Title: Circulating Water System
1This presentation is designed to provide you the
information you need to understand and operate
the Circulating Water System. You should view
all slides and read and study the information
presented. The presentation slides are advanced
by clicking on the button.
You can also advance to a selected section by
using the topic buttons..
2In this module we will
- Describe the function of the Circulating Water
System. - Describe the flow paths and major components
associated with the Circulating Water System. - Describe the Circulating Water System process
control loops and associated methods of control. - Describe the steps required to prepare for and
startup the Circulating Water System. - Describe the steps taken during normal operation
of the Circulating Water System. - Describe the steps required to shut down the
Circulating Water System.
3Circulating Water System Function
4The Circulating Water System Condenses Low
Pressure Turbine Exhaust Steam.
5Cooling Tower
6Flow Path
7Circulating Water System Flow Path
8Cooling Tower
9Circulating Water System Data
10Review Questions
Click to Review
What is the function of the Circulating Water
System?
What process is used to realease the heat from
the Circulating water in the Cooling Tower?
Click to Review
How is the Circulating Water cooled as it flows
through the Cooling Tower?
Click to Review
When you are sure you can correctly answer these
question click the Button to
continue
11Major Components
12Circulating Water Pumps
13Circulating Water Pumps
14Circulating Water Pumps Valves
15Circulating Water Pumps Data
16Condenser
Extraction Piping
LP Heater
Inlet Waterbox
Outlet Waterbox
Waterbox Vent
Tubes
Circ Water Inlet
Circ Water Outlet
Tube Sheet
Hotwell
17Condenser Waterbox Valves
18Condenser Data
19Cooling Tower
Cells
Risers
20Cooling Tower
21Cooling Tower Fans
Cooling Tower Fans
Risers
Bypass
Intake Screen
22Cooling Tower Basin
Makeup
Bypass
Screen
23Cooling Tower Data
24Cooling Tower Fans Data
25Review Questions
What is the function of the Circulating Water
Pumps?
Click to Review
Which Circulating Water System Valve, when open,
allows a single Circulating Water Pump to supply
both condenser sides?
Click to Review
What component mounted in the channel between the
stop gate and the intake structure prevents
debris from entering the pump suction?
Click to Review
When you are sure you can correctly answer these
question click the Button to
continue
26Component Controls
- Circulating Water Pump Controls
- Cooling Tower Bypass Valve Controls
- Cooling Tower Fans Automatic Controls
27Circulating Water Pump Suction Valve Controls
B
A
A
B
28Circulating Water Pump Discharge Valve Controls
A
B
29Pump Cooling Water Supply
30Circulating Water Pump Start/Stop Controls
Start/Stop Soft Keys
31Pump Permits and Process Trips
32Pump Lockout/Tagout
Lockout Tagout
33Circulating Water Pump Discharge Valve Controls
34Cooling Tower Controls
35Cooling Tower Bypass Valve Control
Bypass Valve
36Cooling Tower Bypass Valve Control
37Cooling Tower Fan Controls
38Fan Remote Start/Stop Controls
39De-icing Control
40Review Questions
- How is each Circulating Water Pump motor operated
suction valve typically controlled? - How is each Circulating Water Pump motor operated
discharge valve typically controlled? - How is De-icing of the Cooling Tower performed?
Click to Review
Click to Review
Click to Review
When you are sure you can correctly answer these
question click the Button to
continue
41Process Control
42Cooling Tower Makeup Valve Control
Makeup Valve
Basin Level
Level Controller
43 Cooling Tower Basin Level Controller
44Auto/Manual Control
45Basin Level Setpoint
46Review Questions
- How is the Cooling Tower Makeup Valve actuated
and controlled? - What does the Cooling Tower Makeup Valve
Controller Output Control? - Where does the Cooling Tower Basin Level setpoint
come from?
Click to Review
Click to Review
Click to Review
When you are sure you can correctly answer these
question click the Button to
continue
47Circulating Water System Operation
- Startup Prerequisites
- System Startup
- Normal Operation
- System Shutdown
48Startup Prerequisites
49CIRCULATING WATER SYSTEM STARTUP
- Ensure Basin Level is established and maintained
- Ensure Circulating Water Pumps are ready for
Startup - Ensure system valves are properly aligned
- Ensure support systems are available for service.
50Prepare the Cooling Tower
51Establish Basin Level
Makeup Valve
Basin Level
Level Controller
52Circulating Water Pump
- Rack in pump and valve breakers
- OPEN each pumps suction valve
- Verify motor bearing oil levels are ok.
- Valve in instrument air and cooling water.
- CLOSE the circulating water cross-tie
Circulating Water Pumps
53Cooling Tower Fans
54Align System Valves
Waterbox Inlet Valves
Waterbox Outlet Valves
Discharge Cross-tie Valve
Suction Valves
55Open the Cooling Tower Bypass
56START the A circulating water pump
M
A
57Check Pump Data
58A
59Close the Cooling Tower Bypass
60Start Cooling Tower Fans
61At 50 Percent Load, prepare for and start the 2nd
Circ Water Pump
Cross-tie Valve
M
M
A
M
M
B
62Re-open the Discharge Cross-tie
Cross-tie Valve
63NORMAL OPERATION
64Monitor Circulating Water System process
variables from DCS displays.
65Check Cooling Tower Fans
66De-ice Cooling Tower If Required
67Circulating Water Pumps
68SHUT DOWN
69Shut Down One Circ. Pump
Cross-tie Valve
M
M
A
M
M
M
B
70Select the Cooling Tower Fan Stop Auto Sequence
71OPEN the Cooling Tower Bypass Valve
72STOP the Operating Circulating Water Pump
Cross-tie Valve
M
M
M
A
M
M
B
73Secure Cooling Tower Make-up
Makeup Valve
Level Controller
74Review Questions
- During preparation for Circulating Water
- System Startup, what are the four major
- steps involved?
- What position must the Circ. Water
- Discharge Cross-tie valve be in prior to
- starting the 2nd Circulating Water Pump?
- During Normal Operation, how is ice removed
- from the Cooling Tower?
Click to Review
Click to Review
Click to Review
When you are sure you can correctly answer these
question click the Button to
continue