Mercury Monitoring and Reporting Requirements under the MATS Rule PowerPoint PPT Presentation

presentation player overlay
1 / 31
About This Presentation
Transcript and Presenter's Notes

Title: Mercury Monitoring and Reporting Requirements under the MATS Rule


1
Mercury Monitoring and Reporting Requirements
under the MATS Rule
  • EPRI Conference---Louisville, KY
  • May 2012
  • Matthew Boze Robert Vollaro
  • USEPA, CAMD
  • http//www.epa.gov/airmarkets/workshops/index.html

2
Background
  • On February 16, 2012, EPA published the Mercury
    and Toxics Standards (MATS) rule (40 CFR 63,
    Subpart UUUUU), establishing national emissions
    limitations and work practice standards for
    certain hazardous air pollutants (HAP) emitted
    from coal-fired and oil-fired electric utility
    steam generating units.
  • Compliance with the rule is required
  • For existing units, by April 16, 2015
  • For new or reconstructed units, by April 16,
    2012, or upon startup (first-fire), whichever is
    later
  • Compliance must be demonstrated, by means of
    performance testing, no later than 180 days after
    the above dates
  • Mercury (Hg) is a regulated HAP under the rule.
  • For existing units, the rule specifies both heat
    input-based emission limits (lb/TBtu) and
    electrical output-based limits (lb/GWh) for Hg.

3
Background (contd)
  • Compliance with either Hg limit is acceptable for
    existing EGUs.
  • For new or reconstructed units, only electrical
    output-based emission limits are specified.
  • The magnitude of the applicable Hg emission limit
    depends on which subcategory the EGU is in.
    The general subcategories and applicable Hg
    limits (on a 30-day rolling average basis) are
  • Coal-fired units designed to burn coal with GCV
    8,300 Btu/lb
  • 1.2 lb/TBtu or 1.3 x 10-2 lb/GWh for existing
    units
  • 2.0 x 10-4 lb/GWh for new or reconstructed units
  • Coal-fired units designed to burn low-rank virgin
    coal (GCV lt 8,300 Btu/lb)
  • 4.0 lb/TBtu or 4.0 x 10-2 lb/GWh for existing
    units
  • 4.0 x 10-2 lb/GWh for new or reconstructed units
  • IGCC units
  • 2.5 lb/TBtu or 3.0 x 10-2 lb/GWh for existing
    units
  • 3.0 x 10-3 lb/GWh for new or reconstructed units

4
Background (contd)
  • Liquid oil-fired units
  • 2.0 x 10-1 lb/TBtu or 2.0 x 10-3 lb/GWh for
    existing units (continental)
  • 1.0 x 10-4 lb/GWh for new or reconstructed units
    (continental)
  • 4.0 x 10-2 lb/TBtu or 4.0 x 10-4 lb/GWh for
    existing units (non-continental)
  • 4.0 x 10-4 lb/GWh for new or reconstructed units
    (non-continental)
  • Solid oil-derived fuel (i.e., petroleum
    coke)-fired units
  • 2.0 x 10-1 lb/TBtu or 2.0 x 10 -3 lb/GWh for
    existing units
  • 2.0 x 10-3 lb/GWh for new or reconstructed units
  • Limited-use units in the liquid oil-fired units
    subcategory (lt 8 annual capacity factor, over a
    2-year period) are not subject to emissions
    limits for mercury
  • Existing units in the same subcategory at the
    same facility may use emissions averaging for Hg.
  • If the units in an averaging group are designed
    to burn coal with GCV 8,300 Btu/lb, there are
    alternate Hg limits for the group (1.0 lb/TBtu or
    1.1 x 10-2 lb/GWh on a 90-day rolling average).

5
Hg Compliance Options
  • Certain units can comply with the rule by
    qualifying as Low-Emitting EGUs (LEEs). This
    option may not be used for units with main stack
    and bypass stack configurations.
  • For Hg, a LEE is a unit that
  • Emits at less than 10 of the applicable
    emissions limit or
  • Has the potential to emit 29.0 lb of Hg per
    year
  • To qualify for LEE status, a demonstration test
    is required.
  • EPA Method 30B is used to measure Hg
    concentration for 30 unit operating days
  • Paired sorbent traps are used for the test.
  • Each pair of traps may be used for up to 10
    operating days
  • Additional data (i.e., stack gas flow rate, CO2
    or O2 concentration, moisture, electrical load,
    as applicable) are collected during the test.
    EPA reference methods or certified CEMS that meet
    Part 75 requirements are used to provide the flow
    rate, CO2, O2, or moisture data.
  • The additional data are used either to (1)
    convert the measured Hg concentrations to the
    units of the emission limit or (2) enable the
    EGUs potential annual Hg mass emissions to be
    calculated.
  • The rule includes special provisions for applying
    the LEE methodology to units that share a common
    stack and units that have multiple stack (or
    duct) exhaust configurations.
  • The 30 operating day demonstration test must be
    repeated at least once every 12 months, to show
    that the unit continues to qualify as a LEE for
    Hg.

6
Hg Compliance Options (contd)
  • What are the compliance requirements for EGUs
    that do not qualify as LEEs ?
  • A liquid oil-fired unit that does not qualify as
    a LEE for total HAP metals (including Hg),
    individual HAP metals (including Hg), or
    filterable PM must demonstrate compliance in
    accordance with 63.10000(c)(2)(ii), either by
  • Conducting an initial performance test and
    subsequent quarterly stack tests to show that the
    filterable PM emissions limit is met
  • Using a certified PM CEMS to demonstrate initial
    and on-going compliance with the filterable PM
    emission limit or
  • Conducting an initial performance test and
    subsequent annual stack tests to show that the
    filterable PM emissions limit is met, and using
    a PM CPMS to monitor continuous performance (with
    respect to an operating limit) in-between the
    annual stack tests.
  • A coal-fired unit, IGCC , or solid oil-derived
    fuel (i.e., petroleum coke)-fired unit that does
    not qualify as a LEE for Hg must continuously
    monitor Hg concentration using Hg CEMS or sorbent
    trap monitoring systems, in accordance with
    Appendix A of Subpart UUUUU.

7
Hg CEMS
  • Principle
  • Representative samples of flue gas are
    continuously extracted from the stack or duct
  • Particulate matter is removed (i.e., filtered)
    from the gas samples
  • Hg analyzer measures vapor phase Hg0 and Hg2
    (simultaneously or separately)
  • Typical Hg CEMS Components
  • Probe
  • PM filter
  • Sample conditioning
  • Sample transport (sample line and pump)
  • Gas analyzer (with or without converters)
  • Calibration gas system

8
Typical Hg CEMS
9
Hg CEMS (contd)
  • Types of systems
  • Dilution extractive wet basis
  • Extractive dry basis
  • Development of a quality assurance/quality
    control (QA/QC) program is required.

10
Sorbent Trap Monitoring Systems
  • Principle
  • Known volumes of flue gas are continuously
    extracted from the stack or duct through paired,
    in-stack sorbent traps. Vapor phase Hg is
    collected on the sorbent medium.
  • Typical sorbent medium is halogenated carbon
  • Paired sorbent traps are used for
    quality-assurance purposes and to ensure
    measurement precision
  • A pair of sorbent traps is typically used for 24
    to 168 hours (but may be used for up to 14
    operating days when the Hg concentration is very
    low), before being removed and analyzed.
  • Components
  • Dual trains w/sampling probes and paired sorbent
    traps. The sorbent traps have three sections
    (1) main sample collection section (2)
    breakthrough section and (3) section spiked with
    a known mass of Hg0 , for QA/QC .
  • Moisture removal system
  • Vacuum pump
  • Sample gas flow meter

11
Typical Sorbent Trap Monitoring System---PS 12B
12
Sorbent Trap Monitoring Systems (contd)
Probe
3-section sorbent traps
13
Sorbent Trap Monitoring Systems (contd)
  • The sorbent trap system must be operated and
    maintained according to Performance Specification
    12B in 40 CFR Part 60, Appendix B.
  • Leak checks must be performed (before and after
    sampling)
  • Paired sorbent trap consistency/agreement is
    required
  • A minimum recovery of the spiked Hg0 in the
    third section is required
  • Sample recovery techniques include acid leaching,
    digestion, thermal desorption (see next slide).
  • Analytical methods include UV atomic
    fluorescence, UV atomic absorption, and X-ray
    fluorescence
  • Analyzer calibration is required
  • Development of a QA/QC program is also required.

14
Thermal Desorption System
  • Thermal desorption system allows rapid, on-site
    measurement of mercury in sorbent traps
  • Alternative to traditional wet chemical analysis
    methods

15
Monitoring System Certification
  • Each Hg CEMS or sorbent trap monitoring system
    must be initially certified.
  • For Hg CEMS, the following certification tests
    are required
  • 7-day calibration error test, using elemental or
    oxidized Hg standards
  • Linearity check, using elemental Hg standards
  • 3-level system integrity check, using oxidized Hg
    standards
  • Cycle time test, using elemental or oxidized Hg
    standards. This test is not required for
    integrated batch sampling-type CEMS
  • Relative accuracy test audit (RATA). Note that a
    bias test is not required. Allowable reference
    methods for the RATA include EPA Methods 29, 30A,
    30B, and ASTM D6784-02 (the Ontario Hydro Method)
  • All Hg calibration gas standards must be
    traceable to the National Institute of Standards
    and Technology (NIST). EPA , in cooperation with
    industry, NIST, and outside consultants, has
    developed interim traceability protocols. These
    are cited in Subpart UUUUU, Appendix A, sections
    3.1.4 and 3.1.5.

16
Monitoring System Certification (contd)
  • For sorbent trap monitoring systems, only a RATA
    is required.
  • During the RATA, the monitoring system must be
    operated according to Performance Specification
    12B
  • The sorbent material must be the same type that
    is used for daily operation of the system
  • The sorbent traps used for the RATA may be
    smaller than those used for daily operation
  • The allowable breakthrough in the second section
    of the traps depends on the Hg concentration
    level in the stack gas (see Footnote 1 in Table
    3, below).
  • The required tests and performance specifications
    that must be met for initial certification of Hg
    CEMS are summarized in Table 1.
  • The RATA specifications for the initial
    certification of a sorbent trap monitoring system
    are the same as those shown in Table 1.

17
Monitoring System Certification(contd)
  • Table 1 Certification Requirements for Hg CEMS

For this required certification test..... The main performance specification1 is..... The alternate performance specification1 is..... And the conditions of the alternate specification are.....
7-day calibration error test2 R - A 5.0 of span value, for both the zero and upscale gases, on each of the 7 days R - A 1.0? µg/scm The alternate specification may be used on any day of the test.
Linearity check3 R - Aavg 10.0 of the reference gas concentration at each calibration gas level R - Aavg 0.8 µg/scm The alternate specification may be used at any gas level
3-level system integrity check4 R - Aavg 10.0 of the reference gas concentration at each calibration gas level R - Aavg 0.8 µg/scm The alternate specification may be used at any gas level
RATA 20.0 RA RMavg - Cavg 1.0 µg/scm RMavg lt 5.0 µg/scm
Cycle time test5 15 minutes ----------------------------- ----------------------------
18
On-going Quality-Assurance
  • To ensure that certified Hg CEMS and sorbent trap
    monitoring systems continue to provide accurate
    data, the systems are subject to on-going
    quality assurance and quality control (QA/QC)
    requirements.
  • For Hg CEMS, the following QA tests are required
  • Daily calibration error tests , using elemental
    or oxidized Hg standards
  • Weekly single-point system integrity checks ,
    using oxidized Hg standards
  • Quarterly linearity checks, using elemental Hg
    standards or 3-level system integrity checks
    using oxidized Hg standards
  • Annual RATAs
  • For sorbent trap monitoring systems
  • The system must be operated and maintained
    according to PS 12B
  • Annual RATAs are required
  • Quarterly calibration of the gas flow meter and
    auxiliary equipment is required
  • The on-going QA/QC requirements and acceptance
    criteria for Hg CEMS and sorbent trap monitoring
    systems are summarized in Tables 2 and 3,
    respectively.

19
On-going Quality Assurance (contd)
  • Table 2 On-going QA /QC Requirements for Hg
    CEMS
  • 1 Weekly means once every 7 operating days
  • 2 NIST-traceable Hg
    standards are required

Perform this type of QA test.... At this frequency.... With these qualifications and exceptions.... Acceptance criteria.
Calibration error test Daily Use either a mid- or high- level gas Use either elemental or oxidized Hg2 Calibrations are not required when the unit is not in operation. R - A 5.0 of span value or R - A 1.0?µg/scm
Single-level system integrity check Weekly1 Use oxidized Hg ---either mid- or high-level Not required if daily calibrations are done with a NIST-traceable source of oxidized Hg R - Aavg 10.0 of the reference gas value or R - Aavg 0.8 µg/scm
20
On-going Quality Assurance (contd)
  • Table 2 On-going QA /QC Requirements for Hg
    CEMS (contd)

Perform this QA test.... At this frequency With these qualifications and exceptions.... Acceptance criteria.
Linearity check or 3-level system integrity check Quarterly5 Required in each QA operating quarter3 ---and no less than once every 4 calendar quarters 168 operating hour grace period available Use elemental Hg for linearity check4 Use oxidized Hg for system integrity check4 R - Aavg 10.0 of the reference gas value, at each calibration gas level or R - Aavg 0.8 µg/scm
RATA Annual6 Test deadline may be extended for non-QA operating quarters, up to a maximum of 8 quarters from the quarter of the previous test. 720 operating hour grace period available 20.0 RA or RMavg - Cavg 1.0 µg/scm, if RMavg lt 5.0 µg/scm
21
On-going Quality Assurance (contd)
  • Table 3 Normal Operation and QA/QC for Sorbent
    Trap Systems (PS 12B)
  • 1 For the RATA, Section 2 breakthrough depends
    on CHg stack gas Hg concentration. Allowable
    breakthrough is 10 of Section 1 mass if CHg is
    gt 1 µg/m3 20 of Section 1 mass if CHg is gt
    0.5 and 1 µg/m3 50 of Section 1 mass if CHg
    is gt 0.1 and 0.5 µg/m3. There is no
    breakthrough criterion if CHg is lt 0.1 µg/m3 .

QA/QC test or specification Acceptance criteria Frequency Consequences if not met
Pre-monitoring leak check 4 of target sampling rate Prior to monitoring Monitoring must not commence until the leak check is passed.
Post-monitoring leak check 4 of average sampling rate After monitoring Invalidate the data from the paired traps or, if certain conditions are met, report adjusted data from a single trap (PS 12B, Section 12.8.1.3).
Ratio of stack gas flow rate to sample flow rate Hourly ratio may not deviate from the reference ratio by more than 25. Every hour throughout monitoring period Invalidate the data from the paired traps or, if certain conditions are met, report adjusted data from a single trap (PS 12B, Section 12.8.1.3).
Sorbent trap section 2 breakthrough 5 of Section 1 Hg mass (for daily operation)1 Every sample Invalidate the data from the paired traps or, if certain conditions are met, report adjusted data from a single trap (PS 12B, Section 12.8.1.3).
22
On-going Quality Assurance (contd)
  • Table 3 Normal Operation and QA/QC for Sorbent
    Trap Systems (PS 12B) (contd)

QA/QC test or specification Acceptance criteria Frequency Consequences if not met
Paired sorbent trap agreement 10 Relative Deviation (RD) if the average concentration is gt 1.0 µg/m3 Every sample Either invalidate the data from the paired traps or report the results from the trap with the higher Hg concentration.
Paired sorbent trap agreement 20 RD if the average concentration is 1.0 µg/m3 Every sample Either invalidate the data from the paired traps or report the results from the trap with the higher Hg concentration.
Paired sorbent trap agreement Results also acceptable if difference between paired traps is 0.03 µg/m3 Every sample Either invalidate the data from the paired traps or report the results from the trap with the higher Hg concentration.
Spike Recovery Study Average recovery between 85 and 115 for each of the 3 spike concentration levels Prior to analyzing field samples and prior to use of new sorbent media Field samples must not be analyzed until the percent recovery criteria has been met.
Multipoint analyzer calibration Each analyzer reading within 10 of true value and r2 0.99 On the day of analysis, before analyzing any samples Recalibrate until successful
Analysis of independent calibration standard. Within 10 of true value Following daily calibration, prior to analyzing field samples Recalibrate and repeat independent standard analysis until successful.
Spike recovery from section 3 of both sorbent traps 75125 of spike amount Every sample Invalidate the data from the paired traps or, if certain conditions are met, report adjusted data from a single trap (PS 12B, Section 12.8.1.3).
23
On-going Quality Assurance (contd)
  • Table 3 Normal Operation and QA/QC for Sorbent
    Trap Systems (PS 12B) (contd)
  • 2 Annually means once every four QA operating
    quarters. Limited extensions of the RATA
    deadline are allowed for non-QA quarters---the
    maximum allowable extension is 8 calendar
    quarters from the previous RATA. A 720
    operating hour grace period is available.

QA/QC test or specification Acceptance criteria Frequency Consequences if not met
Relative Accuracy RA 20.0 of RM mean value or if RM mean value 5.0 µg/scm, absolute difference between RM and sorbent trap monitoring system mean values 1.0 µg/scm RA specification must be met for initial certification and annually2 thereafter Data from the system are invalid until a RATA is passed.
Gas flow meter calibration An initial calibration factor (Y) has been determined at 3 settings for mass flow meters, initial calibration with stack gas has been performed. For subsequent calibrations, Y within 5 of average value from the most recent 3-point calibration At 3 settings prior to initial use and at least quarterly at one setting thereafter Recalibrate meter at 3 settings to determine a new value of Y.
Temperature sensor calibration Absolute temperature measured by sensor within 1.5 of a reference sensor Prior to initial use and at least quarterly thereafter Recalibrate sensor may not be used until specification is met.
Barometer calibration Absolute pressure measured by instrument within 10 mm Hg of reading with a NIST-traceable barometer Prior to initial use and at least quarterly thereafter Recalibrate instrument may not be used until specification is met.
24
Hg Emissions Reporting
  • For units that qualify as LEEs for Hg, the
    results of all 30-day demonstration tests must be
    submitted to EPAs WebFIRE database, using the
    Electronic Reporting Tool (ERT). The results
    must be submitted within 60 days after completing
    each test.
  • For units that continuously monitor Hg emissions
  • A monitoring plan must be developed and
    maintained.
  • The Hg CEMS or sorbent trap monitoring system(s)
    and any required additional monitoring systems
    must be represented in the monitoring plan.
  • Monitoring plan data must be submitted to EPA
    electronically and updated when necessary, using
    the Emissions Collection and Monitoring Plan
    System (ECMPS) Client Tool.
  • Hourly Hg concentration data must be reported
    electronically using the ECMPS Client Tool.
  • Data from Hg CEMS are reduced to hourly averages
  • For sorbent trap monitoring systems, the Hg
    concentration obtained from the analysis of a
    pair of traps is reported for each hour of the
    data collection period.

25
Hg Emissions Reporting (contd)
  • Quarterly electronic reporting of Hg emissions is
    required, no later than 30 days after the end of
    each calendar quarter.
  • Hourly records of any additional data needed to
    convert Hg concentration to units of the emission
    standard (e.g., stack gas flow rate and/or
    moisture content, CO2 or O2 concentration,
    electrical load) must be included in the
    electronic quarterly reports.
  • The additional monitoring system(s) used to
    convert Hg concentration to units of the standard
    must meet the requirements of 40 CFR Part 75.
  • For sorbent trap monitoring systems, certain
    other hourly data must be reported (i.e., sample
    flow rate, gas flow meter reading, and the ratio
    of stack gas flow rate to sample flow rate).
  • The data acquisition and handling system (DAHS)
    must be programmed to provide an hourly data
    stream in the units of the applicable Hg emission
    standard (lb/TBtu or lb/GWh).
  • Hg emission rates are calculated only for
    operating hours in which valid data are obtained
    for all parameters in the applicable equation(s).
    For the purposes of Subpart UUUUU, Part 75
    substitute data are not considered to be valid
    data.

26
Hg Emissions Reporting (contd)
  • Operating hours in which a valid Hg emission rate
    is not obtained are counted as hours of
    monitoring system downtime.
  • Only unadjusted monitoring data are used to
    calculate Hg emission rates. Bias adjustment
    factors (BAFs) are not applied to any of the
    parameters.
  • The results of all required certification and QA
    tests of Hg CEMS, sorbent trap monitoring
    systems, and the additional monitoring system(s)
    used to convert Hg concentration to units of the
    standard must be reported electronically, using
    the ECMPS Client Tool.
  • For Hg CEMS and sorbent trap monitoring systems,
    RATA results and test details must also be
    submitted to the WebFIRE database via ERT, within
    60 days after completing each test.
  • Compliance with the 30 (or in some cases, 90)
    operating day rolling average Hg emission rates
    is assessed in the semiannual reports required
    under 63.10031.

27
Future Changes to ECMPS for Hg
  • EPA is reviewing the Hg reporting schema and
    reporting instructions (March 5, 2008) drafted
    for CAMR. This will be our starting point for
    integrating continuous Hg data into ECMPS.
  • Structurally, that schema is compatible with the
    MATS Hg continuous monitoring and reporting
    requirements
  • New method of determination codes (MODC) will be
    needed to handle the differences between the
    CAMR rule and the MATS rule.
  • Exclusion of Startup and Shutdown hours
  • Handling of invalid data hours No Substitute
    Data
  • No Bias Adjustments
  • Etc.

28
Future Changes to ECMPS for Hg CEMS
  • Monitoring Plan will have to reactivate the
    ltCalibrationStandardgt record for reporting the
    basis of daily calibrations (i.e., Hg0 or Hg2 )
  • Add 3-level System Integrity Check to the QA
    schema
  • Add the ltWeeklySystemIntegrityDatagt record back
    to the Emissions schema. Program to check for
    this on an operating day basis when Hg0 is used
    in daily calibrations.
  • Hourly Hg concentration measurements to be
    recorded in MHV records
  • Hourly Hg emission rate data to be reported in
    DHV records

29
Future Changes to ECMPS for Hg Sorbent Trap
Monitoring Systems
  • Add the QA record structure for reporting the
    required Gas Flow Meter Calibrations, GFM
    temperature sensor barometer calibration checks
  • Create special emissions data schema to support
    sorbent trap monitoring
  • Hourly GFM Data record
  • Sampling Train Data record
  • Sample Train Data would contain all the
    information necessary to determine the quality
    assurance status of each sampling period.
  • Spike Recovery
  • Breakthrough
  • Trap Agreement
  • Stack Flow to Sample Rate Ratio Check
  • Leak Check

30
Future Changes to ECMPS for Hg Sorbent Trap
Monitoring Systems (continued)
  • Concentration determined from a sampling period
    would be entered into the appropriate hourly MHV
    records
  • This allows the data to be used to determine
    hourly emission rates and treated like Hg CEMS
    data for compliance averaging.
  • Also allows for a sorbent trap systems to be used
    as a backup to Hg CEMS, (if desired to keep data
    loss at a minimum).
  • Hourly Hg emission rate data to be reported in
    DHV records

31
ECMPS Process Forward
  • EPA is committed to ensuring that the continuous
    monitoring data for MATS is integrated into ECMPS
    in a manner that is consistent with the process
    currently used for Part 75 reporting.
  • Also, we will be working on more specific draft
    documents on the specific plans as they relate to
    MATS ECMPS monitoring requirements
  • Reporting Schema
  • Reporting Instructions
  • Check Specifications
  • Stakeholder meetings
  • Goal is to have ECMPS and your DAHS programming
    updated, tested and ready to go by 1Q2015
Write a Comment
User Comments (0)
About PowerShow.com