Title: Heating and Air Conditioning I
1Heating and Air Conditioning I
- Principles of Heating, Ventilating and Air
Conditioning - R.H. Howell, H.J. Sauer, and W.J. Coad
- ASHRAE, 2005
basic textbook/reference material For ME 421 John
P. Renie Adjunct Professor Spring 2009
2Chapter 5 Design Conditions
- This chapter covers the fundamental elements that
accompany the load calculations for sizing
heating and cooling systems. This includes the
estimation of the outside air quantities and the
evaluation of the overall heat transfer
coefficient for building components. - Basic components of heating and cooling loads
- Transmission
- Solar Radiation
- Lights
- Power
- Infiltration (uncontrolled)
- Fresh Air (controlled)
- People
- Appliances
- Material in and out
- First four terms include Q
- Last five includes Q and mwater
3Chapter 5 Design Conditions
- General Considerations
- Knowledge of thermal insulation and thermal
behavior of materials - Flowing fluids carry heat and moisture
- Heating and cooling include simultaneous transfer
of heat and mass - Humidification and dehumidification depends on
ventilation and other sources of moisture gain
and loss. - Outdoor Air Load Components
- Outdoor air flows through building dilute and
remove indoor air contaminants significant
portion of total space load - Natural infiltration in addition to intentional
mechanical ventilation - Ventilation (both natural and mechanical) versus
infiltration - Air leakage into and out (exfiltration) due to
pressure difference - Modern building usually over pressurized
- Modern building not desirable to have open
windows - Residence building reliant on infiltration and
natural ventilation
4Chapter 5 Design Conditions
- Outdoor Air Load Components
- Small exhaust fans code (condensation?)
- ASHRAE Standard 62 guidance on ventilation and
indoor air quality - Ventilation Rate Procedure
- Control of six pollutants
- Outdoor air supply gt minimums (5 cfm per person
and 0.06 cfm/ft2) - Indoor Air Quality Procedure
- Nine pollutants indoor maintained below standard
level - Subjective (0.5 AC/hr) local codes
- Terminolgy
- Air handling unit (AHU) Figure 5-2
- Return air (ra)
- Exhaust air (ea)
- Recirculated air (ca)
- Outside air (oa) not fresh outside air
fraction Xoa or percent - Mixed air (ma)
- Supply air (sa)
- Bypass air (ba)
5Chapter 5 Design Conditions
6Chapter 5 Design Conditions
- Outdoor Air Load Components.
- Terminolgy
- Makeup air unit (MAU) all air is outside
- Outside air
- Large part of the total space conditioning
(heating, cooling, humidification, and
dehumidification) 20 to 40 - Sensible heating qs Q r cp Dt
- Latent heating qL Q r hfg DW
- Dehumidification in summer
- Humidification in winter
- Infiltration
- Air leakage through cracks and interstices around
windows and doors, and through the floors and
walls depends on construction, building
condition - Pressure difference between indoor and outdoor
caused by wind or differences in density
chimney or stack effect also differences in
temperature
7Chapter 5 Design Conditions
- Outdoor Air Load Components.
- Estimation of the air infiltration
- Crack method measured leakage characteristics
of the building components - Air change method (simplicity)
- Assumption of the number of air changes per hour
(ACH) that a space experiences - Q ACH x VOL/60 where VOL is gross volume of
space - Table 5-1 Change Rates as Function of
Airtightness - Outdoor design temperature
- Tight/Medium/Loose
- Figure 5-3 Building Pressure due to Wind Effects
- Impossible to accurately predict infiltration
from theory alone because of the many unknowns.
However, semi-empirical expressions can be used
to estimate infiltration rate. - Leakage function infiltration cause by pressure
difference - Q CD A (2 Dp/r)n
- Where CD is discharge coefficient (geometry and
Reynolds number) - Dp Dps Dpw Dpp (stack, wind, building
pressurization)
8Chapter 5 Design Conditions
- Outdoor Air Load Components
9Chapter 5 Design Conditions
- Outdoor Air Load Components
10Chapter 5 Design Conditions
- Outdoor Air Load Components.
- Estimation of the air infiltration
- Stack effect occurs when air densities are
different on the inside and outside of the
building density decreases with increasing
temperature - Winter lower outside temperature at higher
pressure than inside - Summer cooler air inside air infiltrates at
top and flows downward - Neutral axis
- Dps 0.52 pb h (1/To) (1/Ti) where pb is
barometric pressure - Wind velocity effect (velocity pressure)
- Dpw 0.5 Cp r Vw2
- Figure 5-5 gives average pressure coefficients
for tall buildings - Building pressurization depends on design and
operation of the HVAC system. - Positive pressurization causes less infiltration
from stack and wind effects - Looking at crack coefficient equation - Q K A
(Dp)n - With A is wall area and K is leakage coefficient
- Table 5-2 Curtain Wall Leakage Coefficients
Figure 5-6 - Tight (K 0.22), Average (K 0.66), and Loose
(K 1.30)
11Chapter 5 Design Conditions
- Outdoor Air Load Components
12Chapter 5 Design Conditions
- Outdoor Air Load Components
13Chapter 5 Design Conditions
- Outdoor Air Load Components
14Chapter 5 Design Conditions
- Outdoor Air Load Components
15Chapter 5 Design Conditions
- Outdoor Air Load Components.
- Estimation of the air infiltration
- Typical infiltrations values for North America
residential housing varies by order of
magnitude - Figure 5-7 Histogram of Infiltration Values New
Construction - Figure 5-8 Histogram of Infiltration Values
Low-Income Construction - Commercial building envelops are thought to be
nearly airtight. - At 0.30 in water 0.1 to 0.6 ACH
- Regression equation for rate (I ACH) based on
Dt and V - I K1 K2 Dt K3 V
- Not appropriate for simulations
- Multi-cell modeling complexity
- Residential single zone effective leakage area
at 0.016 inch water - Q AL (CS Dt CW V2)0.5
- Cw based on shielding class (Table 5-4) wind
coefficient Table 5-6 - Cs values based on number of stories (Table 5-5)
stack coefficient - Commercial doors different characteristics
swinging door Figure 5-9 - Figure 5-10 through 5-14 different styles, with
traffic, etc.
16Chapter 5 Design Conditions
- Outdoor Air Load Components
17Chapter 5 Design Conditions
- Outdoor Air Load Components
18Chapter 5 Design Conditions
- Outdoor Air Load Components
19Chapter 5 Design Conditions
- Outdoor Air Load Components
20Chapter 5 Design Conditions
- Outdoor Air Load Components.
- Ventilation Air
- Acceptable Indoor Air Quality (IAQ) debated for
years - Control of moisture, carbon dioxide, odors,
tobacco smoke - Additional pollutants not generated by occupants
Table 5-7 - Ventilation rate procedure meet outside air
quality standards Table 5-8 - Ventilation effectiveness ability to remove
internally generated pollutants - See Table 5-9 Minimum Ventilation Rates in
Breathing Zone - Indoor air quality procedure amount of outdoor
air ay be reduced by recirculating air which
offending contaminates have been removed or
converted to less objectionable forms - Figure 5-15
- Nomenclature (C contaminant concentration, Fr
reduction factor, N contaminate generation
rate, R recirculation rate) - Filter placement
- Variable air volume (VAV) systems
- See Figure 5-16 for required outdoor air with
recirculation and filtration. - See Example 5-3 Chicago fast-food cafeteria
21Chapter 5 Design Conditions
- Outdoor Air Load Components
22Chapter 5 Design Conditions
- Outdoor Air Load Components
23Chapter 5 Design Conditions
- Outdoor Air Load Components
24Chapter 5 Design Conditions
- Outdoor Air Load Components
25Chapter 5 Design Conditions
- Outdoor Air Load Components
26Chapter 5 Design Conditions
- Outdoor Air Load Components
27Chapter 5 Design Conditions
- Outdoor Air Load Components
28Chapter 5 Design Conditions
- Outdoor Air Load Components
29Chapter 5 Design Conditions
- Outdoor Air Load Components
30Chapter 5 Design Conditions
- Outdoor Air Load Components
31Chapter 5 Design Conditions
- Outdoor Air Load Components - Example
32Chapter 5 Design Conditions
- Outdoor Air Load Components - Example
33Chapter 5 Design Conditions
- Heat Transfer Coefficients
- Modes of heat transfer (driven by DT)
- Conduction transfer of heat through molecular
motion - Convection enhancement of conduction through
motion - Radiation electromagnetic radiation between
surfaces at DT - U-Factor or R-value resistance to flow of
energy - Thermal resistance of building materials (Table
5-11) - Apparent thermal conductivity
34Chapter 5 Design Conditions
- Heat Transfer Coefficients
- Calculation of U requires
- Apparent thermal conductivity and thickness of
material - Thermal conductance of non-homogeneous material
- Surface conductance of surfaces
- Conductance of air spaces
- Surface Conductance
- Combined effects of radiation, convection, and
conduction - Surface properties (reflectivity, emissivity,
roughness) - Geometry, viewing angles,
- Flow behavior, etc.
- Other factors
- Workmanship
- Air-tightness
- Irregular areas, shading
- Shrinkage, settling, compression,etc.
35Chapter 5 Design Conditions
36Chapter 5 Design Conditions
- Surface Conductances and Resistances
37Chapter 5 Design Conditions
- Emittance Values of Surfaces and Airspaces
38Chapter 5 Design Conditions
- Thermal Resistances of Plane Airspaces
39Chapter 5 Design Conditions
- Thermal Properties of Common Building Materials
(pgs. 123-127)
40Chapter 5 Design Conditions
- Determining U-factors
- Total resistance (both conductances and air film)
U 1/Rtot - Parallel heat paths
- Add the U factors (on a percentage basis)
- Unequal areas (pitched roof and ceiling areas)
- Windows and doors - Tables 5-16 and 5-17
41Chapter 5 Design Conditions
42Chapter 5 Design Conditions
- Determining U-factors fenestration products
43Chapter 5 Design Conditions
- Determining U-factors - Doors
44Chapter 5 Design Conditions
- The Overall Thermal Transmittance
45Chapter 5 Design Conditions
- Calculating Surface Temperatures
- Voltage divider network due to resistances
driving DT - Account for temperature effect on the resistance
of material - Look at example of structure wall
46Chapter 5 Design Conditions
- Calculating Surface Temperatures
47Chapter 5 Design Conditions
- Example 5-3 Determining Uoverall
48Chapter 5 Design Conditions
- Example 5-5 Determining Uoverall
49Chapter 5 Design Conditions
- Example 5-5 Determining Uoverall
50Chapter 5 Design Conditions
- Example 5-5 Determining Uoverall
51Chapter 5 Design Conditions
- Example 5-5 Determining Uoverall