • BTUH HEAT CONTENT X CUBIC FOOT/HOUR
  • BTUH 1000 BTU X 120 CFH 120,000 BTUH (INPUT)
  • BTUH (OUTPUT) BTUH (INPUT) X EFFECIENCY
  • USE A MIN. OF 80 EFFICIENCY FOR NAT. GAS
  • USE FURNACE AFUE EFFECIENCY IF HIGHER THAN 80

30
GAS FURNACE INPUT
  • 120,000 BTUH X 92
  • CFM
  • 55 X 1.08
  • 110,400 BTUH (OUTPUT)
  • CFM
    1858 CFM
  • 59.4

31
Measurement Methods
  • calculating input by orifice capacity
  • propane gas furnaces

32
CALCULATING CFM AND INPUT BY ORIFICE CAPACITY
  • determine the burners orifice size.
  • count the number of orifices in the furnace.
  • set the gas valves outlet manifold pressure to 11
    inches of water column.
  • set the thermostat to heat mode and 90 degrees.
  • measure the temperature difference entering and
    leaving the furnace.

33
CALCULATING CFM AND INPUT BY ORIFICE CAPACITY
  • determine the btu per hour input for the selected
    orifice size using table f-2 in apendix f of the
    national fuel gas code.
  • multiply the btu per hour input times the number
    of orifices counted in the furnace.
  • multiply the btu per hour input times the furnace
    effeciency (minimum 80).

34
table F-2
35
Measurement Methods
  • total external static pressure

36
STATIC PRESSURE
  • Definition
  • The pressure measured above or below
    atmospheric pressure created by the blower
    independant of air velocity. It is exerted in all
    direction to the inside walls of the ductwork and
    is measured at a 90 degree angle to the airflow.

37
(No Transcript)
38
Measure return static pressure close to air
handler or furnace cabinet.
messure return static pressure as close to air
handler or furnace cabinet as possible
39
Measure supply static pressure downstream of all
pressure drops. Average readings where turbulant
airrflow is present
40
PRODUCT DATATWEO48C140B - BAY96X1415PUB
22-1298-03 PAGE 8
  • EXAMPLE
  • Measured external static pressure .5 In. W.C.
  • Blower set on high speed tap

41
Product DataTWE048C140B - BAY96X1415
  • EXAMPLE
  • Measured external static pressure .5 In. W.C.
  • Pressure drop accross heater .13 In. W.C.
  • Final static pressure .63
  • Airflow approx. 1550 CFM

42
TUD100C948H - TXC049C4HPB
  • EXAMPLE
  • Measured external static pressure .30 In. W.C.
  • Blower set on black - high speed tap

43
Product Data TUD100C948H - TXC049C4HPB
  • EXAMPLE
  • Measured external static pressure .30 In. W.C.
  • Pressure drop accross coil .30 In. W.C.
  • Final total external static pressure .60 In.
    W.C.
  • Blower set on black - high speed tap
  • Airflow 1595 CFM

44
Product Data TUD100C948H
  • EXAMPLE
  • Temperature rise 47 degrees
  • Airflow 1550 CFM
Write a Comment
User Comments (0)
About PowerShow.com